COMPACT 5000 Analog 8-channel Current/Voltage Input Module
To keep the modules on separate SA power buses, complete the
following steps.
a. Install the modules that use one type of SA power, for
example AC, to the right of the adapter or controller, that
is, the first SA power bus.
b. Install the 5069-FPD field potential distributor to establish
a second SA power bus.
c. Install the modules that use the other type of SA power, for
example DC, on the second SA power bus.
Install the Removable Terminal Block
1. Hook the bottom of the RTB on the module.
2. Push the RTB against the module until the RTB clicks
into place.
3. Push the RTB handle against the RTB until you hear
another click.
Install the Module
Install the I/O module next to the right-most device in the system. To
install the module, complete these steps.
1. Confirm that MOD power and all sources of SA power are off.
If you remove the module with power applied, the system
MOD power bus and SA power bus are affected. For example,
you can interrupt MOD power to the other modules in the
system. Unintended consequences can occur as a result.
2. If an end cap is installed on the right-most module that is
installed in the system, remove it and keep for later use.
3. Confirm that the DIN rail latch is closed.
4. If the DIN rail latches are open, gently push the rear latch back
until the front latch pops up and clicks.
ATTENTION:
To reduce susceptibility to noise, power
analog modules and digital modules from separate
power supplies.
IMPORTANT
We recommend that you use separate external power supplies
for MOD power and SA power respectively. This practice helps
to prevent unintended consequences that can result if you use
one supply.
If you use separate external power supplies, the loss of power
from one external power supply does not affect the
availability of power from the other supply. For example, if
separate external power supplies are used and SA power is
lost, MOD power remains available for the Compact 5000 I/O
modules.
WARNING:
If you connect or disconnect the removable terminal
block (RTB) with power applied, an electric arc can occur. This
could cause an explosion in hazardous location installations.
The removable terminal block (RTB) does not support "Removal
and Insertion Under Power" (RIUP) capability. Do not connect or
disconnect the removable terminal block (RTB) while power is
applied. Be sure that power is removed before proceeding.
WARNING:
If you insert or remove the module while backplane
power is on, an electric arc can occur. This could cause an explosion
in hazardous location installations.
The module does not support "Removal and Insertion Under
Power" (RIUP) capability. Do not connect or disconnect the
module while power is applied. Be sure that power is removed
before proceeding.
ATTENTION:
Do not discard the end cap. Use this end
cap to cover the exposed interconnections on the last
module on the DIN rail. Failure to do so could result in
equipment damage or injury from electric shock.
Open Position
Closed Position