Rockwell Automation Publication 1732E-UM001A-EN-P - December 2019
13
Configure and Startup
Chapter 2
Output Fault Delay Configuration
These parameters are used when the module is configured with digital outputs.
The configuration can be used to set a delay time (Output Fault Delay) that
defines the monitoring procedure for the individual digital output for each
channel.
The delay time starts after a change to the output channel status. If an output is
activated (rising edge) or deactivated (falling edge) the output monitoring does
not start until the delay time expires. Any fault conditions that arise after this
delay are reported as diagnostics.
The adjustable value range for the delay time is 0…255 ms. The default value is
80 ms.
Configure QuickConnect
QuickConnect (QC) enables the module to perform the start-up process faster,
especially the EtherNet/IP communication.
If you enable QC, the module accepts a TCP connection and the control system
establishes a connection within 350 ms after being switched on. The module can
achieve a total start-up time of 400…500 ms.
To use QC, the network must be in a star or linear topology, and the module
must have a static IP address. Ring topologies and DHCP/BOOTP are not
supported. No automatic check is performed for IP addresses that are assigned
more than once in the same network.
If QC is enabled, the following parameters for the Ethernet interface of the
module are fixed:
• 100 Mbit/s transmission speed
• Full duplex connection
• Auto-negotiation and auto-MDIX disabled.
Table 3 - Output Fault Delay Values
Bit
MSB
LSB
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word 0
Output Fault Delay port P0, channel C0 (pin 4), value range 0…255, default value 80
Word 1
Output Fault Delay port P0, channel C1 (pin 2), value range 0…255, default value 80
…
…
Word 14
Output Fault Delay port P7, channel C14 (pin 4), value range 0…255, default value 80
Word 15
Output Fault Delay port P7, channel C15 (pin 2), value range 0…255, default value 80