AADvance System Architectures
Chapter 3
TMR Input and Processor, Fault Tolerant Output
A SIL 3 TMR architecture offers the highest level of fault tolerance for an
AADvance controller and consists of triple input modules, triple processors
and dual output modules.
• The input and processor modules operate in a 2oo3D under no fault
conditions, degrade to 1oo2D on detection of the first fault in any
module, and degrade to 1oo1 on the detection of faults in any two
modules and will fail-safe when there are faults on all three modules.
In the event of a failure in any element of a channel, the channel processor will
still produce a valid output which could be voted on because of the coupling
between the channels. This is why the triple modular redundant
implementation provides a configuration that is inherently better than a typical
2oo3 voting system.
Digital Output Modules
A digital output module fault must be repaired within the MTTR which was
used in the PFD calculation.
Analogue Output Modules
An analogue output module fault must be repaired within the MTTR which
was used in the PFD calculation.