Switch Installation
1
Rod Operated Switch Installation
2
Universal Disconnect Switch Installation Instructions (600A)
A
HOLD FLUSH
TO
INSIDE
OF ENCLOSURE
MEASURE T
O
INSIDE OF
THE
TOP OF ENCLOSURE
TOP
BO
TT
Install gasket.
60-80 lb-in
6.8-9.0 Nm
Install handle and spring bracket.
Use template D to locate handle holes on mounting plate.
Overlay template F (600 A) over D .
Install defeater lever.
Cut (2) Connecting Rods; first rod connects the handle to the switch, second rod provides
stiffening for the enclosure flange and mounting panel. Installation of both rods is required.
N
N minus 3-3/4
"
Enclosure
Working Depth
(Inside Flange
of Enclosure to
Mounting Plate)
Mounting
Plate
Measure working depth of enclosure.
Measure, mark and
cut (2) connecting rods.
5
1
1
2
Remove burrs.
3
2
3
Install disconnect switch.
7
IMPORTANT:
Apply grease to O-Ring
to retain into handle groove.
7-11 lb-in
0.79-1.2 Nm
6
D
HOLD FLUSH
TO
INSIDE
OF ENCLOSURE
MEASURE T
O
INSIDE OF
THE
TOP OF ENCLOSURE
TOP HANDLE HOLE
BO
TT
OM HANDLE HOLE
TAPE
HOLD FLUSH
TO
INSIDE
OF ENCLOSURE
MEASURE T
O
INSIDE OF
THE
TOP OF ENCLOSURE
TOP
BO
TT
D
1
1
3
2
4
90-130 lb-in
10-15 Nm
8-1
/4"
4-1/8"
6-5/8"
15"
2-
1/16"
6-1/2"
42052-
18
5-01 (
1)
Prin
ted
in U
.S.A
.
F
Disconnect Switc
h Hole Location
Template (600A)
RIGHT
Hand Installation
(Use opposite side f
or left hand installation)
Switc
h Mounting Holes
Center punc
h and drill (4) 9/32" holes f
or #5/16-18 thread
forming (T
AP-TITE) scre
ws pr
ovided with s
witc
h
Center punch and drill
(4) 9/32" dia. holes for
thread forming screws
provided with switch.
Handle Installation
2
Cutting Connecting Rod
3
Publication
1494V-IN028A-EN-P - March 2018