Chapter 5
Diagnostics
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart LT Distributed Motor
Controller are designed to help you pinpoint a problem for easy troubleshooting
and quick restarting.
Protection Faults
Protection faults will be generated when potentially dangerous or damaging
conditions are detected. Protection faults are also known as “trips” or “faults”.
These faults will be reported in multiple formats, including:
•
Bit enumeration in the TripStatus parameter (parameter 16) used as
discrete bits or in DeviceLogix
•
In the ArmorStart LT web server for ArmorStart EtherNet/IP version
•
As a sequence of LED flashes on the ECM
MS – Module Status
LED
The bicolor (green/red) LED indicates the
status of the module.
Flashing bicolor (red/green) indicates a
self-test on power up.
Flashing green indicates the device has not
been assigned an IP address.
Steady green indicates the device is
configured and operational.
Flashing red indicates a resettable
protection fault exists or the node address
switches have been changed without a
power cycle and do not match the in-use
configuration.
Steady red indicates a non-resettable
protection fault exists.
I/O Status
Enunciators 0…5
LEDs
Six yellow LEDs are numbered 0…5 and
indicate the status of the input/output
connectors. One LED for each I/O point.
Yellow is illuminated when input is valid or
output is on.
Off when input is not valid or the output is
not turned on.
Reset Button
The blue reset button will cause a
protection fault reset to occur.
—
—
Table 25 - ArmorStart LT Status and Diagnostics Indicators
Indicator
Description
Color_1
Color_2
LED Flash
Bit Enumeration
Bulletin 290E/291E Trip Status Bits
Bulletin 294E Trip Status Bits
1
0
OverloadTrip
➊
OverloadTrip
➊
2
1
PhaseLossTrip
PhaseLShortTrip
3
2
UnderPowerTrip
➊
UnderPowerTrip
➊
4
3
SensorShortTrip
➊
SensorShortTrip
➊
5
4
PhaseImbalTrip
OverCurrentTrip
6
5
NonVolMemoryTrip
➊
NonVolMemoryTrip
➊
7
6
reserved
ParamSyncTrip
➊
8
7
JamTrip
DCBusOrOpenDiscnnct
➊
9
8
StallTrip
StallTrip
➊
10
9
UnderloadTrip
OverTemperature
➊
11
10
reserved
GroundFault
➊
12
11
reserved
RestartRetries
13
12
reserved
DriveHdwFault
➊
Содержание ArmorStart 290E
Страница 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...
Страница 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...
Страница 66: ...66 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 2 Installation and Wiring Notes ...
Страница 98: ...98 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 3 Product Commissioning Notes ...
Страница 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...
Страница 251: ......