146
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
Advanced Configuration
SetToDefaults
This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults
Parameter Number
68
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
AccelTime2
When active, sets the rate of acceleration for all speed increases except for jog.
Parameter Number
69
Related Parameters
36
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 2
0
0
Time
Decel
Time 2
Acc
eler
ation
Dec
eler
ation
DecelTime2
When active, sets the rate of deceleration for all speed decreases except for jog.
Parameter Number
70
Related Parameters
37
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Maximum Freq
Decel Time
--------------------------------------
Decel Rate
=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 2
0
0
Time
Decel
Time 2
Acc
eler
ation
Dec
eler
ation
Содержание ArmorStart 290E
Страница 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...
Страница 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...
Страница 66: ...66 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 2 Installation and Wiring Notes ...
Страница 98: ...98 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 3 Product Commissioning Notes ...
Страница 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...
Страница 251: ......