background image

Publication 1794-IN039F-EN-P - November 2011

Installation Instructions

FLEX™ I/O Isolated Input/Output Analog 
Module

Cat. No. 1794-IF2XOF2I 

      

Important User Information

Solid state equipment has operational characteristics differing from those of 
electromechanical equipment. Safety Guidelines for the Application, Installation and 
Maintenance of Solid State Controls (Publication 

SGI-1.1

 available from your local Rockwell 

Automation sales office or online at 

http://www.rockwellautomation.com/literature/

describes some important differences between solid state equipment and hard-wired 
electromechanical devices. Because of this difference, and also because of the wide variety of 
uses for solid state equipment, all persons responsible for applying this equipment must 
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or 
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. 
Because of the many variables and requirements associated with any particular installation, 
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the 
examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of 
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of 
Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an 
explosion in a hazardous environment, which may lead to personal injury or 
death, property damage, or economic loss.

ATTENTION

Identifies information about practices or circumstances that can lead to 
personal injury or death, property damage, or economic loss. Attentions 
help you:

identify a hazard

avoid a hazard

recognize the consequence

IMPORTANT

Identifies information that is critical for successful application and understanding 
of the product.

SHOCK HAZARD

Labels may be located on or inside the equipment (for example, drive or 
motor) to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be located on or inside the equipment (for example, drive or 
motor) to alert people that surfaces may be dangerous temperatures.

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial 
environment, in overvoltage Category II applications (as defined in IEC 
publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment 
according to IEC/CISPR Publication 11. Without appropriate precautions, 
there may be potential difficulties ensuring electromagnetic compatibility 
in other environments due to conducted as well as radiated disturbance.

This equipment is supplied as open-type equipment. It must be mounted 
within an enclosure that is suitably designed for those specific 
environmental conditions that will be present and appropriately designed 
to prevent personal injury resulting from accessibility to live parts. The 
enclosure must have suitable flame-retardant properties to prevent or 
minimize the spread of flame, complying with a flame spread rating of 
5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the 
enclosure must be accessible only by the use of a tool. Subsequent 
sections of this publication may contain additional information regarding 
specific enclosure type ratings that are required to comply with certain 
product safety certifications.

In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines,

publication 

1770-4.1

, for additional installation requirements.

NEMA Standard 250 and IEC 60529, as applicable, for explanations 

of the degrees of protection provided by enclosures.

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause 
internal damage and affect normal operation. Follow these guidelines 
when you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not 
in use.

WARNING

If you insert or remove the module while backplane power is on, an 
electrical arc can occur. This could cause an explosion in hazardous 
location installations. Be sure that power is removed or the area is 
nonhazardous before proceeding.

WARNING

If you connect or disconnect wiring while the field side power is on, an 
electrical arc can occur. This could cause an explosion in hazardous 
location installations. Be sure that power is removed or the area is 
nonhazardous before proceeding.

WARNING

For Class I Division 2 applications, use only Class I Division 2 listed or 
recognized accessories and modules approved for used within the 1794 
platform.

ATTENTION

Personnel responsible for the application of safety-related programmable 
electronic systems (PES) shall be aware of the safety requirements in the 
application of the system and shall be trained in using the system.

AB Parts

Содержание FLEX 1794-IF2XOF2I

Страница 1: ...age Category II applications as defined in IEC publication 60664 1 at altitudes up to 2000 m 6562 ft without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance ...

Страница 2: ...e cet équipement en environnements dangereux Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code lowest T number may...

Страница 3: ... 33 are internally connected in the terminal base unit 1794 TB3T 1794 TB3TS Terminals 16 17 19 21 23 25 27 29 31 and 33 are internally connected in the terminal base unit V DC power 1794 TB3 1794 TB3S Terminals 34 51 are internally connected in the terminal base unit 1794 TB3T 1794 TB3TS Terminals 34 35 50 and 51 are internally connected in the terminal base unit 1794 TBN 1794 TB2 Terminals 34 and...

Страница 4: ...it 1 0 0 0 1 4 20 mA 7 5 ms 5 0 ms 0 0 1 0 10V 2 5 ms 2 5 ms 0 0 1 1 5V 2 5 ms 2 5 ms 0 1 0 0 0 20 mA 7 5 ms 5 0 ms 0 1 0 1 4 20 mA 7 5 ms 5 0 ms 0 1 1 0 0 10V 5 0 ms 5 0 ms 0 1 1 1 10V 5 0 ms 5 0 ms 1 0 0 0 0 20 mA 2 5 ms 2 5 ms 1 0 0 1 4 20 mA 7 5 ms 5 0 ms 1 0 1 0 0 10V 2 5 ms 2 5 ms 1 0 1 1 0 5V 2 5 ms 2 5 ms 1 1 0 0 20 mA 2 5 ms 2 5 ms 1 1 0 1 4 20 mA 7 5 ms 5 0 ms 1 1 1 0 10V 2 5 ms 2 5 ms 1...

Страница 5: ... non linearity and repeatability error terms 2 If 24V DC is removed from the module input resistance 10 k Output Specifications Attribute Value Number of outputs 2 isolated Resolution Voltage Current 15 bits plus sign 0 320 mV cnt 0 656 A cnt General Specifications Data format 2 s complement 2 s complement Binary Offset binary Conversion type Digital to analog converter Update rate 2 5 5 0 ms all ...

Страница 6: ... Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 X CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 ...

Отзывы: