background image

248

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 

Appendix C

        Using DeviceLogix™

14.

At the Who Active window select the 1756-EN2TR, then the controller, 
and click on the Download button

15.

The Download dialog box will appear, click on Download to proceed

16.

The configuration will be downloaded and the Downloading dialog box 
will show the progress

17.

Upon completion, select Run Mode as per shown

Содержание ArmorStart 290E

Страница 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...

Страница 2: ...cceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility...

Страница 3: ...f personal injury and or equipment damage exists if codes are ignored during installation ATTENTION ThecontrollercontainsESD electrostaticdischarge sensitivepartsandassemblies Staticcontrolprecautionsare required when installing testing servicing or repairing the assembly Component damage may result if ESD control procedures are not followed If you are notfamiliarwithstaticcontrolprocedures refert...

Страница 4: ... Application Guide Publication ENET AP005 Describes how to install configure and maintain linear and device level Ring DLR networks using Rockwell Automation EtherNet IP devices with embedded switch technology EtherNet IP Network Configuration User Manual PublicationENET UM001 Describes how to configure and use EtherNet IP communication modules with a Logix5000 controller and communicate withvario...

Страница 5: ...ctureforEtherNet IP IntroductionandConsiderations ODVApublication http www odva org Portals 0 Library Publications_Numbered PUB00035R0_Infrastructure_Guide pdf Provides an overview of the technologies used in EtherNet IP networks and provides guidelines for deploying infrastructure devices in EtherNet IP networks Resource Description Industrial Controls catalog website http www ab com catalogs Ind...

Страница 6: ...the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phonenumberabove toobtainone to your distributortocompletethereturnprocess Outside United States Please contact your local Rockwell Automation representative for the return procedure ...

Страница 7: ...AutomationPublication290E UM001B EN P June2012 7 Summary of Changes New and Updated Information This table contains the changes made to this revision Topic Page Added source brake and IPS specifications Various ...

Страница 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...

Страница 9: ...ltage Directive and the EU Council 2004 108 EC Electromagnetic Compatibility EMC Directive by applying the following standard s Bulletin 290E_ 291E_ EN 60947 4 1 Low voltage switchgear and controlgear Part 4 1 Contactorsandmotor starters Electromechanical contactors and motor starters Bulletin 294E_ EN 61800 3 Adjustable speed electronic power drive systems Part 3 EMC product standard including sp...

Страница 10: ...est addition to the ArmorStart portfolio ArmorStart LT is a leader in the market place given its compact size and high performance features in network I O and motor control This manual will guide you through the features and functionality when installing the product Thank you for choosing ArmorStart LT for your distributed motor control needs If you have any questions please refer to the Support S...

Страница 11: ...ard Features Across Product Family 19 Network Options 20 Factory Installed Options 22 ArmorStart LT Characteristics 23 Catalog Number Explanation 24 ArmorStart LT Characteristics 25 Catalog Number Explanation 26 Basic Operation 27 Group Motor Installations for USA and Canada Markets 27 Control Circuit 27 Motor Circuit 29 Local I O 29 Overload Protection 30 Mode of Operation Bulletin 290E 291E 30 F...

Страница 12: ...ct Cable Ratings 49 Branch Circuit Protection Requirements for ArmorConnect Three Phase Power Media 49 Fusing 50 Electrical Wiring 50 Group Motor Installations for USA and Canada Markets 55 Wiring 55 Cable Workmanship Guidelines 55 Service Space 56 Hand Operation HOA Considerations 56 General Wiring Considerations 56 Grounding 57 Grounding Safety Grounds 57 Grounding PE or Ground 57 Grounding Moto...

Страница 13: ...New Module Using the Add On Profile 78 Electronic Keying 80 Connections 81 Configured by 81 HOA Keypad Option 82 Source Brake Electro Mechanical Brake Option 82 User Configurable I O 82 RSLogix 5000 Add On Profile 83 Auto Generated Tags 85 Chapter4 Bulletin290E 291E 294E ProgrammableParameters Electronic Data Sheet EDS 99 Basic Setup Parameters 99 Parameter Groups 100 ArmorStart LT EtherNet IP Par...

Страница 14: ... 294E 172 Motor Overload Trip Curves 178 AppendixA ApplyingMoreThanOneArmorStart LTMotorControllerinaSingleBranch CircuitonIndustrialMachinery Introduction 179 ArmorStart LT Product Family 180 Multiple Motor Branch Circuits and Motor Controllers Listed for Group Installation General 181 Maximum Fuse Ampere Rating According to 7 2 10 4 1 and 7 2 10 4 2 183 Complete Text 183 Explanatory Example 185 ...

Страница 15: ...211 Analog Output Point Object 211 CLASS CODE 0x000B Implemented in Bulletin 294E units only 211 Parameter Object 212 CLASS CODE 0x000F 212 Parameter Group Object 213 CLASS CODE 0x0010 213 Discrete Input Group Object 214 CLASS CODE 0x001D 214 Discrete Output Group Object 214 CLASS CODE 0x001E 214 Control Supervisor Object 215 CLASS CODE 0x0029 215 Overload Object 216 CLASS CODE 0x002C 216 Device L...

Страница 16: ...N P June 2012 Table of Contents AppendixC UsingDeviceLogix Introduction 229 DeviceLogix Programming 230 DeviceLogix Programming Example 230 ArmorStart LT Bulletin 294E Example Configuration 236 Download the AOP 237 Use of the AOP in RSLogix 5000 242 ...

Страница 17: ...ritical to the application ArmorStart LT leverages the capabilities of the Rockwell Automation Integrated Architecture so you can achieve an unmatched level of integration and ease of use The architecture of ArmorStart LT allows Premiere Integration with Allen Bradley ControlLogix or CompactLogix line of Automation Controllers and PLCs RSLogix 5000 is the only programming tool needed which consoli...

Страница 18: ...ual port ethernet switch Device Level Ring DLR with Beacon frame performance IEEE 1588 Transparent Clock RSLogix 5000 Add On Profile 6 user configurable I O points DeviceLogix Embedded web server support Configurable e mail response for fault or alarm events Optional internal power supply Optional electromechanical brake contactor Optional local control via Hand Off Auto keypad Optional quick disc...

Страница 19: ...or quick setup and configuration of multiple ArmorStart LTs DeviceLogix ArmorStart LT offers local programmable logic via DeviceLogix DeviceLogix is a stand alone program that resides within the ArmorStart LT It is programmed locally using the Add On Profile and implements operations such as AND OR NOT Timers Counters Latches and Analog operations DeviceLogix can run as a stand alone application i...

Страница 20: ...tart LT supports native EtherNet IP without additional modules or adapters EtherNet IP allows complete integration of control with information across multiple Common Industrial Protocol CIP networks EtherNet IP allows users to integrate I O control device configuration and data collection across multiple networks enabling internet connectivity and information Embedded dual port switch ArmorStart L...

Страница 21: ...protocols PTP A transparent clock measures and adjusts for packet delays therefore removing the negative effects that these variations can cause within a synchronized distributed network of devices Embedded web server ArmorStart LT EtherNet IP version offers a web server that can be accessed via a standard internet browser The web server provides status diagnostics and configuration capabilities E...

Страница 22: ...HOA keypad ArmorStart LT offers an optional local Hand Off Auto keypad This key pad allows local start stop motor control regardless of PLC status This option can be used for troubleshooting or maintenance operations The HOA can also be disabled when local control is not allowed using parameter 67 Source brake ArmorStart LT provides an optional internally controlled electromechanical motor brake c...

Страница 23: ...igurable I Os LockOut TagOut Provision Wiring Access Reset IP Address Switches 1 On 0 Off On Off Switch HOA Keypad optional Gland Plate Conduit Cord Grip or ArmorConnect Media optional Status and Diagnostic LEDs Dual Port EtherNet IP This is replacedby a DeviceNetconnector when DeviceNet communication is selected ECM Electronic Control Module Protective Earth PE ...

Страница 24: ...ption F UL Type 4 12 d Overload Selection Code Description A 0 25 3 5 A B 1 1 7 6 A e Control Voltage Code Description Z External 24V DC control power P Internal power supply f Gland Plate Options Power and Motor Code Description G1 Conduit entry G2 ArmorConnect G3 Gland Kits g Option 1 Code Description 3 Hand Off Auto selector keypad 3FR Hand Off Auto selector keypad with Forward Reverse h Option...

Страница 25: ...ff Protective Earth PE Dual Port EtherNet IP This is replaced by a DeviceNet connector when DeviceNet communication is selected LockOut TagOut Provision Gland Plate Conduit Cord Grip or ArmorConnect Media optional Reset IP Address Switches ECM Electronic Control Module Hand Off Auto Keypad optional On Off Switch Status and Diagnostic LEDs Wiring Access 6 Configurable I Os ...

Страница 26: ...put Current Code Description D1P5 1 5 A 0 4 kW 0 5 Hp D2P5 2 5 A 0 75 kW 1 0Hp D4P2 3 6 A 1 5 kW 2 0Hp e Control Voltage Code Description Z External 24V DC control power P Internal power supply f Gland Plate Options Power and Motor Code Description G1 Conduit entry G2 ArmorConnect G3 Gland kits g Option 1 Code Description 3 Hand Off Auto selector keypad with Jog function h Option 2 Code Descriptio...

Страница 27: ... for switched and unswitched power The control voltage provides power to the inputs unswitched and outputs switched Unswitched control voltage is used to ensure no loss of network connectivity sensor or other field input status under normal operation The control power terminal connections are labeled A1 A2 and A3 Switched power is identified as A1 A2 Unswitched power is identified as A3 A2 As an o...

Страница 28: ...witched Control Power Unswitched Control Power Motor Control Motor Controller Class 2 External Switched 24VDC Power Supply Disconnect 24VDC L N L1 L2 L3 24VDC L N Class 2 External Unswitched 24VDC Power Supply Control power output is determined by disconnect status T1 T2 T3 ArmorStart LT Outputs Inputs EtherNet Comms Off Motor Control Motor Controller Disconnect Internal Power Supply Control power...

Страница 29: ...80 277V AC Local I O The ArmorStart LT provides as standard 6 user configurable I O points By default all points are configured as an Input When not using the AOP the user will need to refer to parameter 49 IOPointConfiguration to define an output point When using the AOP the I O point is configured from the General screen in the Module Definition section by clicking the Change button see Figure 9...

Страница 30: ...ncludes programmable overload Class 10 15 and 20 protection The Bulletin 294E provides overload protection 150 for 60s and 200 for 3s Refer to Chapter 6 Specifications for additional information Mode of Operation Bulletin 290E 291E Full Voltage Start This method is used in applications requiring across the line starting in which full inrush current and locked rotor torque are realized The ArmorSta...

Страница 31: ...rovides excellent speed regulation and high levels of torque across the entire speed range of the drive and improved speed regulation as loading increases Open Loop Speed Regulation with Slip Compensation allows the VFD to automatically adjust the output frequency to compensate for speed changes due to motor loading This feature utilizes an open loop current feedback slip compensation circuit Slip...

Страница 32: ...ation Flashing bicolor red green indicates a self test on power up Flashing green indicates an IP address is configured no CIP connections are established and an Exclusive Owner connection has not timed out Steady green indicates at least one CIP connection is established and an Exclusive Owner connection has not timed out Flashing red indicates the connection has timedout SteadyRedindicatesadupli...

Страница 33: ...ters of the EtherNet IP device They also provide information about the I O connections that the device supports and the content of the associated data structures EDS are used by EtherNet IP device configuration tools such as RSNetWorx for EtherNet IP and data servers such as RSLinx Classic EDS files for all ArmorStart LT EtherNet IP devices can be uploaded directly from the device via the web serv...

Страница 34: ...gix In the ArmorStart LT web server for ArmorStart EtherNet IP version As a sequence of LED flashes on the ECM Table 6 Protection Faults Cannot be disabled LED Flash Bit Enumeration Bulletin 290E 291E Trip Status Bits Bulletin 294E Trip Status Bits 1 0 OverloadTrip OverloadTrip 2 1 PhaseLossTrip PhaseLShortTrip 3 2 UnderPowerTrip UnderPowerTrip 4 3 SensorShortTrip SensorShortTrip 5 4 PhaseImbalTri...

Страница 35: ...e specified in parameter 33 SpeedReference Optional HOA Keypad Configuration Bulletin 290E 291E only The ArmorStart LT offers optional factory installed Hand OFF Auto HOA configurations Standard Bulletin 290E and Forward Reverse Bulletin 291E Figure 13 Bulletin 290E Standard HOA Figure 14 Bulletin 291 Forward Reverse HOA E HAND The Hand key will initiate starter operation AUTO The Auto key allows ...

Страница 36: ... Press Current Mode OFF HAND AUTO AUTO Auto Mode Motor Off HAND If no fault Motor On OFF Motor turns Off Motor turns Off FAULT PRESENT Motor turns Off Motor turns Off Key Press Current Mode OFF Key HAND AUTO Key NO KEY PRESSED Motor Off AUTO Auto Mode Motor Off HAND If no fault Motor On OFF Motor Off Motor Off PROTECTION FAULT PRESENT Motor Off Key Press Current Mode OFF HAND AUTO FWD REV FWD LED ...

Страница 37: ...D Set FWD LED FWD LED Set REV LED REV LED Set FWD LED JOG If no fault Jog Motor AUTO Auto Mode Motor Off HAND If no fault Motor On OFF Motor Off Motor Off Motor Off PROTECTION FAULT PRESENT Motor Off Motor Off Key Press Current Mode OFF HAND JOG AUTO NO KEY PRESSED Motor Off Motor Off FWD REV FWD LED Set REV LED REV LED Set FWD LED FWD LED Set REV LED REV LED Set FWD LED JOG If no fault Jog Motor ...

Страница 38: ...tactor is actuated via the internal power which supplies L1 and L2 voltage to the mechanical brake in the motor The source brake can be configured for independent control via parameter configuration The internal contactor electromechanical motor brake and associated motor branch cable are protected by the branch circuit protective device There is no resettable or replaceable protective device in A...

Страница 39: ...eck the contents of the package to see if all contents are included Contact your local Allen Bradley representative if any items are missing Inspecting After unpacking check nameplate catalog number s of the item s against the purchase order See Chapter 1 for an explanation of the catalog numbering system which will aid in nameplate interpretation Storing The controller should remain in the shippi...

Страница 40: ...Copper ground conductors are recommended The ArmorStart LT external protective earth PE pad is aluminum Refer to your local electrical installationstandardforproperbondingandprotectionwhendissimilarmetals are used ATTENTION An incorrectly applied or installed controller can damage components or reduce product life Wiring or application errors such as undersizing the motor incorrect or inadequate A...

Страница 41: ...upply Gland Plate optional ArmorConnect Media Gland Entrance optional ArmorConnect Source Brake Gland Plate optional 1 in conduit opening 0 75 in conduit opening Line Control Motor Line Motor Control Line Motor Source Brake 152 65 6 0 48 5 1 9 24 25 1 0 38 49 1 5 57 13 2 3 37 1 5 260 10 2 130 5 1 166 5 6 6 202 05 8 0 65 2 6 170 6 7 217 83 8 6 37 1 5 57 13 2 3 24 25 1 0 38 49 1 5 48 5 1 9 37 1 5 57...

Страница 42: ...orConnect Gland Entrance with Source Brake optional 1 in conduit opening 0 75 in conduit opening Control Motor Motor Line Control Motor Line Source Brake Line 206 43 8 1 120 4 7 202 27 8 0 219 32 8 6 170 6 7 381 15 0 240 9 4 37 1 5 92 9 3 7 38 49 1 5 24 25 1 0 48 5 1 9 37 1 5 92 9 3 7 38 61 1 5 24 25 1 0 24 25 1 0 92 9 3 7 92 9 3 7 37 1 5 37 1 5 38 55 1 5 38 55 1 5 48 5 1 9 48 5 1 9 IMPORTANT Forp...

Страница 43: ...Dia 25 5mm Dia 20 5mm Dia 20 5mm G1 Conduit G2 Media Standard U S Trade Knock outs G3 Conduit Daisy Chaining IP66 Metric Fittings No Internal Power Supply No Source Brake Source Brake No Internal Power Supply Internal Power Supply No Source Brake Internal Power Supply and Source Brake User Modified Dia 25 5mm Dia 20 5mm Dia 20 5mm Cat No 290 G3 A2 290 G3 A3 290 G3 A4 290 G3 A5 290 G3 A1 45 66 1 mm...

Страница 44: ...ing Terminal Detail The power control and ground wire capacity and the tightening torque requirements are shown in Table 8 The maximum number of connections per terminal are shown in Table 7 As shown in Figure 21 all the terminals are found in the wiring area Access can be gained by removing the terminal access cover plate ...

Страница 45: ...B2 Wire Strip Length 0 35 0 01 in 9 0 2 mm Table 7 Power Control and Ground Terminal Designations Terminal Designations Wires Connections Description A1 2 Switched 24V DC Control Power A2 2 Control Power Common A3 2 Unswitched 24V DC Control Power PE 2 Ground L1 2 Line Power Phase A L2 2 Line Power Phase B L3 2 Line Power Phase C T1 1 Motor Connection Phase A T2 1 Motor Connection Phase B T3 1 Mot...

Страница 46: ...AC 60 Hz or 400V AC 50 Hz Power Terminals Wire Size 2 18 10 AWG 0 8 5 2 mm2 per terminal Tightening Torque 10 6 2 lb in 1 2 0 2 N m Motor Terminals Wire Size 18 10 AWG 0 8 5 2 mm2 per terminal Tightening Torque 10 6 2 lb in 1 2 0 2 N m Control Terminals Wire Size 2 18 10 AWG 0 8 5 2 mm2 per terminal Tightening Torque 10 6 2 lb in 1 2 0 2 N m PE Ground Wire Size 2 16 10 AWG 1 3 5 2 mm2 per terminal...

Страница 47: ... motor The microcontroller and interface circuits are contained in the ECM The ECM also houses 6 user configurable I O points These six I O points are used for system level control and are accessible via by the communication network or DeviceLogix The user has the flexibility to coordinate the appropriate safety function for their application ArmorStart LT does not provide a safe torque off input ...

Страница 48: ...o 1585A DD4JD 2 CAT5ePatchCord IP67 M12D Code MaleStraight MaleRightAngle ExampleCat No 1585D M4TBDE 3 CAT5e PatchCable IP20 RJ45MaletoRJ45Male ExampleCat No 1585J M4TB 4 ControlPowerMediaPatchcords PatchCordcablewithintegralfemaleor maleconnectoroneachend ExampleCat No 889N F65GFNM 5 ControlPowerTees TheE stopInTee Cat No 898N 653ST NKF isusedtoconnecttotheBulletin800FOn MachineStopstationusing a...

Страница 49: ...M35F M1 Figure 24 On Machine Stop Stations ArmorConnect Cable Ratings The ArmorConnect Power Media cables are rated per UL Type TC 600V 90 C Dry 75 C Wet Exposed Run ER or MTW 600V 90 C or STOOW 105 C 600V Canadian Standards Association CSA STOOW 600V FT2 For additional information regarding ArmorConnect Power Media refer to ArmorStart LT selection guide publication 290 SG001_ EN P Branch Circuit ...

Страница 50: ...s and I O The control power terminal connections are labeled A1 A2 and A3 Switched power A1 will supply outputs and motor control Unswitched power A3 will supply logic power communications and sensor inputs WARNING The total circuit impedance including each cable assembly s own impedance must be low enough to ensure any short circuit or ground fault currentthatcanflowthroughanyassembly willbelarge...

Страница 51: ...us Overload DOL Power Conditioning Board Sinking Input or Sourcing output 6 User Configurable I O Points EtherNet IP Logic Fwd Status Fwd Control Motor Common SensorVoltage 1 4 2 5 3 L1 L2 L3 A1 A2 A3 Power Loss Switched SW Un Switched USW Common T1 T2 T3 Disconnect State Voltage Monitoring and Power Loss External Inputs External Outputs Internal Outputs Internal Inputs Micro PE At Motor Disconnec...

Страница 52: ...put or Sourcing output 6 User Configurable I O pOINTS EtherNet IP Logic Motor L1 L2 L3 T1 T2 T3 J3 TB2 1 11 Fan Drive Enable Common SensorVoltage L1 L2 L3 A1 A2 A3 Power Loss Switched SW Un Switched USW Common T1 T2 T3 Disconnect State Voltage Monitoring and Power Loss External Inputs External Outputs Internal Outputs Internal Inputs Micro PE At Motor Disconnect Disconnect Status Power Conditionin...

Страница 53: ...Motor Disconnect Disconnect Status Overload DOL 1 4 2 5 3 Sinking Input or Sourcing output 6 User Configurable I O Points EtherNet IP Logic Fwd Status Fwd Control Motor Common SensorVoltage Power Loss 1 1 2 3 4 L1 L2 L3 T1 T2 T3 Disconnect State Voltage Monitoring and Power Loss External Inputs External Outputs Internal Outputs Internal Inputs Micro PE At Motor Disconnect Disconnect Status Overloa...

Страница 54: ... output 6 User Configurable I O Points EtherNet IP Logic Motor L1 L2 L3 T1 T2 T3 J3 TB2 1 11 Fan Drive Enable Common SensorVoltage Power Loss 1 2 3 4 Power Loss 1 2 3 4 L1 L2 L3 T1 T2 T3 Disconnect State Voltage Monitoring and Power Loss External Inputs External Outputs Internal Outputs Internal Inputs Micro PE At Motor Disconnect Disconnect Status 1 4 2 5 3 Sinking Input or Sourcing output EtherN...

Страница 55: ...tween a cable tray and the utilization equipment or device as open wiring The cable shall be secured at intervals not exceeding 6 ft 1 8 m and installed in a good workman like manner Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable While the ArmorStart LT is intended for installation in factory floor environments of industrial...

Страница 56: ...orking position 2 Install where the operator is not placed in a hazardous situation when operating the equipment 3 Install where the possibility of inadvertent operation is minimized Where inadvertent operation may cause adverse effects the HOA can be disabled via parameter 67 General Wiring Considerations Wire in an industrial control application can be divided into three groups power control and...

Страница 57: ...f distribution system and other factors Periodically check the integrity of all ground connections General safety dictates that all metal parts are connected to earth with separate copper wire or wires of the appropriate gauge Most equipment has specific provisions to connect a safety ground or PE protective earth directly to it Grounding PE or Ground The safety ground PE must be connected to eart...

Страница 58: ...quire line reactors In most applications the ArmorStart LT is further away from the power distribution panel therefore the length of cable provides additional impedance as compared to an in panel solution Therefore ArmorStart LT does not define a minimum line impedance specification and does not require a line reactor Its design trades the external reactor supplied by the customer for an internal ...

Страница 59: ...me amplitude and frequency of these pulses must be considered when choosing a wire cable type The choice of cable must consider 1 The effects of the drive output once the cable is installed 2 The need for the cable to contain noise caused by the drive output 3 The amount of cable charging current available from the drive 4 Possible voltage drop and subsequent loss of torque for long wire runs Keep...

Страница 60: ...r devices that may be affected by electrical noise in the distribution system Applications with large numbers of drives in a similar location imposed EMC regulations or a high degree of communications networking are also good candidates for shielded cable An acceptable shielded cable will have 4 XLPE insulated conductors with a 100 coverage foil and an 85 coverage copper braided shield with drain ...

Страница 61: ...oth the motor and the ArmorStart LT for electrical bonding SKINTOP MS SC MS SCL cable grounding connectors and NPT PG adapters from LAPPUSA are good examples of this type of shield terminating gland Description Gland Knockout Size Cable Diameter Range in 2 Thomas and Betts Part Nos Cord Grip Sealing Ring Lock Nut Motor Source Brake G1 0 75 in 0 500 0 750 2932NM 5263 142TB Motor Source Brake G1 0 7...

Страница 62: ...s with CE EMC requirements Many factors can influence total machine installation compliance The EMI filter may result in relatively high ground leakage currents Therefore ArmorStart LT must only be applied in installations that are solidly grounded bonded to the building power distribution ground U T1 V T2 W T3 PE One or More Ground Leads Braid wires pulled back in a 360 pattern around the ground ...

Страница 63: ... bonded to the building power distribution ground Grounding should not include any form of plug or socket that would permit inadvertent disconnection Consult your local codes regarding redundant ground connections and or size of protective earthing conductor The integrity of all connections should be periodically checked Pin 1 Drain no connection Pin 2 VDNET Pin 3 VDNET Pin 4 CAN_H Pin 5 CAN_L 4 3...

Страница 64: ...nnector optional Source Brake Connector optional Incoming Control Power optional 24V DC Only Incoming Three Phase Power optional Pin 1 T1 black Pin 2 T2 white Pin 3 T3 red Pin 4 Ground green yellow Pin 1 Ground green yellow Pin 2 B1 black Pin 3 B2 white Pin 1 V Unswitched A3 red Pin 2 V Common A2 black Pin 3 Not used green Pin 4 Not used blank Pin 5 V Switched A1 blue Pin 6 Not used white Pin 1 L1...

Страница 65: ...O NOT connect or disconnect power or motor connections while power is applied to ArmorStart LT Proper Lock Out Tag Out procedures should be followed to reduced the risk of severe injury SHOCKHAZARD TheArmorStartLTlocaldisconnectwillonlyisolatethemotor power and remove switched power when turned OFF Power inputs must be switched OFF properly from their respective sources before connection or discon...

Страница 66: ...66 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 2 Installation and Wiring Notes ...

Страница 67: ...ust have an IP address of the same class and must have the same net ID Each node on the same network must have a different Host ID thus giving it a unique IP address Gateway Address The Gateway Address is the default address of a network It provides a single domain name and point of entry to the site Gateways connect individual physical networks into a system of networks Subnet Mask The subnet mas...

Страница 68: ...ey are set to a valid IP address between 1 254 When switches are set to a valid number the IP address will be 192 168 1 _ _ _ switch setting If the switches are set to an invalid number for example 000 or a value greater than 254 excluding 888 DHCP is enabled The DHCP server will assign the IP address and the Transport Control Protocol TCP parameters The RS Logix 5000 installation provides a BootP...

Страница 69: ...s This setting is useful in situations where the user wishes to decommission a module or when the user wishes to commission a previously used module that has an unknown configuration When the switches are set to 888 upon the next power cycle the ArmorStart LT will return to factory default settings and cease all communications The Module Status LED shall transition to blinking red and the Network ...

Страница 70: ...rmorStart LT must have DHCP enabled factory default to use the utility To configure your adapter using the BootP DHCP utility perform the following steps 1 Run the BootP DHCP software In the BOOTP DHCP Request History panel you will see the Ethernet Mac addresses of the devices issuing requests Note the Ethernet Mac address for a device can be found on the product label Figure 41 BOOTP DHCP Reques...

Страница 71: ...the IP Address column in the Request History section it signifies that the IP address assignment has been made 4 To assign this configuration to the device highlight the device in the Relation List panel and click the Disable BOOTP DHCP button When power is cycled to the device it uses the configuration you assigned and does not issue a DHCP request 5 To enable DHCP for a device with DHCP disabled...

Страница 72: ... Product Commissioning Figure 44 Enable DHCP Button Save the Relation List You can save the Relation List to use later To save the Relation List perform the following steps 1 Select Save As from the File menu Figure 45 Save Relation List You will see the Save As Dialog ...

Страница 73: ...uest its network configuration from a DHCP BOOTP server Any configuration received from a DHCP server will be stored in non volatile memory The unit will try to obtain the same IP address from the DHCP server If the server is not present e g server fails to power up the unit will use the IP address it previously received from the server The DHCP timeout 30 s Be cautious about using an unmanaged sw...

Страница 74: ...net browser and enter the IP address of the desired ArmorStart LT for example 192 168 1 1 Figure 47 Internal Web Browser From here you are able to view parameter settings device status and diagnostics from multiple tab views IMPORTANT The user should set the password to a unique value for authorized personnel If the login and password are lost you will need to reset the device to the factory defau...

Страница 75: ...r Network Password The user will be prompted to enter the default User Name Administrator The factory default password is blank The user is expected to change the password to avoid unauthorized access Figure 49 Network Configurations From this screen you can change the Ethernet Configuration For example in the above image the IP address will be changed to 10 10 10 101 Choose APPLY Changes for new ...

Страница 76: ...ick the Edit button Figure 51 Enter Network Password The user will be prompted to enter the default User Name Administrator The factory default password is blank The user is expected to change the Password to avoid unauthorized access E mail Notification Configuration ArmorStart LT internal web server will support the e mailing of warning and trip messages via Simple Mail Transfer Protocol SMTP Th...

Страница 77: ...tL1Amps 1 11 Amps SnapShotL2Amps 2 22 Amps SnapShotL3Amps 3 33 Amps SnapShotAveAmps 2 22 Amps SnapShot Thermal 55 Trip Type Overload Trip Trip Info Load has drawn excessive current based on the trip class selected Device Name ArmorStart LT 291E Test Unit Device Description Latest AB On Machine Offering Device Location Sixth Floor Comms Lab Contact Info Contact 1 Info Slicia Turnbull in California ...

Страница 78: ...providing an easy to use configuration interface In addition the copy and paste function allows easy configuration of multiple ArmorStart LTs with RSLogix 5000 revision 17 01 or later There is a known compatibility issue with revision 20 0 Update RSLogix 5000 to 20 1 or greater 1 Launch RS Logix 5000 2 From the I O Configuration tree add a New Module IMPORTANT If your version of RSLogix 5000 does ...

Страница 79: ...ess configurations using the switches The IP Address is a static address but configured from the webpage This allows more flexibility in defining the address If the address is served up use Host Name field 6 In the General page select the Change button From here define what options are available and what discrete point if any will need to be defined as an output The General page of the ArmorStart ...

Страница 80: ...g options are available Exact Match Exact Match keying requires all keying attributes that is Vendor Product Type Product Code catalog number Major Revision and Minor Revision of the physical module and the module created in the software to match precisely to establish communication Compatible Keying Compatible Keying indicates that the module determines whether to accept or reject communication C...

Страница 81: ... how the ArmorStart LT is configured once added to RS Logix 5000 The valid options are Web Page The unit is configured by the ArmorStart LT s web pages The AOP will NOT display any page or content of a page that allows configuration of the unit In this mode Connection Type will include a Backup and Restore feature The Backup selection will store parameter data in the RSLogix 5000 programming file ...

Страница 82: ...ciated parameters User Configurable I O The ArmorStart LT I O points may be used as either an input or an output The ArmorStart LT hardware does not require the user to specify a point s actual use as an input or output but the AOP requires the user to specify it to assign the correct tag name for the I O point When a point is configured as an input or output the corresponding tag name is Pt0_Data...

Страница 83: ...ges for configuration within RS Logix 5000 In addition the AOP will automatically create descriptive tag names for the input and output assemblies The following table lists the available AOPs for ArmorStart LT when adding a new module in RS Logix 5000 Catalog Number AOP Description 290E FAZ ArmorStart LT DOL 0 24 3 5 A 24V DC 290E FBZ ArmorStart LT DOL 1 1 7 6 A 24V DC 291E FAZ ArmorStart LT Rever...

Страница 84: ...h page includes basic information that must be reviewed by the user In addition within each page there are capabilities that can be accessed using the advance buttons The AOP page below is an example of the Advanced button that provides the user additional functionality 294E FVD1P5P ArmorStart LT VFD 480V AC 0 5 Hp IPS 294E FVD2P5P ArmorStart LT VFD 480V AC 1 Hp IPS 294E FVD4P2P ArmorStart LT VFD ...

Страница 85: ...the controller tags are generated The tag names are descriptive and automatically generated This greatly simplifies programming The figure below shows an example of the auto generated tags for ArmorStart LT The following tables provide more clarification regarding the Produce and Consume assemblies and how they correlate with the auto generated names ...

Страница 86: ...SLT_DEMO O Pt00Data BOOL Decimal ASLT_DEMO Pt01Data ASLT_DEMO O Pt01Data BOOL Decimal ASLT_DEMO Pt02Data ASLT_DEMO O Pt02Data BOOL Decimal ASLT_DEMO Pt03Data ASLT_DEMO O Pt03Data BOOL Decimal ASLT_DEMO Pt04Data ASLT_DEMO O Pt04Data BOOL Decimal ASLT_DEMO Pt05Data ASLT_DEMO O Pt05Data BOOL Decimal ASLT_DEMO Accel2 ASLT_DEMO O Accel2 BOOL Decimal ASLT_DEMO Decel2 ASLT_DEMO O Decel2 BOOL Decimal ASLT...

Страница 87: ...ngReverse RunningForward WarningPresent TripPresent 5 BrakeStatus DisconnectClosed KeyPadJogging KeyPadHand KeyPadOff KeyPadAuto DLXEnabled 6 OutputFrequency Low xxx x Hz 7 OutputFrequency High xxx x Hz 8 Pt05 Pt04 Pt03 Pt02 Pt01 Pt00 9 10 Pt07DeviceOut Pt06DeviceOut Pt05DeviceOut Pt04DeviceOut Pt03DeviceOut Pt02DeviceOut Pt01DeviceOut Pt00DeviceOut 11 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt1...

Страница 88: ...SLT_DEMO I Pt00Data BOOL Decimal ASLT_DEMO Pt01Data ASLT_DEMO I Pt01Data BOOL Decimal ASLT_DEMO Pt02Data ASLT_DEMO I Pt02Data BOOL Decimal ASLT_DEMO Pt03Data ASLT_DEMO I Pt03Data BOOL Decimal ASLT_DEMO Pt04Data ASLT_DEMO I Pt04Data BOOL Decimal ASLT_DEMO Pt05Data ASLT_DEMO I Pt05Data BOOL Decimal ASLT_DEMO Pt00DeviceOut ASLT_DEMO I Pt00DeviceOut BOOL Decimal ASLT_DEMO Pt01DeviceOut ASLT_DEMO I Pt0...

Страница 89: ...nd output ON Pt01Data If user defined as output commnd output ON Pt02Data If user defined as output commnd output ON Pt03Data If user defined as output commnd output ON Pt04Data If user defined as output commnd output ON Pt05Data If user defined as output commnd output ON Accel2 VFD acceleration ramp 2 Decel2 VFD deceleration ramp 2 FreqCommand Logix command frequency Pt00DeviceIn Network input to...

Страница 90: ...1 close 0 open OutputFrequency VFD frequency Pt00Data User configured I O status Pt01Data User configured I O status Pt02Data User configured I O status Pt03Data User configured I O status Pt04Data ASLT_DEMO I Pt04Data Pt05Data User configured I O status Pt00DeviceOut DeviceLogix network output status Pt01DeviceOut DeviceLogix network output status Pt02DeviceOut DeviceLogix network output status P...

Страница 91: ...oltage Parameter 11 UnswitchedVoltageLevel Unswitched control power voltage Parameter 12 InternalFanRPM VFD fan speed Parameter 13 OperatingHours Elapse run hours Parameter 14 DriveTemperature VFD internal temperature Parameter 15 TripStatus Bit enumerate trip status Parameter 16 WarningStatus Bit enumerate warning status Parameter 17 Device Input Status Tags Tag Description Use ...

Страница 92: ...REV Pt02Data DEMO_REV O Pt02Data BOOL Decimal DEMO_REV Pt03Data DEMO_REV O Pt03Data BOOL Decimal DEMO_REV Pt04Data DEMO_REV O Pt04Data BOOL Decimal DEMO_REV Pt05Data DEMO_REV O Pt05Data BOOL Decimal DEMO_REV Pt00DeviceIn DEMO_REV O Pt00DeviceIn BOOL Decimal DEMO_REV Pt01DeviceIn DEMO_REV O Pt01DeviceIn BOOL Decimal DEMO_REV Pt02DeviceIn DEMO_REV O Pt02DeviceIn BOOL Decimal DEMO_REV Pt03DeviceIn DE...

Страница 93: ...Out Pt00DeviceOut 9 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt12DeviceOut Pt11DeviceOut Pt10DeviceOut Pt09DeviceOut Pt08DeviceOut 10 AnalogDeviceOut low byte 11 AnalogDeviceOut high byte 12 Param 1 PhaseL1Current 13 14 Param 2 PhaseL2Current 15 16 Param 3 PhaseL3Current 17 18 Param 4 AverageCurrent 19 20 Param 5 ThermalUtilized 21 22 Param 11 SwitchedVolts OutputSourceV IPS units 23 24 Param 12 ...

Страница 94: ... Decimal DEMO_REV Pt06DeviceOut DEMO_REV I Pt06DeviceOut BOOL Decimal DEMO_REV Pt07DeviceOut DEMO_REV I Pt07DeviceOut BOOL Decimal DEMO_REV Pt08DeviceOut DEMO_REV I Pt08DeviceOut BOOL Decimal DEMO_REV Pt09DeviceOut DEMO_REV I Pt09DeviceOut BOOL Decimal DEMO_REV Pt10DeviceOut DEMO_REV I Pt10DeviceOut BOOL Decimal DEMO_REV Pt11DeviceOut DEMO_REV I Pt11DeviceOut BOOL Decimal DEMO_REV Pt12DeviceOut DE...

Страница 95: ...commnd output ON Pt00DeviceIn Network input to DeviceLogix engine Pt01DeviceIn Network input to DeviceLogix engine Pt02DeviceIn Network input to DeviceLogix engine Pt03DeviceIn Network input to DeviceLogix engine Pt04DeviceIn Network input to DeviceLogix engine Pt05DeviceIn Network input to DeviceLogix engine Pt06DeviceIn Network input to DeviceLogix engine Pt07DeviceIn Network input to DeviceLogi...

Страница 96: ... configured I O status Pt00DeviceOut DeviceLogix network output status Pt01DeviceOut DeviceLogix network output status Pt02DeviceOut DeviceLogix network output status Pt03DeviceOut DeviceLogix network output status Pt04DeviceOut DeviceLogix network output status Pt05DeviceOut DeviceLogix network output status Pt06DeviceOut DeviceLogix network output status Pt07DeviceOut DeviceLogix network output ...

Страница 97: ... 97 Product Commissioning Chapter 3 UnswitchedVoltageLevel Unswitched control power voltage Parameter 12 TripStatus Bit enumerate trip status Parameter 16 WarningStatus Bit enumerate warning status Parameter 17 Device Input Status Tags Tag Description Use ...

Страница 98: ...98 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 3 Product Commissioning Notes ...

Страница 99: ...d web browser RSLogix 5000 is the recommended commissioning software DownloadtheAdd On Profile AOP fromhttp support rockwellautomation com controlflash Logix Profiler aspfor additional functionality There are additional capabilities that are not enabled or left at their default values When using the AOP this parameter is configured during module definition on the General page Table 22 Quick Parame...

Страница 100: ...rSourceV 13 Reserved 14 Reserved 15 Reserved 1 OutputFreq 2 CommandFreq 3 OutputCurrent 4 OutputVoltage 5 DCBusVoltage 6 StarterStatus 7 StarterCommand 8 AuxIOStatus 9 NetworkStatus 10 DLXControlStatus 11 OutputSourceV 12 SensorSourceV 13 InternalFanRPM 14 ElapsedRunTime 15 DriveTemperature 16 TripStatus 17 WarningStatus 18 TripLog0 19 TripLog1 20 TripLog2 21 TripLog3 22 TripLog4 28 FLASetting 29 ...

Страница 101: ...e 54 OutNetFaultState 55 OutNetFaultValue 56 OutNetIdleState 57 OutNetIdleValue 58 Input00Function 59 Input01Function 60 Input02Function 61 Input03Function 62 Input04Function 63 Input05Function 64 NetworkOverride 65 CommsOverride 66 KeypadMode 67 KeypadDisable 68 SetToDefaults Bulletin 290E 291E Units Bulletin 294E Units Advanced Config 69 OLWarningLevel 70 JamInhibitTime 71 JamTripDelay 72 JamTri...

Страница 102: ...ll ArmorStart LTs Bulletin 290E 291E Basic Status Group IMPORTANT Parameter setting changes take effect immediately unless otherwise noted in the parameter listing These changes maybe immediate even during the running status PhaseL1Current This parameter determines the actual Phase L1 current Parameter Number 1 Access Rule GET Data Type INT Group Basic Status Units x xx Amps Minimum Value 0 Maximu...

Страница 103: ...average of 3 Phase currents Parameter Number 4 Access Rule GET Data Type INT Group Basic Status Units x xx Amps Minimum Value 0 Maximum Value 32767 Default Value 0 ThermalUtilized This parameter determines the percent of Thermal Capacity used Parameter Number 5 Access Rule GET Data Type USINT Group Basic Status Units Percent Minimum Value 0 Maximum Value 100 Default Value 0 StarterStatus This para...

Страница 104: ...ngPresent X RunningForward X RunningReverse X Ready X NetControlStatus X Reserved X CurrentFlowing X DLXEnabled X KeyPadAuto X KeyPadOff X KeyPadHand X X Reserved X DisconnectClosed X Reserved StarterCommand TheparameterprovidestheRunCommand status to the starter Parameter Number 7 Access Rule GET Data Type WORD Group Basic Status Units Minimum Value 0 Maximum Value 0x3F07 Default Value 0 ...

Страница 105: ...t X X X X X Reserved X Out00 X Out01 X Out02 X Out03 X Out04 X Out05 X X Reserved AuxIOStatus The parameter provides the status of hardware input output points Parameter Number 8 Access Rule GET Data Type WORD Group Basic Status Units Minimum Value 0 Maximum Value 0x3F Default Value 0 Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X Pt00 X Pt01 X Pt02 X Pt03 X Pt04 X Pt05 X X X X X X X X X X R...

Страница 106: ...14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X ExplicitCnxn X I OConnection X ExplicitCnxnFlt X IOCnxnFault X IOCnxnIdle X Reserve X DLREnabled X DLRFault X X X X X X X X Reserved DLXControlStatus The parameter provides the DeviceLogix Control Status 0 Controlled in Logix programs 1 Controlled in local DLX programs Parameter Number 10 Access Rule GET Data Type UINT Group Basic Status Units Minimum Value 0 M...

Страница 107: ...olts Minimum Value 0 Maximum Value 65535 Default Value 0 SensorSourceV IPS UnswitchedVolts This parameter determines the incoming unswitched control voltage across terminals A2 A3 IPS Available voltage on Input Sensor Source Pin 1 for all I O points Parameter Number 12 Access Rule GET Data Type UINT Group Basic Status Units x xx Volts Minimum Value 0 Maximum Value 65535 Default Value 0 TripStatus ...

Страница 108: ...derloadTrip X X X Reserved X OutputShortTrip X UserDefinedTrip X HardwareFltTrip WarningStatus This parameter provides the current warning condition Parameter Number 17 Access Rule GET Data Type WORD Group Trip Status Units Minimum Value 0 Maximum Value 0xC295 Default Value Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X OverloadWarning X Reserved X UnderPowerWarn X Reserved X PhaseImbalanceW...

Страница 109: ...vides the second last trip to occur Parameter Number 19 Access Rule GET Data Type UINT Group Trip Status Units Minimum Value 0 Maximum Value 75 Default Value 0 TripLog3 This parameter provides the third last trip to occur Parameter Number 20 Access Rule GET Data Type UINT Group Trip Status Units Minimum Value 0 Maximum Value 75 Default Value 0 TripLog4 Thisparameterprovidesthefourthlasttrip to occ...

Страница 110: ... Parameter Number 23 Access Rule GET Data Type INT Group Trip Status Units x xx Amps Minimum Value 0 Maximum Value 32767 Default Value SnapShotL2Amps This parameter provides a snapshot of actual Phase L2 current at time of last trip Parameter Number 24 Access Rule GET Data Type INT Group Trip Status Units x xx Amps Minimum Value 0 Maximum Value 32767 Default Value 0 SnapShotL3Amps This parameter p...

Страница 111: ... of Thermal Capacity used at time of last trip Parameter Number 27 Access Rule GET Data Type USINT Group Trip Status Units Percent Minimum Value 0 Maximum Value 100 Default Value 0 FLASetting The motor s full load current rating is programmed in this parameter Parameter Number 28 Access Rule GET SET Data Type INT Group Basic Configuration Units x xx Amps Minimum Value See Table 23 Maximum Value Se...

Страница 112: ...e overload trip classification 1 10 2 15 3 20 Parameter Number 30 Access Rule GET Data Type USINT Group Basic Configuration Units Minimum Value 1 Maximum Value 3 Default Value 1 ProtFltResetMode This parameter configures the Protection Fault reset mode 0 Manual 1 Automatic Parameter Number 41 Access Rule GET SET Data Type BOOL Group Starter Protection Units Minimum Value 0 Maximum Value 1 Default ...

Страница 113: ...X SensorShortTrip X PhaseImbalanceTrip X NonVolMemoryTrip X Reserved X JamTrip X StallTrip X UnderloadTrip X X X Reserved X OutputShortTrip X UserDefinedTrip X HardwareFltTrip The highlighted functions are enabled by default WarningStatus This parameter provides the current warning condition Parameter Number 43 Access Rule GET Data Type WORD Group Trip Status Units Minimum Value 0 Maximum Value 0x...

Страница 114: ...arning ProtectFltReset Thisparameter resets a ProtectionFault by setting the bit to 1 0 NoAction 0 1 ResetFault Parameter Number 44 Access Rule GET SET Data Type BOOL Group Starter Protection Units Minimum Value 0 Maximum Value 1 Default Value 0 RunNetFltAction This parameter in conjunction with Parameter 46 RunNetFltValue defines how the starter will respond when a fault occurs 0 GoToFaultValue 1...

Страница 115: ...es how the starter will respond when a network is idle as determined by Parameter 48 0 GoToIdleValue 1 HoldLastState Parameter Number 47 Access Rule GET SET Data Type BOOL Group Starter Protection Units Minimum Value 0 Maximum Value 1 Default Value 0 RunNetIdlValue This parameter determines the state that starter assumes when the network is idle and Parameter 47 RunNetIdlAction is set to 1 0 OFF 1...

Страница 116: ...m Value 0 Maximum Value 64 Default Value 0 FilterOnOff This parameter determines the input which must be absent for this time before being reported OFF Parameter Number 51 Access Rule GET SET Data Type USINT Group User I O Config Units msecs Minimum Value 0 Maximum Value 64 Default Value 0 OutProtFltState This parameter in conjunction with Parameter 53 OutProtFltValue defines howthestarteroutputsw...

Страница 117: ... GoToFaultValue 1 HoldLastState Parameter Number 54 Access Rule GET SET Data Type BOOL Group User I O Config Units Minimum Value 0 Maximum Value 1 Default Value 0 OutNetFaultValue Thisparameterdeterminesthestateofthe starter outputs when an Ethernet fault occurs and Parameter 54 OutNetFaultState is set to 0 0 OFF 1 ON Parameter Number 55 Access Rule GET Data Type BOOL Group User I O Config Units M...

Страница 118: ...r Number 58 Access Rule GET SET Data Type USINT Group User I O Config Units Minimum Value 0 Maximum Value 4 Default Value 0 Input01Function This parameter determines the special function for User Input 1 0 NoFunction 1 FaultReset 2 MotionDisable 3 ForceSnapShot 4 UserFault 5 BrakeRelease These choices are level sensitive All others areedge sensitive Parameter Number 59 Access Rule GET SET Data Typ...

Страница 119: ...le 3 ForceSnapShot 4 UserFault 5 BrakeRelease These choices are level sensitive All others are edge sensitive Parameter Number 62 Access Rule GET SET Data Type USINT Group User I O Config Units Minimum Value 0 Maximum Value 4 Default Value 0 Input05Function This parameter determines the special function for User Input 5 0 NoFunction 1 FaultReset 2 MotionDisable 3 ForceSnapShot 4 UserFault 5 BrakeR...

Страница 120: ...omentary 1 Maintained Parameter Number 66 Access Rule GET SET Data Type BOOL Group Misc Config Units Minimum Value 0 Maximum Value 1 Default Value 0 KeypadDisable This parameter disables all keypad function except for the OFF and RESET buttons 0 KeypadEnabled 1 KeypadDisabled Parameter Number 67 Access Rule GET SET Data Type BOOL Group Misc Config Units Minimum Value 0 Maximum Value 1 Default Valu...

Страница 121: ...ng that Jam detection is inhibited Parameter Number 70 Access Rule GET Data Type USINT Group Advanced Config Units secs Minimum Value 0 Maximum Value 250 Default Value 10 JamTripDelay This parameter determines how much time above the Jam Level before the unit will trip Parameter Number 71 Access Rule GET Data Type USINT Group Advanced Config Units x x secs Minimum Value 1 Maximum Value 25 0 Defaul...

Страница 122: ... during motor starting Parameter Number 74 Access Rule GET Data Type USINT Group Advanced Config Units secs Minimum Value 0 Maximum Value 250 Default Value 10 StallTripLevel This parameter determines the Stall Trip Level as a percentage of Full Load Amps Parameter Number 75 Access Rule GET Data Type UINT Group Advanced Config Units FLA Minimum Value 100 Maximum Value 600 Default Value 600 ULInhibi...

Страница 123: ... 1 Maximum Value 25 0 Default Value 5 0 ULTripLevel This parameter determines the Underload Trip Level as a percentage of Full Load Amps Parameter Number 78 Access Rule GET Data Type USINT Group Advanced Config Units FLA Minimum Value 10 Maximum Value 100 Default Value 50 ULWarningLevel This parameter determines the Underload Warning Level as a percentage of Full Load Amps Parameter Number 79 Acce...

Страница 124: ...frequency even if the starter is not running Parameter Number 2 Access Rule GET Data Type UINT Group Basic Status Units x x Hz Minimum Value 0 Maximum Value 999 9 Default Value 0 OutputCurrent This parameter provides the output current at motor terminals T1 T2 T3 Parameter Number 3 Access Rule GET Data Type UINT Group Basic Status Units x xx Amps Minimum Value 0 Maximum Value 8 00 Default Value 0 ...

Страница 125: ... 1200 Default Value 0 Starter Status This parameter provides the status of the starter Parameter Number 6 Access Rule GET Data Type WORD Group Basic Status Units Minimum Value 0 Maximum Value OxDFFF Default Value 0 Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X TripPresent X WarningPresent X RunningForward X RunningReverse X Ready X NetControlStatus X NetRefStatus X AtReference X DLXEnabled ...

Страница 126: ... Status Units Minimum Value 0 Maximum Value 0xFF1F Default Value 0 Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X RunningForward X RunningReverse X ResetFault X JogForward X JogReverse X X X Reserved X Out00 X Out01 X Out02 X Out03 X Out04 X Out05 X Accel2 X Decel2 AuxIOStatus Status of the hardware input output points Parameter Number 8 Access Rule GET Data Type WORD Group Basic Status Unit...

Страница 127: ...e GET Data Type WORD Group Basic Status Units Minimum Value 0 Maximum Value 0xDF Default Value 0 Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X ExplicitCnxn X IOConnection X ExplicitCnxnFlt X IOCnxnFault X IOCnxnIdle X Reserve X DLREnabled X DLRFlt X X X X X X X X Reserved DLXControlStatus The parameter provides the DeviceLogix Control Status 0 Controlled in Logix Programs 1 Controlled in lo...

Страница 128: ...ing switched control voltage across terminals A1 A2 IPS available voltage on User Output Pin 4 for all I O points Parameter Number 11 Access Rule GET Data Type UINT Group Basic Status Units x xx Volts Minimum Value 0 Maximum Value 65535 Default Value 0 SensorSourceV IPS UnswitchedVolts This parameter determines the incoming unswitched control voltage across terminals A2 A3 IPS available voltage on...

Страница 129: ...mulatedruntimedisplayedin10hour increments 1 10 Hrs Parameter Number 14 Access Rule GET Data Type UINT Group Basic Status Units Minimum Value 0 Maximum Value 9999 Default Value 0 DriveTemperature This parameter determines the present operating temperature of the power section Parameter Number 15 Access Rule GET Data Type UINT Group Basic Status Units C Minimum Value 0 Maximum Value 9999 Default Va...

Страница 130: ...sconnect X StallTrip X OverTemperature X GroundFault X RestartRetries X DriveHdwFault X OutputShortTrip X UserDefinedTrip X HardwareFltTrip WarningStatus This parameter provides the current warning condition Parameter Number 17 Access Rule GET Data Type WORD Group Trip Status Units Minimum Value 0 Maximum Value 0xC044 Default Value 0 Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X X Reserved ...

Страница 131: ...vides the second last trip to occur Parameter Number 19 Access Rule GET Data Type UINT Group Trip Status Units Minimum Value 0 Maximum Value 75 Default Value 0 TripLog2 This parameter provides the third last trip to occur Parameter Number 20 Access Rule GET Data Type UINT Group Trip Status Units Minimum Value 0 Maximum Value 75 Default Value 0 TripLog3 Thisparameterprovidesthefourthlasttrip to occ...

Страница 132: ...trip Parameter Number 23 Access Rule GET Data Type UINT Group Trip Status Units x x Hz Minimum Value 0 Maximum Value 999 9 Default Value 0 SnapShotOutAmps This parameter provides a snapshot of output current at time of last trip Parameter Number 24 Access Rule GET Data Type UINT Group Trip Status Units x xx Amps Minimum Value 0 Maximum Value 4 60 Default Value 0 SnapShotOutVolts This parameter pro...

Страница 133: ...perature at time of last trip Parameter Number 27 Access Rule GET Data Type UINT Group Trip Status Units C Minimum Value 0 Maximum Value 9999 Default Value 0 MotorNPVolts Set to the motor nameplate rated voltage Parameter Number 28 Access Rule GET SET Data Type UINT Group Motor and Control Units V AC Minimum Value 35 Maximum Value 460 Default Value 460 MotorNPHertz Set to the motor nameplate rated...

Страница 134: ... UINT Group Motor and Control Cat No Hp kW Units x x Amps 294_FD1P5 0 5 Hp Min 0 Max 2 7 Default 2 2 Minimum Value 0 294_FD2P5 1 0 Hp Min 0 Max 4 5 Default 3 7 Maximum Value Cat No Dependent 294_FD4P2 2 0 Hp Min 0 Max 7 5 Default 6 3 Default Value Cat No Dependent StopMode Valid Stop Mode for the Bulletin 294E ArmorStart LT are the following 0 RampToStop Stop command clears active fault 1 Coast to...

Страница 135: ...m Value 0 Maximum Value 2 Default Value 0 MinimumFreq Sets the lowest frequency the drive will output continuously Parameter Number 34 Related Parameter 1 2 35 Access Rule GET SET Data Type UINT Group Speed Control Units x x Hz Minimum Value 0 0 Maximum Value 400 0 Default Value 0 0 MaximumFreq Sets the highest frequency the drive will output Parameter Number 35 Related Parameter 1 2 34 35 139 Acc...

Страница 136: ...oup Speed Control Units x x secs Minimum Value 0 1 Maximum Value 600 0 Default Value 10 0 Maximum Freq Accel Time Accel Rate Parameter 35 Maximum Freq Speed Accel Time 1 0 0 Time Decel Time 1 A c c e l e r a t i o n D e c e l e r a t i o n Maximum Freq Decel Time Decel Rate Parameter 35 Maximum Freq Speed Accel Time 1 0 0 Time Decel Time 1 A c c e l e r a t i o n D e c e l e r a t i o n SCurvePerc...

Страница 137: ...get 2 Target 1 2 S CurveTime 2 5 Seconds JogFrequency Sets the output frequency when the jog command is issued Parameter Number 39 Related Parameters 35 40 Access Rule GET SET Data Type UINT Group Drive Advanced Setup Units x x Hz Minimum Value 0 0 Maximum Value 400 0 Default Value 10 0 JogAccelDecel Sets the acceleration and deceleration time when a jog command is issued Parameter Number 40 Relat...

Страница 138: ... Maximum Value 1 Default Value 0 ProtectFltEnable This parameter enables the Protection Fault by setting the bit to 1 Parameter Number 42 Access Rule GET SET Data Type WORD Group Starter Protection Units Minimum Value 0 Maximum Value 0xFFFF Default Value 0xBFFF Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X OverloadTrip X PhaseShortTrip X UnderPowerTrip X SensorShortTrip X OverCurrentTrip X ...

Страница 139: ...aramInit X X X X X X X Reserved X UnswitchedPwrWarn X ConfigWarning ProtectFltReset This parameter resets a Protection Fault by setting the bit to 1 0 NoAction 0 1 ResetFault Parameter Number 44 Access Rule GET SET Data Type BOOL Group Starter Protection Units Minimum Value 0 Maximum Value 1 Default Value 0 RunNetFltAction This parameter in conjunction with Parameter 46 RunNetFltValue defines how ...

Страница 140: ...nes how the starter will respond when a network is idle as determined by Parameter 48 0 GoToIdleValue 1 HoldLastState Parameter Number 47 Access Rule GET SET Data Type BOOL Group Starter Protection Units Minimum Value 0 Maximum Value 1 Default Value 0 RunNetIdlValue This parameter determines the state that starter assumes when the network is idle and Parameter 47 RunNetIdlAction is set to 1 0 OFF ...

Страница 141: ...alue 0 Maximum Value 64 Default Value 0 FilterOnOff This parameter determines the input which must be absent for this time before being reported OFF Parameter Number 51 Access Rule GET SET Data Type USINT Group User I O Config Units msecs Minimum Value 0 Maximum Value 64 Default Value 0 OutProtFltState This parameter in conjunction with Parameter 53 OutProtFltValue defines how the starter outputs ...

Страница 142: ... 0 GoToFaultValue 1 HoldLastState Parameter Number 54 Access Rule GET SET Data Type BOOL Group User I O Config Units Minimum Value 0 Maximum Value 1 Default Value 0 OutNetFaultValue This parameter determines the state that starter outputs when an Ethernet fault occurs and Parameter 54 OutNetFaultState is setto 0 0 OFF 1 ON Parameter Number 55 Access Rule GET Data Type BOOL Group User I O Config Un...

Страница 143: ... Number 58 Access Rule GET SET Data Type USINT Group User I O Config Units Minimum Value 0 Maximum Value 5 Default Value 0 Input01Function This parameter determines the special function for User Input 1 0 NoFunction 1 FaultReset 2 MotionDisable 3 ForceSnapShot 4 UserFault 5 BrakeRelease These choices are level sensitive All others are edge sensitive Parameter Number 59 Access Rule GET SET Data Typ...

Страница 144: ... parameter determines the special function for User Input 4 0 NoFunction 1 FaultReset 2 MotionDisable 3 ForceSnapShot 4 UserFault 5 BrakeRelease These choices are level sensitive All others areedge sensitive Parameter Number 62 Access Rule GET SET Data Type USINT Group User I O Config Units Minimum Value 0 Maximum Value 5 Default Value 0 Input05Function This parameter determines the special functi...

Страница 145: ...connection timeout 0 Disable 1 Enable Parameter Number 65 Access Rule GET SET Data Type BOOL Group Misc Config Units Minimum Value 0 Maximum Value 1 Default Value 0 KeypadMode This parameter selects if the keypad operation is maintained or momentary 0 Momentary 1 Maintained Parameter Number 66 Access Rule GET SET Data Type BOOL Group Misc Config Units Minimum Value 0 Maximum Value 1 Default Value ...

Страница 146: ...ameters 36 Access Rule GET SET Data Type UINT Group Advanced Config Units x x secs Minimum Value 0 0 Maximum Value 600 0 Default Value 20 0 Maximum Freq Accel Time Accel Rate Parameter 35 Maximum Freq Speed Accel Time 2 0 0 Time Decel Time 2 A c c e l e r a t i o n D e c e l e r a t i o n DecelTime2 When active sets the rate of deceleration for all speed decreases except for jog Parameter Number 7...

Страница 147: ...ter will change the frequency command in real time Parameter Number 72 Related Parameters 33 Access Rule GET SET Data Type UINT Group Advanced Config Units x x Hz Minimum Value 0 0 Maximum Value 400 0 Default Value 60 0 SkipFrequency Sets the frequency at which the drive will not operate Parameter Number 73 Related Parameters 74 Access Rule GET SET Data Type UINT Group Advanced Config Units Hz Min...

Страница 148: ...aximum Value 99 9 Setting of 99 9 Continuous Default Value 0 0 DCBrakeLevel Defines the maximum DC brake current in amps applied to the motor when Parameter 32 StopMode is set to either 0 RAMP or 2 DC BRAKE For0 5Hpunits Min 0 Max 2 7 Default 1 For1 0Hpunits Min 0 Max 4 5 Default 1 For 2 0Hp units Min 0 Max 7 5 Default 2 Parameter Number 76 Related Parameters 32 75 Access Rule GET SET Data Type UI...

Страница 149: ...e changed 0 Enabled 1 Disabled Parameter Number 77 Related Parameters Access Rule GET SET Data Type UINT Group Advanced Config Units Minimum Value 0 Maximum Value 1 Default Value 0 FlyingStartEn Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM 0 Disabled 1 Enabled Parameter Number 78 Access Rule GET SET Data Type UINT Group Advanced Config Units Minimum Value...

Страница 150: ...correct this condition 3 Both Parameter Number 79 Access Rule GET SET Data Type UINT Group Advanced Config Units Minimum Value 0 Maximum Value 3 Default Value 1 SlipHertzAtFLA Compensates for the inherent slip in an induction motor This frequency is added to the commanded output frequency based on motor current Parameter Number 80 Related Parameters 30 Access Rule GET SET Data Type UINT Group Adva...

Страница 151: ...ion Sets the derating factor for I2T motor overload function 0 NoDerating 1 MinDerating 2 MaxDerating Parameter Number 82 Related Parameters 29 30 Access Rule GET SET Data Type UINT Group Advanced Config Units Minimum Value 0 Maximum Value 2 Default Value 0 Min Derate 0 80 100 60 40 20 of Motor Overload Current P30 No Derate 0 80 100 60 40 20 of Motor Nameplate Hertz P29 of Motor Overload Current ...

Страница 152: ...tartTries to a value other than 0 2 Set Parameter 85 AutoRestartDelay to 0 AutoRstrtTries Set the maximum number of times the drive attempts to reset a fault and restart Parameter Number 84 Related Parameter 85 Access Rule GET SET Data Type UINT Group Advanced Config Units Minimum Value 0 Maximum Value 9 Default Value 0 ATTENTION Equipment damage and or personal injury may result if this parameter...

Страница 153: ...Value 120 0 Default Value 1 0 BoostSelect Setstheboost voltage of Parameter 28 MotorNPVolts and redefines the Volts per Hz curve See Table 24 for details Parameter Number 86 Related Parameters 28 29 Access Rule GET SET Data Type UINT Group Advanced Config Units Minimum Value 1 Maximum Value 14 Default Value 8 Table 24 Boost Select Options Options Description Custom V Hz Variable Torque Typical fan...

Страница 154: ...20V AC Maximum Value 460V AC Default Value 2V AC MotorNamePlateFLA Set to themotor nameplate Full Load Amps For0 5Hpunits Min 0 Max 3 0 Default 1 5 For1 0Hpunits Min 0 Max 5 0 Default 2 5 For2 0Hpunits Min 0 Max 8 4 Default 3 6 Parameter Number 88 Related Parameters Access Rule GET SET Data Type UINT Group Advanced Config Units x x Amps Minimum Value 0 0 Maximum Value Hp Dependent Default Value Hp...

Страница 155: ...ameter Number 90 Related Parameters Access Rule GET SET Data Type UINT Group Advanced Config Units x x Hz Minimum Value 0 0 Maximum Value 999 9 Default Value 0 0 BrakeCurrThresh This parameter determines the motor current above which the source brake is released Parameter Number 91 Related Parameters Access Rule GET SET Data Type UINT Group Advanced Config Units x xx Amps Minimum Value 0 0 Maximum...

Страница 156: ...156 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 4 Bulletin 290E 291E 294E Programmable Parameters Notes ...

Страница 157: ...its or has incorrect polarity Flashingyellowindicateslinevoltageisnot present Bulletin 294 units only RUN FLT LED The bicolor green red LED combines the functions of the Run and Fault LEDs Solid green is illuminated when a Run command is present The LED will blink red in a prescribed fault pattern when a protection fault trip condition is present See table for fault blink patterns NS Network Statu...

Страница 158: ...rational Flashing red indicates a resettable protectionfault exists or the node address switches have been changed without a power cycle and do not match the in use configuration Steadyred indicates a non resettable protection fault exists I O Status Enunciators 0 5 LEDs Six yellow LEDs are numbered 0 5 and indicate the status of the input output connectors One LED for each I O point Yellowisillum...

Страница 159: ...eset When manual reset mode faults are latched until a fault reset command has been detected either locally or remotely A Manual reset operation is either remotely via the network locally via the Reset button on the front keypad or via a DeviceLogix program A rising edge 0 to 1 transition of the ResetFault tag will attempt a reset A rising edge of the parameter 44 ProtectFltReset will attempt a re...

Страница 160: ...sts Verify fault by reviewing TripStatus Parameter 16 and TripLog0 4 Parameters 18 22 Correct and press the blue reset button Solid Red Non resettable protection fault exists Verifyfaultbyreviewing TripStatus Parameter16and TripLog0 4 Parameters18 22 Correctandcycle controlpower switchedandunswitched Flashes Green Red Self test on power up No action NS Network Status Indicator Off The NS LED is no...

Страница 161: ...nthetripclassselected thedevice has tripped Verify that the load is operating correctly and is properly set up FLASetting Parameter 28 OLResetLevel Parameter 29 The fault may be reset only after the motor has sufficiently cooled 2 Yes Yes Off Phase Loss Trip The ArmorStart LT has detected a missing phase This fault is generated by monitoring the relative levels of the 3 phase currents Correct phas...

Страница 162: ...oad Trip Underload protection is for undercurrent monitoring A trip occurs when the motor current drops below the trip level Check motor andmechanical system for broken shaft belts or gear box Check ULInhibitTime Parameter 76 ULTripDelay Parameter 77 ULTripLevel Parameter 78 and ULWarningLevel Parameter 79 11 Reserved 12 Reserved 13 Reserved 14 No No On Output Short Trip This fault is generated wh...

Страница 163: ... Exceeding the Drive overload rating of 150 for 1 minute or 200 for 3 seconds caused the device totrip The fault may be reset only after the overload algorithm determines thatthe motor has sufficiently cooled or that the Drive heatsink temperature falls to an acceptable level Check the following 1 Excessive motor load Reduceload sodrive output current does not exceed the current set by MotorOLCurr...

Страница 164: ...ccelTime1 Parameter 36 or AccelTime2 Parameter 69 or reduce load so drive output current does not exceed the current set by CurrentLimit Parameter 31 10 Drive Controlled No On Over Temperature PF4MCode8 This fault occurs when the drive detects a heat sink over temperature condition Check for blocked or dirty heat sink fins Verify that ambient temperature has not exceeded 40 C 104 F 11 No No On Gro...

Страница 165: ...400Y 230 480Y 277 15 10 Rated Impulsed Voltage Uimp 4 kV Dielectric Withstand UL 1960V AC IEC 2500V AC Operating Frequency 50 60 Hz 10 Maximum Rated Operating Current Cat No Hp kW Overload Range 290_ ___ A 291_ ___ A 2 1 5 0 24 3 5 A 290_ ___ B 291_ ___ B 5 3 1 1 7 6 A Overload Type Solid state I2 T Trip Class 10 15 20 with thermal memory retention see Motor Overload Trip Curves Trip Rating Full L...

Страница 166: ... 2 26 4V DC Nominal Current 275 mA Power 6 6 W Number of Inputs x 50 mA user defined Number of Outputs x 500 mA user defined Maximum Current 275 mA user defined Maximum Power 6 6 W 24V DC x user defined Peak Inrush 10 for 35 ms Control Circuit Internal Source An internal 50 W power supply sources 24V DC for input outputs and logic control Short Circuit Current Rating SCCR Cat No Sym Amps RMS Circu...

Страница 167: ...or On Off 0 5 ms 64 ms Filtering 100 μs DeviceLogix I O Response 2 ms 500 Hz Output Supply Voltage Switched Power A1 A2 Type of Outputs DC sourcing Load Types Resistive or light inductive Utilization Category IEC DC 1 DC 13 Output State Normally Open N O Connection Type Single keyed M12 quick disconnect Output per Connection 1 each Overcurrent Protection 1 5 A the sum of all outputs cannot exceed ...

Страница 168: ... 8 12 ms Contactor Closing Delay 18 40 ms Minimum Off Time 200 ms ContactorMechanical Life 15 million operations Power Terminals Motor Terminals Control Terminals PE Ground Wire Size 2 18 10 AWG 0 8 5 2 mm2 per terminal 18 10 AWG 0 8 5 2 mm2 per terminal 2 18 10 AWG 0 8 5 2 mm2 per terminal 2 16 10 AWG 1 3 5 2 mm2 per terminal Wire Type Multi strand copper wire Tightening Torque 10 6 2 lb in 1 2 0...

Страница 169: ...et keying 4 Pin Ethernet Cable Category 5e Shielded or unshielded IP Configuration Static DHCP or BootP DHCP Timeout 30 s Data Transported over both TCP and UDP Packet Rate pps 500 packets per second 2000 μs Tx 500 packets per second 2000 μs Rx Consume Instance Command Default of 3 words Instance 150 Produce Instance Status Default of 14 words Instance 152 Message Support Unicast or Multicast Addr...

Страница 170: ... EN P June2012 Chapter 6 Specifications Motor Overload Trip Curves Class 10 Full Load Current Approximate Trip Time s Cold Hot Class 15 Full Load Current Approximate Trip Time s Cold Hot Class 20 Full Load Current Approximate Trip Time s Cold Hot ...

Страница 171: ... 0 01 0 1 1 10 Used with ArmorStart LT 100 K09 Bulletin 100 K 104 K Life Load Curves Electrical life Ue 400 460V AC AC 3 Switching of squirrel cage motors while starting Contact Life millions of operations Rated Current Ie AC 4 A 0 1 1 10 0 01 0 1 1 10 100 K09 Used with ArmorStart LT Electrical life Ue 400 460V AC AC 4 Stepping of squirrel cage motors ...

Страница 172: ...ry III Reset Mode Automatic or manual Output Frequency 0 400 Hz programmable Efficiency 97 5 typical Overvoltage 380 480V AC Input Trip occurs at 810V DC bus voltage equivalent to 575V AC incoming line Undervoltage 380 480V AC Input Trip occurs at 390V DC bus voltage equivalent to 275V AC incoming line Control Ride Through Minimum ride through is 0 5 s typical value is 2 s Faultless Power Ride Thr...

Страница 173: ... Power 6 6 W Number of Inputs x 50 mA user defined Number of Outputs x 500 mA user defined Maximum Current 275 mA user defined Maximum Power 6 6 W 24 xuser defined 60 W max Peak Inrush 10 A for 35 ms Control Circuit Internal Source An internal 50 W power supply sources 24V DC forinput outputs and logic control Short Circuit Current Rating SCCR Cat No Sym Amps RMS Circuit Breaker Fuse 294_ G1 or G3...

Страница 174: ...On or On Off 0 5 ms 64 ms Filtering 100 μs DeviceLogix I O Response 2 ms 500 Hz Output Supply Voltage Switched Power A1 A2 Type of Outputs DC sourcing Load Types Resistive or light inductive Utilization Category IEC DC 1 DC 13 Output State Normally Open N O Connection Type Single keyed M12 quick disconnect Output per Connection 1 each Overcurrent Protection 1 5 A the sum of all outputs cannot exce...

Страница 175: ...k shackle or hasp Disconnect LOTO Locks Up to 2 locks or hasps are supported Disconnect Mechanical Life 200 000 operations Power Terminals Motor Terminals Control Terminals PE Ground Source Brake Wire Size 2 18 10 AWG 0 8 5 2 mm2 per terminal 18 10 AWG 0 8 5 2 mm2 per terminal 2 18 10 AWG 0 8 5 2 mm2 per terminal 2 16 10 AWG 1 3 5 2 mm2 per terminal 16 10 AWG 1 0 4 0 mm2 per terminal Wire Type Mul...

Страница 176: ... Certifications cULus File No E207834 Guides NMMS NMMS7 Communication Ratings Rated Insulation Voltage 250V Operating Dielectric Withstand UL NEMA 1500V AC IEC 2000V AC DeviceNet DeviceNet Supply Voltage Rating Range 11 25V DC 24V DC nominal DeviceNet Input Current 50 mA 24V DC DeviceNet Input Current Surge 500 mA peak inrush Baud Rates 125 250 500 kbps Distance Maximum 500 m 1630 ft 125 kbps 200 ...

Страница 177: ...mmand Default of 4 words Instance 154 Produce Instance Status Default of 16 words Instance 156 Message Support Unicast or Multicast Address Conflict Detection ACD IP v4 Address Conflict Detection for EtherNet IP devices Sockets 150 maximum Web Server Security Login and password configurable E mail Support Simple Mail Transfer Protocol SMTP Webpage Features Status diagnostics configuration Concurre...

Страница 178: ...s inherent in the electronic design of the overload Min Derate 0 80 100 60 40 20 of Motor Overload Current P30 No Derate 0 80 100 60 40 20 of Motor Nameplate Hertz P29 of Motor Overload Current P30 of Motor Nameplate Hertz P29 of Motor Overload Current P30 of Motor Nameplate Hertz P29 Max Derate 0 80 100 60 40 20 0 200 175 150 125 100 75 50 25 0 200 175 150 125 100 75 50 25 0 200 175 150 125 100 7...

Страница 179: ...ddresses only NFPA 79 applications This is not because these products are only suitable for industrial machinery but because industrial machinery is their primary market In fact while all versions of the ArmorStart LT products may be applied on industrial machinery the versions that have the Conduit Entrance Gland Plate Option may also be used in applications governed by NFPA 70 National Electrica...

Страница 180: ...the ArmorStart LT motor controllers that are relevant to applying them in multiple motor branch circuits The term motor controller refers to the device that stops and starts the motor The ArmorStart LT product family consists of two types of motor controllers The Bulletin 290 and 291 controllers are magnetic motor controllers that use an electromechanical contactor to stop and start the motor The ...

Страница 181: ...troller In exchange for eliminating the cost and space necessary for a dedicated set of fuses in front of each controller the construction of each controller itself must be more robust For the circuit configuration shown in Figure 58 to be practical the ampere rating of the fuse must be large enough to operate all of the motors without opening under normal starting and running conditions This rati...

Страница 182: ...troller on the left UL 508C permits the individual motor testing to be performed with the maximum rating of fuse that can be used to protect an individual motor branch circuit According to both NFPA 70 and NFPA 79 this is 400 percent of the full load current rating of the largest motor that the controller can supply In UL 508C this is taken to be 400 percent of the rated output current of the cont...

Страница 183: ...eaker or a single set of fuses provided the following conditions under 1 and either 2 or 3 are met 1 Each motor controller and overload device is either listed for group installation with specified maximum branch circuit protection or selected such that the ampere rating of the motor branch short circuit and ground fault protective device does not exceed that permitted by 7 2 10 1 for that individ...

Страница 184: ... Each motor controller and overload device is listed for group installation with specified maximum branch circuit protection e 2 The rating or setting of the branch short circuit and ground fault protection device does not exceed the values in Table 7 2 10 4 for the smallest conductor in the circuit f Summarizing the requirements relevant to Figure 58 7 2 10 4 1 and 7 2 10 4 2 permit two or more A...

Страница 185: ...ollers have the Conduit Entrance Gland Plate Option Fuses protect the branch circuit The example addresses five basic requirements that the motor controllers fuses and conductors must satisfy The letters in the circles on Figure 61 and Figure 62 are referenced in the explanations as letters in parentheses Ellipses points are used to replace NFPA 79 text that is not applicable to the multiple motor...

Страница 186: ...r restrict the fuse Compare to controller max fuse ratings Suitable for Motor Group Installation Max Ratings 5 KA 10 KA 45A 45A Sym Amps RMS Fuse Type CC J andT fuses only Conductor protection 60 A max any class Determine fuse class and max rating for conductor protection Conductor protection Smallest conductor 7 2 10 4 2 smallest conductor in the circuit 14 AWG Table 7 2 10 4 Max Fuse AWG A 14 60...

Страница 187: ... the fuse s indicates that the maximum protection specified on the nameplate applies to these fuse s 2 Requirement Two Conductor Short circuit and Ground Fault Protection The fuse must protect the conductors for short circuit faults and ground faults Text 7 2 10 4 2 The rating or setting of the branch short circuit and ground fault protection device does not exceed the values in Table 30 for the s...

Страница 188: ...uctor by limiting two things the ratio of the ampacity of the larger conductor to the ampacity of the smaller conductor and the maximum length of the smaller conductor see for example 7 2 8 2 When applying 7 2 10 4 2 such a tap rule is neither applicable nor necessary In Figure 61 the smaller 14 AWG conductors may be connected to combined load conductors of any size because 7 2 10 4 does not indir...

Страница 189: ...n tested with and are intended to be used with fuses having a class of RK 5 Of course fuses of a class that have lower let throughs than Class RK 5 such as Class CC J or T are also acceptable A fuse having a rating of any class also restricts the fuse to those that have been evaluated for use as branch circuit protection devices This means that semiconductor fuses used to protect power electronic ...

Страница 190: ...not less than 125 percent of the motor full load current rating 12 5 4 Combined load conductors shall have an ampacity not less than 125 percent of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all other connected motors Analysis Referring to Figure 62 a b and c explain the method for calculating the minimum required conductor ampacity for...

Страница 191: ...t of the output conductors must be 125 of the motor full load current rating Referring to Figure 62 the 1 Hp Bulletin 294E controller has a rated input current of 3 0 amperes Using the rated input current the conductors from the combined load conductors to the controllers must have an ampacity of 125 of 3 0 A or 3 75 A The output conductors must have an ampacity of 125 of 2 1 A or 2 6 A Combined L...

Страница 192: ... currents to the motor because the input currents contain harmonics resulting from the power conversion process This harmonic content and the magnitude of the resulting non sinusoidal input currents depend on the impedance of the electrical supply The value specified for the rated input current is the maximum value over the range of possible supply impedances For this reason the magnitude of curre...

Страница 193: ...oduct Code Current Rating Identity Object Name String Integrated Power Supply 0x301 0 24 3 5 amps ArmorStart 290E 0 24 3 5 A No 0x302 1 1 7 6 amps ArmorStart 290E 1 1 7 6 A No 0x311 0 24 3 5 amps ArmorStart 290EP 0 24 3 5 A Yes 0x312 1 1 7 6 amps ArmorStart 290EP 1 1 7 6 A Yes 0x341 0 24 3 5 amps ArmorStart 291E 0 24 3 5 A No 0x342 1 1 7 6 amps ArmorStart 291E 1 1 7 6 A No 0x351 0 24 3 5 amps Armo...

Страница 194: ...ny output consumed Assembly instance Class Code 0x04 Attribute 3 or 4 of the Control Supervisor Object Class Code 0x29 EDS Files The information contained in the EDS Electronic Data Sheet files for ArmorStart LT EtherNet IP can be extracted via the network CIP Object Requirements The following CIP objects will be covered in the following subsections For convenience all objects that are accessible ...

Страница 195: ...vision Attribute 1 Main Control Board The firmware rev of the main control board operating system 3 PowerFlex 4M Bulletin 294E only The firmware revision of the PowerFlex 4M Attribute ID Access Rule Name Data Type Value 1 Get Vendor UINT 1 2 Get Device Type UINT 22 3 Get Product Code UINT Product Code specific 4 Get Revision Major Revision Minor Revision Structure of USINT USINT 5 Get Status WORD ...

Страница 196: ...Self testing or unknown 1 Firmware update in progress 2 At least one faulted I O connection 3 No I O connections established 4 Non volatile configuration bad 5 Major fault either bit 10 or bit 11 is true 1 6 At least one I O connection in run mode 7 At least one I O connection established all in idle mode Service Code Implemented for Service Name Class Instance 0x01 Yes Yes Get_Attributes_All 0x05...

Страница 197: ...rvice Name Class Instance 0x0E Yes Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single Instance Type Description 3 Consumed Required ODVA Consumed Instance 52 Produced Required ODVA Produced Instance 100 Config Configuration Assembly for Bulletin 290E 291E Starters 101 Config Configuration Assembly for Bulletin 294E Starters 150 Consumed Default Consumed Instance for Bulletin 290E 291E units...

Страница 198: ...etFltAction 45 9 18 RunNetFltValue 46 10 20 RunNetIdleAction 47 11 22 RunNetIdleValue 48 12 24 IOPointConfigure 49 13 26 FilterOffOn 50 14 28 FilterOnOff 51 15 30 OutProtFltState 52 16 32 OutProtFltValue 53 17 34 OutNetFltState 54 18 36 OutNetFltValue 55 19 38 OutNetIdleState 56 20 40 OutNetIdleValue 57 21 42 Input00Function 58 22 44 Input01Function 59 23 46 Input02Function 60 24 48 Input03Functio...

Страница 199: ...NPVolts 28 3 6 MotorNPHertz 29 4 8 MotorOLCurrent 30 5 10 CurrentLimit 31 6 12 StopMode 32 7 14 SpeedReference 33 8 16 MinimumFreq 34 9 18 MaximumFreq 35 10 20 AccelTime1 36 11 22 DecelTime1 37 12 24 SCurvePercent 38 13 26 JogFrequency 39 14 28 JogAccelDecel 40 15 30 ProtFltResetMode 41 16 32 ProtectFltEnable 42 17 34 WarningEnable 43 18 36 RunNetFltAction 45 19 38 RunNetFaultValue 46 20 40 RunNet...

Страница 200: ...1 82 AccelTime2 69 42 84 DecelTime2 70 43 86 MotorOLRetention 71 44 88 InternalFreq 72 45 90 SkipFrequency 73 46 92 SkipFreqBand 74 47 94 DCBrakeTime 75 48 96 DCBrakeLevel 76 49 98 ReverseDisable 77 50 100 FlytingStartEna 78 51 102 Compensation 79 52 104 SlipHertzAtFLA 80 53 106 BusRegulateMode 81 54 108 MotorOLSelect 82 55 110 SWCurrentTrip 83 56 112 AutoRestartTries 84 57 114 AutoRestartDelay 85...

Страница 201: ...In Pt08DeviceIn 4 AnalogDeviceIn low byte 5 AnalogDeviceIn high Byte Instance 152 Starter Stat DeviceLogix Produced Assembly for Bulletin 290E 291E Starters Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Reserved 1 Reserved 2 Reserved 3 Reserved 4 CurrentFlowing NetControlStatus Ready RunningReverse RunningForward WarningPresent TripPresent 5 DisconnectClosed KeyPadHand KeyPadOff KeyPadAut...

Страница 202: ...ecel2 Accel2 Out05 Out04 Out03 Out02 Out01 Out00 2 CommandFreq Low xxx x Hz 3 CommandFreq High xxx x Hz 4 Pt07DeviceIn Pt06DeviceIn Pt05DeviceIn Pt04DeviceIn Pt03DeviceIn Pt02DeviceIn Pt01DeviceIn Pt00DeviceIn 5 Pt15DeviceIn Pt14DeviceIn Pt13DeviceIn Pt12DeviceIn Pt11DeviceIn Pt10DeviceIn Pt09DeviceIn Pt08DeviceIn 6 An00DeviceIn lowbyte 7 An00DeviceIn highbyte Instance 156 Drive Status Produced As...

Страница 203: ...arameter 13 InternalFanRPM 25 26 Parameter 14 ElaspedRunTime 27 28 Parameter 15 DriveTemperature 29 30 Parameter 16 TripStatus 31 32 Parameter 17 WarningStatus 33 Instance 156 Drive Status Produced Assembly for Bulletin 294E Starters Attribute ID Access Rule Name Data Type Value 1 Set Open Requests UINT Number of Forward Open service requests received 2 Set Open Format Rejects UINT NumberofForward...

Страница 204: ... exclusive owner connection can be opened against the module If an exclusive owner connection is already opened Connection in Use General Status 0x01 Extend Status 0x0100 shall be returned an error code Connection point O T shall be Assembly object Instance 3 150 or 154 Connection point T O shall be Assembly object Instance 52 152 or 156 7 Set Close Other Requests UINT Number ofForward Close servi...

Страница 205: ...ion of the Forward_Open be zero there are however no checks that this is actually the case If no other connection exists when listen only tries to be opened a Controlling connection not open general status 0x01 extend status 0x0119 error message shall be sent Number of supported listen only connections equals four shared with exclusive owner and input only connection Class 3 Connections ExplicitMe...

Страница 206: ...ported fo 0x10 No Yes Set_Attribute_Single 0x4E No Yes Forward_Close 0x54 No Yes Forward_Open Service Code Implemented for Service Name Class Instance Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 2 Get Max Instance UINT 6 Attribute ID Access Rule Name Data Type Value 3 Get Value BOOL 0 OFF 1 ON 4 Get Fault Status BOOL 0 OK 1 Fault 115 Get Set Force Enable BOOL 0 Disable 1 En...

Страница 207: ... idle conditions and protection fault conditions An output point must know how to select which source of data to use to drive its value attribute Instance Name Alternate Mapping Description 1 Run Fwd Output 0029 01 03 Run Forward output 2 Run Rev Output 0029 01 04 Run Reverse output 3 User Output A None These are the six ArmorStart LT user outputs for all starter types Their fault idle behavior is...

Страница 208: ...3 State Transition for Unbound Bulletin 290E Non Existent Available Idle Ready Run DNet Fault Receive Idle Power off Connection Transitions to Established Protection Fault Protection Fault Protection Fault Protection Fault Reset Connection Transitions to Established DNet Fault Receive Data DNet Idle Ready DNet Fault Protection Fault Protection Fault DNet Fault Power up ...

Страница 209: ...tection Fault Unrecoverable Network Fault EM I O Comm Override DN Fault DN Idle Available Pr Fault Action Ignore Network Fault Override Logic Enabled Run Use DNIdle Action DNIdle Value Use DNFault Action DNFault Value Use PrFault Action PrFault Value Apply Force Value Perform LEO Function Clear Value Ignore Message Return Object State Conflict Apply Value Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Ye...

Страница 210: ...or Bound Bulletin 290E Protection Fault Unrecoverable Network Fault EM I O Comm Override DN Fault DN Idle Available Network Fault Override Logic Enabled Run Use DNIdle Action DNIdle Value Use DNFault Action DNFault Value Turn off output Apply Force Value Perform LEO Function Clear Value Ignore Message Return Object State Conflict Apply Value Yes Yes Yes Yes Yes Y es Yes Yes Yes Yes Yes ...

Страница 211: ... will supported It will represent the Frequency command sent to the PF40 via the DSI link CommandFreq from Assembly 154 is placed in the Value Attribute when it is consumed The Value Attribute can then be overwritten by DeviceLogix Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 2 Get Max Instance UINT 1 Attribute ID Access Rule Name Data Type Value 1 Get Value INT 0 Default Se...

Страница 212: ...tribute_Single Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 Get Max Instance UINT 8 Get Parameter Class Descriptor WORD 9 Get Configuration Assembly Instance UINT 100 for Bulletin 290E 291E units 101 for Bulletin 294E units Attribute ID Access Rule Name Data Type Value 1 Get Set Value Specified in Descriptor 2 Get Link Path Size USINT 3 Get Link Path Array of BYTE EPATH 4 Ge...

Страница 213: ...Get Base Link UINT 20 Get Offset Link UINT 21 Get Decimal Precision USINT Attribute ID Access Rule Name Data Type Value Service Code Implemented for Service Name Class Instance 0x01 No Yes Get_Attribute_All 0x0E Yes Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single 0x4b No Yes Get_Enum_String Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 Get Max Instance UINT Attribut...

Страница 214: ...will contain the following attributes Instance 2 controls the communication fault and idle behaviors for run jog outputs Instance 2 contains the following instance attributes Attribute ID Access Rule Name Data Type Value 3 Get Number of Instances USINT 6 4 Get Binding Array of UINT List of DIP Instances 6 Get Set Off_On_Delay UINT 7 Get Set On_Off_Delay UINT Service Code Implemented for Service Na...

Страница 215: ...Binding Array of UINT 1 2 for DOLs Bulletin 290E 291E 1 2 9 10 for Drives Bulletin 294E 6 Get Set Command BOOL 0 Idle 1 Run 7 Get Set Fault Action BOOL 0 Fault Value Attribute 1 Hold Last State 8 Get Set Fault Value BOOL 0 OFF 1 On 9 Get Set Idle Action BOOL 0 Idle Value Attribute 1 Hold Last State 10 Get Set Idle Value BOOL 0 OFF 1 On Attribute ID Access Rule Name Data Type Value 3 Get Number of ...

Страница 216: ...BOOL These Run outputs also map to DOP Instances 1 and2 4 Get Set Run 2 BOOL 7 Get Running 1 BOOL 8 Get Running 2 BOOL 9 Get Ready BOOL 10 Get Tripped BOOL 12 Get Set Fault Reset BOOL 0 1 Trip Reset Service Code Implemented for Service Name Class Instance 0x0E No Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single Attribute ID Access Rule Name Data Type Value 3 Get Set FLA Setting BOOL xxx x...

Страница 217: ...nted for Service Name Class Instance 0x01 No Yes Get_Attribute_All 0x0E No Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 Attribute ID Access Rule Name Data Type Value 1 Get Network Topology USINT 0 Linear 1 Ring 2 Get Network Status USINT 0 Normal 1 Ring Fault 2 Unexpected Loop Detect 3 Partial Network Fault 4 Rapid Fa...

Страница 218: ... chars max 101 Set Contacxts 1 STRING Contacts String Defaults to a null 80 chars max 102 Set Contacts 2 STRING Contacts String Defaults to a null 80 chars max Service Code Implemented for Service Name Class Instance 0x01 No Yes Get_Attribute_All 0x0E Yes Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single Attribute ID Access Rule Name Data Type Value 1 Get Class Revision UINT 1 2 Get Number...

Страница 219: ...amp Timer Value Timer Descriptor Struct of UINT Struct of USINT USINT Struct of ULINT WORD See Tables below 0 3 Get Help Text STRING See Tables below Service Code Implemented for Service Name Class Instance 0x0E Yes Yes Get_Attribute_Single 0x10 Yes No Set_Attribute_Single Table 33 Fault Codes Fault Text and Fault Help Strings for DOL and Reversers Fault Code Fault Text Help Text 1 Fault 1 2 User ...

Страница 220: ...unitswithIntegratedPowerSupply 22 Fault 22 23 Fault 23 24 Fault 24 25 Fault 25 26 Fault 26 27 NonVol Memory This is a major fault which renders the unit inoperable 28 Fault 28 29 Fault 29 30 Hardware Fault This is a major fault which renders the unit inoperable 31 Fault 31 32 Fault 32 33 Fault 33 34 Fault 34 35 Fault 35 36 Fault 36 37 Fault 37 38 Fault 38 39 Fault 39 40 Unknown Fault Table 34 Faul...

Страница 221: ...ip has been exceeded 63 21 Aux Power Loss Auxiliary Power was lostor dipped below the minimum threshold NotavailableinunitswithIntegratedPowerSupply 22 Internal Comm Communication with the internal Power Flex drive has been lost 71 23 Drive Comm Loss The RS485 port on the internal Power Flex stopped communicating 81 24 Power Loss Drive DC Bus Voltage remained below 85 of nominal bus voltage 3 25 U...

Страница 222: ...Recorded Alarms UINT The number of faults recorded in the fault queue Attribute ID Access Rule Name Data Type Value 0 Get Full All Info Alarm Code Alarm Source DPI Port Number Device Object Instance Alarm Text Alarm Time Stamp Timer Value Timer Descriptor Help Object Interface Alarm Data Struct of UINT Struct of USINT USINT STRING Struct of ULINT WORD USINT See Tables below 0 See Tables below 1 Ge...

Страница 223: ...dPowerSupply 14 Under Power Warn Indicates the internal power supply is below its optimal level AvailableinunitswithIntegrated PowerSupplyonly 15 Warning 15 16 Warning 16 17 Warning 17 18 Warning 18 19 Warning 19 20 Warning 20 21 Aux Power Warn Indicates auxiliary Power was has dipped below 19 Volts NotavailableinunitswithIntegratedPowerSupply Table 35 Fault Codes Fault Text and Fault Help Strings...

Страница 224: ...9 Get Set Multicast Config Structure of USINT USINT UINT UDINT Allocation Control Reserved Number of multicastaddresses to allocate 1 4 Multicast starting address 10 Get Set SelectAcd BOOL Activates the use of ACD 11 LastConflictDetected Structure of USINT USINT 6 USINT 28 AcdActivity RemoteMAC ArpPdu Attribute ID Access Rule Name Data Type Value Service Code Implemented for Service Name Class Ins...

Страница 225: ...f Alignment Errors FCS Errors Single Collisions SQE Test Errors Deferred Transmits LateCollisions Excessive Collisions MAC Transmit Errors Carrier Sense Errors Frame Too Long MAC Receive Errors 6 Get Set Interface Control Struct of Control Bits Forced Interface Speed 7 Get Interface Type USINT 8 Get Inteface State USINT 9 Get Set Admin State USINT 10 Get Interface Label SHORT_STRING Instance 1 LS ...

Страница 226: ... ASCII characters 7 Required Set NV SMTP Password Struct of SMTP Password String The default value of this string is the null string To Length UDINT Length of string in bytes To Data Array of USINT ASCII characters 8 Required Set NV SMTP Port UINT The SMTP Port The Default Value is 0 9 Optional Set NV TripEmail Mask WORD Mask to enableemails for individual trip conditions 10 Optional Set NV Warnin...

Страница 227: ...CIP Information Appendix B The following common services will be implemented for the TCP IP Interface Object Service Code Implemented for Service Name Class Instance 0x01 No Yes Get_Attribute_All 0x0E No Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single ...

Страница 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...

Страница 229: ... If the Network Override is enabled and the logic is enabled then DeviceLogix controls the state of the outputs when the PLC is in Run mode and if a network fault occurs If the Communications Override is enabled and the logic is enabled the device does not need any I O connection to run the logic As long as there are switched and unswitched power sources connected to the device the logic will cont...

Страница 230: ...ctions There are many reasons to use the DeviceLogix functionality but some of the most common are listed below Increased system reliability Fast update times 1 2 ms possible Improved diagnostics and reduced troubleshooting Operation independent of PLC or Network status Continue to run process in the event of network interruptions Critical operations can be safely shutdown through local logic Devi...

Страница 231: ...ar Click on the Discrete Input button and select Pt00 from the pull down menu This is the remote start button based on the example I O table 8 Place the input to the left of the RSL function To drop the input on the page left click on the desired position 9 Place the mouse cursor over the tip of Pt00 The tip will turn green Click on the tip when it turns green 10 Move the mouse cursor toward the i...

Страница 232: ...input of the RSL latch 14 From the toolbar Click on the Discrete Output button and select RunForward from the pull down menu RunForward is the relay controlling the coil of the contactor Click OK 15 Move the cursor into the grid and place the Output to the right of the RSL function block 16 Connect the output of the RSL function block to Run Fwd 17 Click on the Verify button located in the toolbar...

Страница 233: ...nput and Output Variables Element Type Bulletin 290E Bulletin 291E Bulletin 294E Consumed Network Data PT00DeviceIn PT00DeviceIn PT00DeviceIn PT15DeviceIn PT15DeviceIn PT15DeviceIn Discrete Input Points PT00 PT00 PT00 PT00 PT00 PT00 Discrete Output Points RunForward RunForward RunForward RunReverse RunReverse Out00 Out00 Out00 Out05 Out05 Out05 JogForward JogReverse Produced Network Data Pt00Devic...

Страница 234: ...cTrip JamTrip JamTrip DCBusFaults StallTrip StallTrip StallTrip UnderloadTrip UnderloadTrip UnderloadTrip GroundFault RestartRetries DriveHdwFault OutputShortTrip OutputShortTrip OutputShortTrip UserDefinedTrip UserDefinedTrip UserDefinedTrip HardwareFltTrip HardwareFltTrip HardwareFltTrip Warnings OverloadWarning OverloadWarning OverloadWarning UnderPowerWarn UnderPowerWarn UnderPowerWarn PhaseIm...

Страница 235: ...tCnxnFault ExplicitCnxnFault ExplicitCnxnFault IOCnxnFault IOCnxnFault IOCnxnFault IOCnxnIdle IOCnxnIdle IOCnxnIdle DLREnabled DLREnabled DLREnabled DLRFault DLRFault DLRFault Analog Input Point NetInputFreq Analog Output Point CommandFreq Misc Analog Input Data PhaseL1Current PhaseL1Current OutputFreq PhaseL2Current PhaseL2Current OutputCurrent PhaseL3Current PhaseL3Current OutputVoltage AverageC...

Страница 236: ... system set Control Logix 1756 EN2TR EtherNet IP module for Control Logix The IP address of the Hardware will be preset to as followed The Armorstart LT control power wiring example used Figure 1 Control Power Wiring Example Item Description IP Address 1 ArmorStart LT 192 168 1 36 2 1756 EN2TR 192 168 1 32 3 PC 192 168 1 89 Outputs Inputs EtherNet Comms A3 A1 A2 Off Switched Control Power Unswitch...

Страница 237: ...et Explorer and enter the following URL http support rockwellautomation com controlflash LogixProfiler asp 2 From the list of the Add On I O Modules Profiles scroll down and select Bulletin 290E 291E 294E ArmorStart LT from the list and download the file 3 To download the file your RSLOGIX 5000 Serial Number will be prompted Enter the Serial Number and click on the Qualify For Update button to pro...

Страница 238: ...2 Appendix C Using DeviceLogix 4 Upon verification the following screen will appear Click on the link to download the file 5 At the pop up dialogue box select Save to save the file 6 Select the folder to save the file and click Save The downloading will start ...

Страница 239: ...ceLogix Appendix C 7 Upon the completion of downloading unzip the files to the folder 8 Run the MPSetup exe from the folder and start installation 9 The following dialog box will appear 10 The RSLogix 5000 Module Profiles Setup window will be shown Click Next to continue ...

Страница 240: ... RockwellAutomationPublication290E UM001B EN P June2012 Appendix C Using DeviceLogix 11 Select I accept the terms in the license agreement and click on Next 12 Then click on Next to proceed to installation ...

Страница 241: ...RockwellAutomationPublication290E UM001B EN P June2012 241 Using DeviceLogix Appendix C 13 Select Install to start installation 14 The profiles will be installed upon completion click on Next to proceed ...

Страница 242: ...EN P June2012 Appendix C Using DeviceLogix 15 To complete click on Finish Use of the AOP in RSLogix 5000 1 Start the RSLogix5000 from Start Rockwell Software RSLogix 5000 Enterprise Series RSLogix 5000 2 Start a new project by clicking on the icon ...

Страница 243: ...3 Using DeviceLogix Appendix C 3 In the controller dialog box enter the appropriate information of the controller Then click OK to proceed 4 In the Controller Organizer window find I O Configuration and right click on the 1756 Backplane and select New module ...

Страница 244: ...n290E UM001B EN P June2012 Appendix C Using DeviceLogix 5 Select Module Dialog box followed by Communications and then select 1756 EN2TR and click OK 6 In the New module dialog box enter the Unit name IP address and slot then click OK ...

Страница 245: ...O Configuration 1756 Backplane 1756 EN2TR select New Module 8 In the Select Module window select Other and choose the 294E FD2P5Z and click on OK Note Please select the appropriate module If the wrong module is selected once RSLOGIX 5000 is in Online with the controller a yellow triangle will appear next to the module indicating an I O error has occurred ...

Страница 246: ... New Module window enter the Name of the Armorstart LT and the IP address assigned to it You can now start to configure the ArmorStart LT Begin with Motor Protection Control 10 At the Motor Protection Control enter the motor information Note Please refer to the motor nameplate for the information ...

Страница 247: ... Logix The speed of the motor will be control by the controller tag in the Contrologix Configure the Acceleration Deceleration and Jog Frequency here 12 Then proceed to the Fault Configuration and configure the reset mode to Automatic or Manual Then click OK to proceed 13 Download the configuration to the controller To download select Communication Who Active ...

Страница 248: ...ho Active window select the 1756 EN2TR then the controller and click on the Download button 15 The Download dialog box will appear click on Download to proceed 16 The configuration will be downloaded and the Downloading dialog box will show the progress 17 Upon completion select Run Mode as per shown ...

Страница 249: ...N P June2012 249 Using DeviceLogix Appendix C 18 Double click on the Armorstart_LT at the Controller Organizer 19 Proceed to the Status to check the status of the ArmorStart LT 20 Double click on the Controller Tags at the Controller Organizer ...

Страница 250: ...6_O RunReverse The motor will run in the reverse direction 24 Change the value of the FreqCommand to vary the speed Note Setting the tag value to 500 instructs the drive to run at 50 0Hz This example configuration is now complete If additional help is needed please contact your Rockwell Automation sales representative or technical support Name Value Description Armorstart_LT_36 O FreqCommand 300 3...

Страница 251: ......

Страница 252: ...f your product is not functioning and needs to be returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Trademark List Allen Bradley ArmorConnect ArmorStart LT ControlLogix Comp...