8
Universal Disconnect Switch Installation Instructions (600A)
1
2
3
90-130 lb-in
10-15 Nm
Remove drive mechanism
from right side of switch
(3) - 5/16 - 18 Hex Head Screws
with disconnect switch
in the "OFF" position.
Rotate crossbar to closed or "on" position.
Reinstall drive mechanism on left side of switch
Conversion from Right Hand to Left Hand Operation (If Required)
IMPORTANT: Switch conversion to left-hand operation requires left-hand cable mechanism.
ATTENTION:
With switch in the "CLOSED" position,
drive mechanism should align with crossbar.
Line Terminal Guard Installation
90-130 lb-in
10-15 Nm
1
2
6-10 lb-in
0.68-1.1 Nm
Line Terminal Adapter Installation
Torque
Range
1494U-
ALT600
25 lb-in
(2.8 N-m)
(1) 14-10 STR/SOL
(1) 8 STR
(2) 14 SOL/SOL
(2) 14 STR/STR
(2) 12 SOL/SOL
(2) 12 STR/STR
(2) 10 SOL/SOL
(2) 10 STR/STR
(2) 8 STR/STR
Lug Adapter Kit
Wire
Catalog
Number
Publication
1494V-IN028A-EN-P - March 2018
Wire
Clamp
Adapter