The LED indicators on the front face provide diagnositic 
information.  In some cases, the PWR/Fault indicator blinks 
only red         .  In some cases, the PWR/Fault indicator is 
green         and fl ashes red        .  The fl ash sequence pauses 
2 sec before repeating.

Die LEDs auf der Front zeigen den Gerätezustand an. Zur 
Fehlerdiagnose werden Blinkfrequenzen angezeigt. Je 
nach Fehlerart blinkt die PWR/Fault LED nur rot           oder 
abwechselnd rot         und grün        . Die Blinksequenz wird 
nach 2 Sekunden Pause wiederholt.

Las LED frontales indican el estado del dispositivo. Para 
el diagnóstico de los errores se indican frecuencias de 
parpadeo. Según el tipo de error parpadea la LED PWR/
Fault solo en rojo         o alternativamente en rojo         y en 
verde        . La secuencia de parpadeo se repite después de 
2 segundos de pausa.

Diagnostics

Diagnose

Diagnósticos

10000335607 ver 00, Dwg. No: 95302416, Issue 1, EO: 0412, August 2012  

Copyright ©2012 Rockwell Automation, Inc. All Rights Reserved. Printed in Germany. 

PWR / FAULT

FAULT MODE / FEHLERMODI / MODO DE ERRORES

RESET / RÜCKSTELLUNG /  RESET

Non-recoverable fault. 
A) If unit comes back healthy: check potential sources for EMC distrubance in the related system around GLP
B) If unit remains in same fault state: Potential internal fault.

Cycle power 

Align Proximity Sesnors and cyle power

Remove fault and cycle power

Self test of single wire safety outputs L11, L61 failed: Check connections of L11 and L61 against shorts to 24V or 0V and cross loop shorts. 
If unit remains in same fault state: Potential internal fault. 

 Speed monitoring fault. Both Proximity inputs are LOW simultaneously:  Potential missalignment of Proximity Sensors e.g. exceeding max.
sensing distance, both sensors facing a space

Remove fault and cycle power 

Self test of X14, X24 failed: Check connections of X14 and X24 against shorts to 24V or 0V and cross loop shorts. 
If unit remains in same fault state: Potential internal fault. 

Remove fault and cycle power 

Remove fault and cycle power

Proximity Input fault, stuck at LOW or HIGH: Potential damage or missalignment of Proximity Sensors e.g. exceeding max. sensing distance, 
both sensors facing a space 

Remove fault and cycle power 

Self test of 51, L61 failed: Check guard locking connections of 51 and L61  against shorts to 24V or 0V and cross loop shorts. 
If unit remains in same fault state: Potential internal fault. 

Remove fault and cycle power

Over voltage

Remove fault and cycle power 

1x

2x

3x

4x

5x

6x

7x

8x

9x

10x

PWR / FAULT

STATUS / STATUS / E STADO

RESET / RÜCKSTELLUNG /  RESET

Normal Operation, no fault 

Cycle power 

The actual configuration, rotary switches and jumpers do not match the EEPROM. Relay will function normally.

Configuration has been changed during operation: 
Adjust rotary switch back to target position and reconfigure
jumpers

Lock command/Reset has been initated while safety input circuit S12, S22 open

-

Close safety circuit and Reset again 

-

Speed exceeded maximum speed limit SL2 

Slow down speed below, speed limit SL2 and sequentially 
press S54 and S44 
Slow down speed below, speed limit SL2 and sequentially 
press S54 and S44 

Speed exceed maximum speed limit SL1

2x

3x

4x

5x