32
Rockwell Automation Publication 1732E-UM001A-EN-P - December 2019
Chapter 3
Configure Module Using Generic Profile
Configuration Data
16-bit configuration data with diagnostics and padding byte, default I/O
mapping, assembly Instance 110.
Description of Process Data
Terms
The following table lists the definition for terms that are used in the process data
tables for the ArmorBlock 16-channel configurable digital module.
Parameter
Datatype
CfgSize
DINT
CfgIDNum
DINT
Pt00FaultDelay…Pt15FaultDelay
INT
Pt00Fault…Pt15Fault
INT
Pt00FaultValue…Pt015FaultValue
BIT
Pt00FaultMode…Pt15FaultMode
BIT
MiscSettings
INT
QuickConnectEn
BIT
WebServerDisable
BIT
OutputGroupPowerFaultEn
BIT
OutputGroupFaultEn
BIT
DOAutoRestartEn
Bit
Pt00DataDirection…Pt15DataDirection
INT
Pt00IOMapping…Pt15IOMapping
INT
Table 19 - Description of Terms in Process Data Tables
Parameter
Description
C0…C15
Refers to the status of the channel.
PowerFault
Sensor power supply voltage is < 18V ±1V.
FieldPowerLow
Output power supply voltage is < 18V ±1V.
InputGroupFault
Sensor error
OutputGroupFault
Output error
InternalFault
Module error
Ptxx_xxInputShortCircuit
Sensor short-circuit on ports P0…P7
PtxxOutputFault
Output fault on channels C0…C15
PtxxFaultDelay
Fault delay on channels C0…C15
PtxxFaultValue
Fault value for channels C0…C15
PtxxDataDirection
Direction of data for channels C0…C15
QuickConnectEn
Enables or disables QuickConnect.
0 = Disable (default), 1 = Enable
WebServerDisable
Enables or disables the web server.
0 = Enable (default), 1 = Disable
Содержание ArmorBlock 1732E-16CFGM12M12LDR
Страница 6: ...6 Rockwell Automation Publication 1732E UM001A EN P December 2019 Preface Notes...
Страница 28: ...28 Rockwell Automation Publication 1732E UM001A EN P December 2019 Chapter 2 Configure and Startup Notes...
Страница 38: ...38 Rockwell Automation Publication 1732E UM001A EN P December 2019 Chapter 4 Diagnostic Properties Notes...
Страница 41: ......