Rockwell Automation Publication ICSTT-RM446N-EN-P - April 2018
87
AADvance Functional Safety System Implementation
Chapter 4
Processor Module Locking Screw safety Function
The module
locking screw
acts as a module retaining device and also as a
switch that controls the module's operation. For the module to be fully
operational the locking screw must be turned to the locked position. If the
screw is turned to the unlocked position when a module is operational it will
initiate a fault indication and the module will become non-operational.
Processor modules can be replaced or installed on-line without affecting the
controller operation provided at least one is fitted and is fully operational.
However, each module must be installed one at a time and allowed to educate
before the next module is installed.
Processor Module Access Port
The front panel of the T9110 Processor Module has a concealed PS/2 style
connector on the front panel behind a plastic cover. This connector is for
Rockwell Automation use only and is used for factory settings during
manufacturing. However, the plastic cover can be removed to replace the
processor battery.
I/O Module Safety Functions
This section describes the I/O safety parameters.
I/O Module Safety Related Parameters
The AADvance Workbench provides you with the capability to adjust these
safety related parameters for an I/O module:
• Process safety time
• Shutdown action of a digital output module channel
• Fail-safe guard for the Analogue Output Module
• Shutdown action for the Analogue Output module
I/O Module Start-Up and Locking Screw Safety Function
I/O modules can be replaced or installed on-line without affecting the
controller operation provided at least one is fitted in a dual/triple Termination
Assembly and is fully operational. However, each module must be installed one
at a time and allowed to educate before the next module is installed.
The module
locking screw
acts as a retaining device and also as a switch that
controls the module's operational status. For the module to be fully operational
the locking screw must be in the locked position.
Содержание AADvance T9110
Страница 4: ...4 Rockwell Automation Publication ICSTT RM446N EN P April 2018 ...
Страница 10: ...10 Rockwell Automation Publication ICSTT RM446N EN P April 2018 Preface ...
Страница 44: ...44 Rockwell Automation Publication ICSTT RM446N EN P April 2018 Chapter 2 Functional Safety Management ...
Страница 116: ...116 Rockwell Automation Publication ICSTT RM446N EN P April 2018 Chapter 5 Checklists ...