Specifications
A–2
Publication 1794-6.5.15 – December 1998
Specifications – 1794-ID2 2 Input Incremental Encoder Module
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Vibration
0 to 55
o
C (32 to 131
o
F) Note: Do not connect
maximum input voltage simultaneously to all
inputs if the module ambient temperature is
expected to exceed 40
o
C.
–25 to 70
o
C (–13 to 158
o
F)
5 to 90% noncondensing (operating)
5 to 80% noncondensing (nonoperating)
15 g peak acceleration, 11(+1)ms pulse width
Tested 2 g @ 10–500Hz per IEC 68-2-6
Input Conductors
Wire
Category
Length (max)
Belden 8761
2
1
1000ft (304.8m)
Agency Certification
(when product is marked)
•
CUL certified
•
CUL listed – Class I, Division 2
Groups A, B, C, D
•
UL listed
•
CE marked for all applicable directives
Installation Instruction
Publication 1794-5.63
1 Use this conductor category information for planning conductor routing . Refer to publication
1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise Immunity.”