Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
147
Troubleshooting
Appendix
B
0xF0878
Recoverable An index used to access a bit is beyond the
boundaries of the data type it is used on.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 149
.
2. Correct the program to ensure that there is no index used to access
a bit beyond the boundaries of the data type.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF880
Recoverable A data conversion error occurred.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 149
.
2. Correct the program to ensure that there is no data conversion error.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF888
Recoverable The call stack of the controller cannot support the
sequence of calls to function blocks in the current
project. Too many blocks are within another
block.
Perform the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Change the project to reduce the quantity of blocks being called
within a block.
0xF898
Recoverable An error occurred in the user interrupt
configuration for the plug-in I/O module.
Perform the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Correct the user interrupt configuration for plug-in I/O module in the
user program to match that of the actual hardware configuration.
0xF8A0
Recoverable The TOW parameters are invalid.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 149
.
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF8A1
Recoverable The DOY parameters are invalid.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 149
.
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
Содержание 2080-LC20-20AWB
Страница 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Страница 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Страница 16: ...6 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 1 Hardware Overview Notes...
Страница 40: ...30 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 2 About Your Controller Notes...
Страница 46: ...36 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 3 Install Your Controller Notes...
Страница 66: ...56 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 4 Wire Your Controller Notes...
Страница 106: ...96 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 8 Using the Micro800 Remote LCD Notes...
Страница 162: ...152 Rockwell Automation Publication 2080 UM005E EN E March 2018 Appendix B Troubleshooting Notes...
Страница 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Страница 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Страница 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...