Rockwell Automation Publication 2097-UM001D-EN-P - November 2012
Chapter 4
Connecting the Kinetix 300 Drive System
Ethernet Cable Connections
This procedure assumes you have your Logix Ethernet/IP module and
Kinetix 300 drive mounted and ready to connect the network cables.
The EtherNet/IP network is connected by using the Port 1 connector. See
to locate the Ethernet connector on your Kinetix 300 drive. See the
figure below to locate the connector on your Logix communication module.
Shielded Ethernet cable is available in lengths up to 78 m (256 ft). However, the
total length of Ethernet cable connecting drive-to-drive, drive-to-controller, or
drive-to-switch must not exceed 100 m (328 ft).
If the entire channel is constructed of stranded cable (no fixed cable), then this is
the equation for calculating maximum length:
Maximum Length = (113-2N)/y, meters
where N = the number of connections in the channel
and y = the loss factor compared to fixed cable (typically 1.2…1.5).
Figure 49 - CompactLogix Ethernet Port Location
The Port 1 Ethernet connection is used for connecting to a web browser and
configuring your Logix module.
Figure 50 - Ethernet Wiring Example - External Switch
CompactLogix
L23E
Ethernet Port
CompactLogix Controller Platform
1769-L23E-QB1B Shown
CompactLogix
L23E
00
300
00
300
CompactLogix Controller Platform
1769-L23E-QB1B Shown
Personal Computer
1783-EMS08T
Stratix 6000
Switch
Kinetix 300 Drives
Содержание Kinetix 300
Страница 4: ...4 Rockwell Automation Publication 2097 UM001D EN P November 2012 Summary of Changes Notes...
Страница 18: ...18 Rockwell Automation Publication 2097 UM001D EN P November 2012 Chapter 1 Start Notes...
Страница 188: ...188 Rockwell Automation Publication 2097 UM001D EN P November 2012 Appendix A Interconnect Diagrams Notes...
Страница 216: ...216 Rockwell Automation Publication 2097 UM001D EN P November 2012 Appendix D MicroLogix Explicit Messaging Notes...
Страница 229: ...Kinetix 300 EtherNet IP Indexing Servo Drives User Manual...
Страница 230: ......