Publication 1784-6.5.30 - February 2001
A-2
Diagnostics and Troubleshooting
Module (MOD)
Status Indicator
This bi-color (green/red) LED indicates whether or not the
1784-PCIDS card has power and is operating properly.
Network (NET)
Status Indicator
This bi-color (green/red) LED indicates the status of the
communication link
Network Status Indicator
condition
status
indicates
off
no power
No power applied to device
green
device operational
Device is operating in a normal condition.
flashing green
(1)
(1)
The flash rate of the LED is approximately 1 flash per second. The LED should be on for
approximately 0.5 seconds and off for approximately 0.5 seconds.
device in standby
(device needs
commissioning)
Device needs commissioning due to
configuration missing, incomplete, or
incorrect.
Device may be in the standby state. Refer to
the DeviceNet Specification, Volume II,
Identity Object.
flashing red
recoverable fault
e.g., the device’s scan list configuration does
not match the actual network configuration.
red
unrecoverable fault
Device has an unrecoverable fault. Cycle
power to the card by shutting down and
cycling power to your computer. If the problem
persists the device may need to be replaced.
flashing
red-green
device self testing
Device is in self test. Refer to the DeviceNet
Specification, Volume II, Identity Object.
Network Status Indicator
condition
status
indicates
off
not powered,
not online
Device is not online.
•
The device has not completed the
Dup_MAC_ID test yet.
•
The device may not be powered; look at
the Module Status LED.
flashing green
(1)
(1)
The flash rate of the LED is approximately 1 flash per second. The LED should be on for
approximately 0.5 seconds and off for approximately 0.5 seconds.
online,
not connected
The device has passed the Dup_MAC_ID test
and is online, but has no established
connections to other nodes.
green
link okay, online,
connected
The device is online and has connections in
the established state.
flashing red
connection time-out
One or more I/O connections are in the
timed-out state.
red
critical link failure
Failed communication device. The device has
detected an error that has rendered it
incapable of communicating on the network
(Duplicate MAC ID or Bus-off).
Check network integrity and baud rate of all
devices. Then cycle power to the card by
shutting down and cycling power to your
computer.
Содержание DeviceNet 1784-PCIDS
Страница 1: ...DeviceNet PCI Communication Interface Card 1784 PCIDS CPCIDS User Manual Allen Bradley Parts...
Страница 4: ......
Страница 12: ...Publication 1784 6 5 30 February 2001 P 8 About This User Manual...
Страница 38: ...Publication 1784 6 5 30 February 2001 3 8 Setting Up the Hardware for the Example Network...
Страница 58: ...Publication 1784 6 5 30 February 2001 4 20 Configuring the DeviceNet Network...
Страница 68: ...Publication 1784 6 5 30 February 2001 5 10 Using IOLinx To Test the Example Network...
Страница 82: ...Publication 1784 6 5 30 February 2001 B 12 Creating and Running a SoftLogix 5 Application...
Страница 92: ...Publication 1784 6 5 30 February 2001 C 10 Configuring the DeviceNet Network from Another Network...
Страница 94: ...Publication 1784 6 5 30 February 2001 D 2 Changing the Network Baud Rate...
Страница 99: ...Allen Bradley Parts...
Страница 101: ...DeviceNet PCI Communication Interface Card User Manual Allen Bradley Parts...