Universal Disconnect Switch Installation Instructions (600A)
2
3
1
Assemble the cable mechanism bracket to the disconnect switch.
Rotate connecting rod into drive bar approximately
9 - 10 turns.
Turn the connecting rod counter-clockwise (less than 1 turn)
until hole in threaded rod aligns with hole in cable mechanism
lever.
90-130 lb-in
10-15 Nm
Connecting
Rod
Cable
Mechanism
Lever
4
Attach connecting rod to cable mechanism lever.
1
2
Connecting
Rod
Cable
Mechanism
Lever
90-130 lb-in
10-15 Nm
1/2"
9/16"
5/16"
Fully seat bolt
prior to attaching
nut.
Lubricate
90-130 lb-in
10-15 Nm
Cable Operated Mechanism Installation
1
Publication
1494V-IN028A-EN-P - March 2018
IMPORTANT:
Verify that the cable assembly does not interfere with any mechanical and moving parts. Keep the cable conduit away from all heat sources and current carrying terminals,
fuses, transformers, etc.
IMPORTANT:
When locating the 600A switch, verify that the minimum diameter for the loop of the cable between the switch mechanism and the handle mechanism is not less than 10 inches.