Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
71
Communication Connections
Chapter
5
4.
Under Ethernet, click Port Settings.
5.
Set Port State as Enabled or Disabled.
6.
To manually set connection speed and duplexity, uncheck the option box
Auto-Negotiate speed and duplexity. Then, set Speed (10 or 100 Mbps)
and Duplexity (Half or Full) values.
7.
Click Save Settings to Controller if you would like to save the settings to
your controller.
8.
On the device configuration tree, under Ethernet, click Port Diagnostics to
monitor Interface and Media counters. The counters are available and
updated when the controller is in Debug mode.
Validate IP Address
Modules must validate the incoming IP address configuration, whether it is
obtained through explicit configuration or through DHCP.
The following rules must be obeyed when configuring the IP address:
•
The IP address for the module cannot be set to zero, a multicast address, a
broadcast address, or an address on the Class A loopback network
(127.x.x.x).
•
The IP address should not start with zero, and the IP address network ID
should be not zero.
•
The Network mask cannot be set to 255.255.255.255.
•
The Gateway address must be on the same subnet as the IP address that is
being configured.
•
The Name Server address cannot be set to zero, a multicast address, a
broadcast address, or an address on the Class A loopback network
(127.x.x.x).
The valid range of static IPv4 IP address exclude:
•
Broadcast or zero IP (255.255.255.255 or 0.0.0.0)
•
IP address starting with 0 or 127 (0.xxx.xxx.xxx or 127.xxx.xxx.xxx)
•
IP address ending with 0 or 255 (xxx.xxx.xxx.0 or xxx.xxx.xxx.255)
•
IP addresses in range 169.254.xxx.xxx (169.254.0.0 to 169.254.255.255)
•
IP addresses in range 224.0.0.0 to 255.255.255.255
Содержание 2080-LC20-20AWB
Страница 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Страница 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Страница 16: ...6 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 1 Hardware Overview Notes...
Страница 40: ...30 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 2 About Your Controller Notes...
Страница 46: ...36 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 3 Install Your Controller Notes...
Страница 66: ...56 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 4 Wire Your Controller Notes...
Страница 106: ...96 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 8 Using the Micro800 Remote LCD Notes...
Страница 162: ...152 Rockwell Automation Publication 2080 UM005E EN E March 2018 Appendix B Troubleshooting Notes...
Страница 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Страница 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Страница 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...