The LED indicators on the front face provide diagnositic
information. In some cases, the PWR/Fault indicator blinks
only red . In some cases, the PWR/Fault indicator is
green and fl ashes red . The fl ash sequence pauses
2 sec before repeating.
Die LEDs auf der Front zeigen den Gerätezustand an. Zur
Fehlerdiagnose werden Blinkfrequenzen angezeigt. Je
nach Fehlerart blinkt die PWR/Fault LED nur rot oder
abwechselnd rot und grün . Die Blinksequenz wird
nach 2 Sekunden Pause wiederholt.
Las LED frontales indican el estado del dispositivo. Para
el diagnóstico de los errores se indican frecuencias de
parpadeo. Según el tipo de error parpadea la LED PWR/
Fault solo en rojo o alternativamente en rojo y en
verde . La secuencia de parpadeo se repite después de
2 segundos de pausa.
Diagnostics
Diagnose
Diagnósticos
10000335607 ver 00, Dwg. No: 95302416, Issue 1, EO: 0412, August 2012
Copyright ©2012 Rockwell Automation, Inc. All Rights Reserved. Printed in Germany.
PWR / FAULT
FAULT MODE / FEHLERMODI / MODO DE ERRORES
RESET / RÜCKSTELLUNG / RESET
Non-recoverable fault.
A) If unit comes back healthy: check potential sources for EMC distrubance in the related system around GLP
B) If unit remains in same fault state: Potential internal fault.
Cycle power
Align Proximity Sesnors and cyle power
Remove fault and cycle power
Self test of single wire safety outputs L11, L61 failed: Check connections of L11 and L61 against shorts to 24V or 0V and cross loop shorts.
If unit remains in same fault state: Potential internal fault.
Speed monitoring fault. Both Proximity inputs are LOW simultaneously: Potential missalignment of Proximity Sensors e.g. exceeding max.
sensing distance, both sensors facing a space
Remove fault and cycle power
Self test of X14, X24 failed: Check connections of X14 and X24 against shorts to 24V or 0V and cross loop shorts.
If unit remains in same fault state: Potential internal fault.
Remove fault and cycle power
Remove fault and cycle power
Proximity Input fault, stuck at LOW or HIGH: Potential damage or missalignment of Proximity Sensors e.g. exceeding max. sensing distance,
both sensors facing a space
Remove fault and cycle power
Self test of 51, L61 failed: Check guard locking connections of 51 and L61 against shorts to 24V or 0V and cross loop shorts.
If unit remains in same fault state: Potential internal fault.
Remove fault and cycle power
Over voltage
Remove fault and cycle power
1x
2x
3x
4x
5x
6x
7x
8x
9x
10x
PWR / FAULT
STATUS / STATUS / E STADO
RESET / RÜCKSTELLUNG / RESET
Normal Operation, no fault
Cycle power
The actual configuration, rotary switches and jumpers do not match the EEPROM. Relay will function normally.
Configuration has been changed during operation:
Adjust rotary switch back to target position and reconfigure
jumpers
Lock command/Reset has been initated while safety input circuit S12, S22 open
-
Close safety circuit and Reset again
-
Speed exceeded maximum speed limit SL2
Slow down speed below, speed limit SL2 and sequentially
press S54 and S44
Slow down speed below, speed limit SL2 and sequentially
press S54 and S44
Speed exceed maximum speed limit SL1
2x
3x
4x
5x