Allen-Bradley Compact 5000 Скачать руководство пользователя страница 7

Rockwell Automation Publication 5069-IN010B-EN-P - November 2017

7

COMPACT 5000 Analog 8-channel Current/Voltage Input Module

To keep the modules on separate SA power buses, complete the 
following steps.

a. Install the modules that use one type of SA power, for 

example AC, to the right of the adapter or controller, that 
is, the first SA power bus.

b. Install the 5069-FPD field potential distributor to establish 

a second SA power bus.

c. Install the modules that use the other type of SA power, for 

example DC, on the second SA power bus.

Install the Removable Terminal Block

1. Hook the bottom of the RTB on the module.

2. Push the RTB against the module until the RTB clicks 

into place. 

3. Push the RTB handle against the RTB until you hear 

another click.

Install the Module

Install the I/O module next to the right-most device in the system. To 
install the module, complete these steps.

1. Confirm that MOD power and all sources of SA power are off. 

If you remove the module with power applied, the system 
MOD power bus and SA power bus are affected. For example, 
you can interrupt MOD power to the other modules in the 
system. Unintended consequences can occur as a result.

2. If an end cap is installed on the right-most module that is 

installed in the system, remove it and keep for later use.

3. Confirm that the DIN rail latch is closed.

4. If the DIN rail latches are open, gently push the rear latch back 

until the front latch pops up and clicks.

ATTENTION: 

To reduce susceptibility to noise, power 

analog modules and digital modules from separate 
power supplies.

IMPORTANT

We recommend that you use separate external power supplies 

for MOD power and SA power respectively. This practice helps 
to prevent unintended consequences that can result if you use 
one supply.

If you use separate external power supplies, the loss of power 
from one external power supply does not affect the 
availability of power from the other supply. For example, if 
separate external power supplies are used and SA power is 
lost, MOD power remains available for the Compact 5000 I/O 
modules.

WARNING: 

If you connect or disconnect the removable terminal 

block (RTB) with power applied, an electric arc can occur. This 
could cause an explosion in hazardous location installations.

The removable terminal block (RTB) does not support "Removal 

and Insertion Under Power" (RIUP) capability. Do not connect or 
disconnect the removable terminal block (RTB) while power is 
applied. Be sure that power is removed before proceeding.

WARNING: 

If you insert or remove the module while backplane 

power is on, an electric arc can occur. This could cause an explosion 
in hazardous location installations.

The module does not support "Removal and Insertion Under 

Power" (RIUP) capability. Do not connect or disconnect the 
module while power is applied. Be sure that power is removed 
before proceeding.

ATTENTION: 

Do not discard the end cap. Use this end 

cap to cover the exposed interconnections on the last 
module on the DIN rail. Failure to do so could result in 
equipment damage or injury from electric shock.

Open Position

Closed Position

Содержание Compact 5000

Страница 1: ...ng polled For more information on how to use Compact 5000 I O modules see the publications that are listed in Additional Resources on page 14 SummaryofChanges The following changes were made to this r...

Страница 2: ...ttuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell ap...

Страница 3: ...Les produits marqu s CL I DIV 2 GP A B C D ne conviennent qu une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livr avec des marqu...

Страница 4: ...y external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product Do not disconnect equipment unless power has been remov...

Страница 5: ...g Piece Bottom Interlocking Piece DIN Rail Latch RTB Handle RTB MOD Power Bus and SA Power Bus Connectors isolatedfromeach other internally RTB LowerTab Lower hook for use with cable tie Component Des...

Страница 6: ...in the system that is the controller or the adapter establishes an SA power bus A system can have more than one SA power bus You use 5069 FPD field potential distributors to establish a new SA power...

Страница 7: ...p and clicks ATTENTION To reduce susceptibility to noise power analog modules and digital modules from separate power supplies IMPORTANT Werecommendthatyouuseseparateexternalpowersupplies for MOD powe...

Страница 8: ...the fronts of both modules are flush with each other InstalltheEndCap You must install an end cap on the last module in your system 1 Align the end cap with the interlocking pieces on the module 2 Pus...

Страница 9: ...sulation from the wires Spring Strip 10 mm 0 39 in of insulation from the wires RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque...

Страница 10: ...1 Input 1 Input 2 Input 2 Input 3 Input 3 Input 4 Input 4 Input 5 Input 5 Input 6 Input 6 Input 7 Input 7 Shield Shield 2 wire Transmitter 24V DC Shield Ground A A i IMPORTANT Place additional loop d...

Страница 11: ...ge mode ANALOG INPUT 5069 IF8 Input 0 Input 0 Input 1 Input 1 Input 2 Input 2 Input 3 Input 3 Input 4 Input 4 Input 5 Input 5 Input 6 Input 6 Input 7 Input 7 Shield Shield User Analog Input Device 24V...

Страница 12: ...ces of SA power are turned off 2 If necessary remove the end cap from the right side of the module 3 If desired disconnect wires from the RTB as described on page 9 4 Press the DIN rail latch down unt...

Страница 13: ...Passthrough 2 2 Maximum level of SA Power current that the module can pass through to the next module in the system The specific level of current passed through varies based on system configuration 9...

Страница 14: ...nd EtherNet IP adapters Compact 5000 I O Analog Modules User Manual publication 5000 UM005 Describes how to use the Compact 5000 I O analog modules EtherNet IP Communication Modules in Logix 5000 Cont...

Страница 15: ...Rockwell Automation Publication 5069 IN010B EN P November 2017 15 COMPACT 5000 Analog 8 channel Current Voltage Input Module Notes...

Страница 16: ...ur documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents d...

Отзывы: