Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
143
Troubleshooting
Appendix
B
0xF010
Recoverable The user program contains a function/function
block that is not supported by the Micro800
controller.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Contact your local Rockwell Automation technical support
representative.
0xF014
Recoverable A memory module memory error occurred.
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Reprogram the memory module. If the error persists, replace the
memory module.
0xF015
Non-
recoverable
An unexpected software error occurred.
Perform one of the following:
•
See
Corrective Actions for Non-recoverable Faults on page 149
.
•
Refer to
Wiring Requirements and Recommendation on page 37
0xF016
Non-
recoverable
An unexpected hardware error occurred.
Perform one of the following:
•
See
Corrective Actions for Non-recoverable Faults on page 149
.
•
Refer to
Wiring Requirements and Recommendation on page 37
0xF017
Non-
recoverable
An unexpected software error occurred due to
unexpected hardware interrupt.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
Perform one of the following:
•
See
Corrective Actions for Non-recoverable Faults on page 149
.
•
Refer to
Wiring Requirements and Recommendation on page 37
0xF018
Non-
recoverable
An unexpected software error occurred due to SPI
communication failure.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
Perform one of the following:
•
See
Corrective Actions for Non-recoverable Faults on page 149
.
•
Refer to
Wiring Requirements and Recommendation on page 37
0xF019
Non-
recoverable
An unexpected software error occurred due to
memory or other controller resource issue.
Corrective Actions for Non-recoverable Faults on page 149
0xF01A
Recoverable The controller was unexpectedly reset during Run
Mode Change (RMC) due to a noisy environment
or an internal hardware failure.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
Corrective Actions for Recoverable Faults on page 149
0xF020
Recoverable The base hardware faulted or is incompatible
with the Micro800 controller’s firmware revision.
Corrective Actions for Recoverable Faults on page 149
0xF021
Recoverable The I/O configuration in the user program is
invalid or does not exist in the Micro800
controller.
Corrective Actions for Recoverable Faults on page 149
0xF022
Recoverable The user program in the memory module is
incompatible with the Micro800 controller’s
firmware revision.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Replace the memory module.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
Содержание 2080-LC20-20AWB
Страница 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Страница 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Страница 16: ...6 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 1 Hardware Overview Notes...
Страница 40: ...30 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 2 About Your Controller Notes...
Страница 46: ...36 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 3 Install Your Controller Notes...
Страница 66: ...56 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 4 Wire Your Controller Notes...
Страница 106: ...96 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 8 Using the Micro800 Remote LCD Notes...
Страница 162: ...152 Rockwell Automation Publication 2080 UM005E EN E March 2018 Appendix B Troubleshooting Notes...
Страница 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Страница 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Страница 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...