Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Environment and Enclosure
Install the Controller
Follow these steps to install the GuardPLC 1600 controller.
1.
Mount the controller to a DIN rail.
2.
Ground the controller.
3.
Wire the controller.
4.
Make communication connections.
This publication describes these steps in detail.
ATTENTION:
This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in
IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties
with electromagnetic compatibility in residential and other environments due
to conducted as well as radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
•
Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication
1770-4.1
, for additional installation requirements.
•
NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by different types of enclosure.