Rockwell Automation Publication 2097-UM001D-EN-P - November 2012
41
Kinetix 300 Drive Connector Data and Feature Descriptions
Chapter 3
Control Signal Specifications
This section provides a description of the Kinetix 300 drive I/O (IOD),
communication, shunt resistor and DC bus (BC), and back-up power (BP)
connectors.
Digital Inputs
The Kinetix 300 drive has twelve digital inputs. They can be used for travel limit
switches, proximity sensors, push buttons, and hand shaking with other devices.
Each input can be assigned an individual de-bounce time via MotionView
software or Explicit Messaging.
The inputs are separated into three groups: A, B, and C. Each group has four
inputs and share one common: ACOM, BCOM, and CCOM respectively.
Travel limit switches, the inhibit/enable input, and registration input have
dedicated inputs as shown in
. For more information on the overtravel
inputs, see Appendix E on
.
Table 9 - Digital Input Assignments
You can configure the inputs listed as N/A for any of these functions.
•
Abort Homing
•
Abort Index
•
Start Homing
•
Start Index
•
Fault Reset
•
Home Sensor
•
Index Select
Digital Input
Function
IN_A1
Negative travel limit switch
IN_A2
Positive travel limit switch
IN_A3
Inhibit/enable input
IN_A4
N/A
IN_B1
N/A
IN_B2
N/A
IN_B3
N/A
IN_B4
N/A
IN_C1
N/A
IN_C2
N/A
IN_C3
Registration input sensor
IN_C4
N/A
Содержание Kinetix 300
Страница 4: ...4 Rockwell Automation Publication 2097 UM001D EN P November 2012 Summary of Changes Notes...
Страница 18: ...18 Rockwell Automation Publication 2097 UM001D EN P November 2012 Chapter 1 Start Notes...
Страница 188: ...188 Rockwell Automation Publication 2097 UM001D EN P November 2012 Appendix A Interconnect Diagrams Notes...
Страница 216: ...216 Rockwell Automation Publication 2097 UM001D EN P November 2012 Appendix D MicroLogix Explicit Messaging Notes...
Страница 229: ...Kinetix 300 EtherNet IP Indexing Servo Drives User Manual...
Страница 230: ......