Rockwell Automation Publication 1753-IN001C-EN-P - June 2010

Fuse (external)

24V DC power: 10 A (time-lag)

Enclosure type rating

Meets IP20

Width, approx.

257 mm (10.1 in.) 

Height, approx.

114 mm (4.49 in.) including latch

Depth, approx.

66 mm (2.60 in.) including grounding bolt

Weight

1.2 kg (2.64 lb)

Digital Inputs

Number of inputs

20 (not electrically isolated)

On-state

Voltage: 15…30V DC

Current consumption: 

≥ 

2 mA @ 15V

                                           7.5 mA @ 30V

Off-state

Voltage: 5V DC max
Current consumption: 1.5 mA max (1 mA @ 5V)

Switching point

typically 7.5V

Supply

5 x 20V / 100 mA @ 24V short-circuit proof

Digital Outputs

Number of outputs

8 (not electrically isolated)

Output voltage range

18.4…26.8V

Output current

Channels 1…3 and 5…7: 0.5 A @ 60 °C (140 °F)

Channels 4 and 8: 1 A @ 60 °C (140 °F); 2 A @ 50 °C (122 °C)

Surge current per channel

1 A for 10ms @ 1Hz (Channels 1…3 and 5…7)

4 A for 10ms @ 1Hz (Channels 4 and 8)

Current load, min

2 mA per channel

On-state voltage drop

2.0V DC max @ 2 A

Off-state leakage current

 1 mA max @ 2V

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and 
Grounding Guidelines, publication

 1770-4.1

.

Technical Specifications – GuardPLC 1600 Controllers

Attribute

1753-L28BBB-M, 1753-L28BBB-P

Содержание GuardPLC 160

Страница 1: ...rtant User Information 2 About the GuardPLC 1600 Controller 3 General Safety 3 Install the Controller 4 Mount the Controller 5 Ground the Controller 5 Wire the Controller 6 Make Communication Connecti...

Страница 2: ...Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of in...

Страница 3: ...system and shall be trained in using the system ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines wh...

Страница 4: ...es This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately...

Страница 5: ...lines refer to the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 IMPORTANT For effective cooling mount the controller following these guidelines Mount the controller horiz...

Страница 6: ...C under normal conditions and under single fault conditions A PELV supply has the same rating and is connected to protected earth The supply voltage is connected via a 4 pin connector that accommodate...

Страница 7: ...9 10 5 L L DO 6 2A 7 8 11 12 COMM1 MODBUS RS 485 24V DC COMM2 COMM3 RUN 24 V DC GuardPLC Ethernet 10 100 BaseT PROG ERROR FAULT FORCE BL OSL PROFIBUS 3 4 3 4 1753 L28BBBM 20 DC Inputs 8 DC Outputs 1...

Страница 8: ...n number 1753 UM001 1 2 3 4 5 6 1 2 3 4 1 L L L L L L DO 2 2A 3 4 1 LS LS LS LS LS L D1 2 3 4 5 6 13 14 15 16 17 18 5 L D1 6 7 8 19 20 21 22 23 24 9 L D1 10 11 12 25 26 27 28 29 30 13 L D1 14 15 16 31...

Страница 9: ...input 1 15 2 Digital input 2 16 3 Digital input 3 17 4 Digital input 4 18 L Reference pole 19 LS Sensor supply for inputs 5 8 20 5 Digital input 5 21 6 Digital input 6 22 7 Digital input 7 23 8 Digita...

Страница 10: ...he E stop off switches is pressed in the example above Safety related Digital Outputs The controller has eight digital outputs DO1 DO8 whose status is indicated via status indicators An output is in a...

Страница 11: ...he power supply input it is strictly recommended to use 1 and 6 for outputs 1 4 only and 7 and 12 for outputs 5 8 only EMC testing was performed in this manner Terminal Number Designation Function Cur...

Страница 12: ...g software Connectors 1 and 2 are on the bottom side on the left Connectors 3 and 4 are on the top side on the left All four connectors and the GuardPLC processor are connected together by an internal...

Страница 13: ...n assignments of the D shell connector are listed in this table IP Address and System ID SRS A transparent label provided with the controller can be used to note the IP address and system ID SRS The d...

Страница 14: ...9 5 mm 0 375 in To reset press and hold the push button for 20 seconds while rebooting the device by cycling power Pressing the Reset push button during operation has no affect With activation of the...

Страница 15: ...perature Tests The temperature of the controller is automatically and continuously monitored The alarm is triggered by the temperature conditions described in this table Voltage Level System Condition...

Страница 16: ...ime All system outputs will be reset and the controller ceases all hardware and software tests The controller can only be restarted by a command from the programming software Off No errors are detecte...

Страница 17: ...KB max application data memory Watchdog min 10 ms Safety time min 20 ms Current consumption 8 A max with max load 0 5 A idle current Operating voltage 24V DC 15 to 20 wss 15 from a power supply with p...

Страница 18: ...ly 7 5V Supply 5 x 20V 100 mA 24V short circuit proof Digital Outputs Number of outputs 8 not electrically isolated Output voltage range 18 4 26 8V Output current Channels 1 3 and 5 7 0 5 A 60 C 140 F...

Страница 19: ...t Ea unpackaged shock 15 g Relative humidity IEC 60068 2 30 Test Db unpackaged damp heat 10 95 noncondensing Emissions CISPR 11 Group 1 Class A ESD Immunity IEC 61000 4 2 6 kV contact discharges 8 kV...

Страница 20: ...Industrial Control Equipment certified for US and Canada See UL File E65584 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2...

Отзывы: