142
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
Appendix B
Troubleshooting
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
0xF000
Recoverable The controller was unexpectedly reset due to a
noisy environment or an internal hardware
failure.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
Perform one of the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Check wiring to eliminate any noise, refer to
0xF001
Recoverable The controller program has been cleared. This
happened because:
•
a power-down occurred during program
download or data transfer from the memory
module
•
the cable was removed from the controller
during program download.
•
the RAM integrity test failed.
Perform one of the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Transfer the program using the memory module restore utility.
0xF002
Non-
recoverable
The controller hardware watchdog was activated.
The controller hardware watchdog timeout
happens if program scan is more than three
seconds.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
See
Corrective Actions for Non-recoverable Faults on page 149
.
0xF003
Recoverable One of the following occurred:
•
The memory module hardware faulted.
•
The memory module connection faulted.
•
The memory module was incompatible with
the Micro800 controller’s firmware revision.
Perform one of the following:
•
Remove the memory module and plug it in again.
•
Obtain a new memory module.
•
Corrective Actions for Recoverable Faults on page 149
•
Upgrade the Micro800 controller’s firmware revision to be
compatible with the memory module. For more information on
firmware revision compatibility, go to
http://www.rockwellautomation.com/support/firmware.html
0xF004
Recoverable A failure occurred during the memory module
data transfer.
Perform one of the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Attempt the data transfer again. If the error persists, replace the
memory module.
•
For Embedded RTC failure, restart the controller.
0xF005
Recoverable The user program failed an integrity check while
the Micro800 controller was in Run mode.
Perform one of the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Wire Your Controller on page 37
0xF006
Recoverable The user program is incompatible with the
Micro800 controller’s firmware revision.
Perform one of the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Contact your local Rockwell Automation technical support
representative.
Содержание 2080-LC20-20AWB
Страница 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Страница 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Страница 16: ...6 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 1 Hardware Overview Notes...
Страница 40: ...30 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 2 About Your Controller Notes...
Страница 46: ...36 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 3 Install Your Controller Notes...
Страница 66: ...56 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 4 Wire Your Controller Notes...
Страница 106: ...96 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 8 Using the Micro800 Remote LCD Notes...
Страница 162: ...152 Rockwell Automation Publication 2080 UM005E EN E March 2018 Appendix B Troubleshooting Notes...
Страница 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Страница 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Страница 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...