Configure and Startup
Chapter 2
Connection Page
Use the Connection page to configure the type of connection and behavior for
the module.
Figure 4 - Example of Connection Page
Requested Packet Interval
The Requested Packet Interval (RPI) is a configurable parameter that defines a
specific rate at which data is exchanged between the owner-controller and the
module.
Table 11 - Connection Parameters
Parameter
Definition
Name
Displays the type of connection
Requested Packet Interval (RPI) (ms)
Set the RPI rate.
Connection over EtherNet/IP
Set the type of connection to use on the EtherNet/IP network
Inhibit Module
Select to inhibit the module.
When the module is inhibited, the outputs follow the settings that are
configured in the Fault/Program Action page. See
for more information.
Major Fault On Controller If Connection
Fails While in Run Mode
Select to trigger a major fault on the controller if connection fails while the
controller is in Run mode. If the checkbox is not selected, only a minor fault
is triggered.
Module Fault
Displays details about a module fault to help in troubleshooting.