Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

59

Create an RSFieldbus Software Project        

Chapter

 

3

Design Templates

Templates save time and provide consistency to your projects. This section 
describes how to create a base template and how to import and export the 
template into projects.

Create a Device or Bridge Template

Do these steps to create a device or bridge template. This base template can be 
used for the same block type for other projects.

1.

From the RSFieldbus main menu, click New 

 and choose

Bridge Template.

The New Bridge Template dialog box appears.

2.

Choose the Manufacturer, Device Type, and Device Rev.

3.

Enter a device tag name.

TIP

You also can choose Device Template from the New pull-down 
menu. For our example, we will create a bridge template. 
Procedures are the same for creating a device template.

Содержание 1757-FFLD2

Страница 1: ...User Manual FOUNDATION Fieldbus System Catalog Numbers 9308 RSFB64ENE 9308 RSFB256ENE 9308 RSFB1024ENE 1757 FFLD2 1757 FFLD4 1757 FFLDC2 1757 FFLDC4...

Страница 2: ...its equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this m...

Страница 3: ...olbar 19 Process Cell Window 19 Process Cell Window Toolbar 19 Strategy Window 20 Function Blocks and Parameters 20 Strategy Toolbar 21 Drawing Toolbar 22 Alignment Toolbar 23 Copy Attributes Toolbar...

Страница 4: ...t Setup Tool 63 Chapter 4 RSFieldbus Communication Introduction 67 Initialize Communication 68 Assign Tags 71 Export Tags 72 Consolidate the OPC Database 72 Download the Configuration 74 Chapter 5 Cre...

Страница 5: ...Device Function Blocks Introduction 105 Parameter Attributes 105 RES Resource Block 106 Block Use 106 RESTART Parameter 106 Nonvolatile Parameters 107 Alert Notification 107 FEATURES FEATURE_SEL Param...

Страница 6: ...hapter 10 Advanced Diagnostics and Hidden Web Pages Introduction 135 Advanced Diagnostics 135 Configure H1 Capture 135 H1 Captures 137 HSE Captures 139 Hidden Pages 140 Date and Time Zone 140 Reset th...

Страница 7: ...57 DS 72 Discrete Alarm Structure 157 DS 73 Event Update Structure 157 DS 74 Alarm Summary Structure 158 DS 85 Test Structure 158 Appendix C Fieldbus Status Codes for RSLogix 5000 Projects Introductio...

Страница 8: ...8 Rockwell Automation Publication 1757 UM012A EN P July 2011 Table of Contents Notes...

Страница 9: ...ifications for the 1757 FFLD and 1757 FFLDC linking devices Foundation Fieldbus Linking Device Installation Instructions publication 1757 IN021 Provides details on how to install the 1757 FFLD linking...

Страница 10: ...10 Rockwell Automation Publication 1757 UM012A EN P July 2011 Preface Notes...

Страница 11: ...the ControlNet network to fieldbus devices on H1 segments Both linking devices can have either two or four H1 segments with each segment supporting the recommended maximum 8 10 devices and a maximum o...

Страница 12: ...ON Fieldbus Design Considerations Reference Manual publication RSFBUS RM001 Figure 1 shows the RSFieldbus workstation connected directly over the EtherNet IP network to the ControlLogix chassis Figure...

Страница 13: ...e 2 ControlNet Ethernet and 1757 FFLDC Linking Device Example Item Description Item Description 1 ControlLogix controller with 1756 ENBT and 1756 CNB modules 5 Power conditioner 2 Host computer and OP...

Страница 14: ...ules The list of RSFieldbus software features includes the following Configure a fieldbus network with devices Create and edit function block control strategies Integrate fieldbus data into ControlLog...

Страница 15: ...3 The table lists the software topics described in this section The menu bar contains actions specific to the selected window These windows open depending on which actions you have completed Main Wind...

Страница 16: ...pears below the Rockwell Software copyright The Main window contains a counter in the lower right corner that lets you see how many blocks you have in use TIP When choosing an RSFieldbus license keep...

Страница 17: ...in this window opens a corresponding menu Figure 4 Project Window To open the Project window you must open a new or existing project See page 31 for more information IMPORTANT Toolbars can be moved an...

Страница 18: ...To open a Fieldbus window you must add a fieldbus H1 and expand it See page 40 for more information Toolbar Icon Description Opens a new template You must close any open templates before you can open...

Страница 19: ...ess Cell Window The Process Cell window shows an individual process cell and all attached control modules and blocks Right clicking each item in this window opens a corresponding menu To open a Proces...

Страница 20: ...ameters The standard blocks for fieldbus devices include the following You can change or set the action of a block by changing the settings of its parameters A block parameter that is written to the b...

Страница 21: ...choose Tool Boxes on the Tools menu and select the toolbar you want to view or hide Toolbar Icon Description Selects items To select more than one item press Shift Used to modify block tags links link...

Страница 22: ...ounded on the top click and drag to the right To draw a chord that is rounded on the bottom click and drag to the left To expand the chord click Modify Used to draw sections of a ring To draw a sectio...

Страница 23: ...eft side of the objects to the left side of the anchor Vertically aligns the center of the objects to the center of the anchor Aligns the right side of the objects to the right side of the anchor Alig...

Страница 24: ...s in the order Select the two objects that you want to switch then click the icon Moves the selected object in front of another Select the object you want to move click the InFrontOf icon then select...

Страница 25: ...or log The Communication window shows all errors in the current project Do these steps 1 Click the Error Log icon to open the Communication window 2 To delete individual entries right click the date a...

Страница 26: ...26 Rockwell Automation Publication 1757 UM012A EN P July 2011 Chapter 2 RSFieldbus Software Basics Notes...

Страница 27: ...table lists the main topics described in this section IMPORTANT You must have RSFieldbus software installed on the computer that will be used as the host server In addition you need all the device des...

Страница 28: ...The 1757 FFLDC bridges data flow between H1 segments on the ControlNet network Figure 5 Fieldbus System Example You must have at least one power conditioner per power supply on the H1 line and two te...

Страница 29: ...menu 2 Click the New icon and choose Project The Setup New Project Workspace dialog box appears 3 Type a project name for the File name Our example shows PID The ffp extension for saved projects denot...

Страница 30: ...erwise proceed to Create a New Bridge linking device on page 31 1 In the Setup New Project Workspace dialog box double click the file name with the ffp extension In our example it would be PID ffp The...

Страница 31: ...shows and click OK Create the Physical Component Do these steps to add bridges and devices to your project Create a New Bridge linking device This section defines the linking device as the bridge fro...

Страница 32: ...device a tag name to differentiate between devices on the same H1 segment Tags cannot include a period If a separator is necessary we suggest using an _ underscore Spaces are allowed but not recommend...

Страница 33: ...Host 7 Click the Advanced Options tab Use the default of Creation based on Default Template Clear the box to make your own selections 8 Click OK The linking device is added to the HSE Host Create a N...

Страница 34: ...Upstream Port 1 3 Select the Upstream Port H1 port on the linking device to which the H1 segment is connected 4 Click OK The Fieldbus H1 is added to the Project Set the Macrocycle RSFieldbus software...

Страница 35: ...ed If more unscheduled time is needed increase the macrocycle The unused scheduled time will be used for the unscheduled activities 1 In the Project window double click H1 1 or whatever you named the...

Страница 36: ...12A EN P July 2011 Chapter 3 Create an RSFieldbus Software Project Create a New Device Do these steps to add devices to the H1 network 1 In the Fieldbus H1 window right click the H1 icon and choose Ne...

Страница 37: ...alues default to the latest revisions in the device support files if the Follow the Latest DD and CF Revisions box is checked If the DD and CF revisions do not match your device firmware clear the box...

Страница 38: ...vice class to a Backup LAS ATTENTION During this procedure control of the associated devices and anything linked to them will be lost IMPORTANT We recommend that you open the Live List to verify the c...

Страница 39: ...hange to a Backup LAS and click the right arrow 3 Repeat for any other devices that you want to change to a Backup LAS 4 Click Apply Change Device Class to Basic Do these steps to change the device cl...

Страница 40: ...ps 1 To edit a tag double click the corresponding icon in the H1 window An Attributes dialog box appears 2 Make the necessary changes and then click OK 3 To delete a tag right click the corresponding...

Страница 41: ...k tag right click the block icon and choose Attributes Attach Block to a Device Function blocks that have been added to the logical component can be attached to a device in the physical component 1 In...

Страница 42: ...block and choose Detach Block 2 Click Yes at the warning message The function block is removed from the device Tag Search Do these steps to search and locate a tag in your configuration 1 From the Sea...

Страница 43: ...the tag appears in the Fieldbus Networks Location section 3 Click OK The tag is highlighted in your configuration Create the Logical Component This section describes how to create a logical component...

Страница 44: ...Publication 1757 UM012A EN P July 2011 Chapter 3 Create an RSFieldbus Software Project The Process Cell dialog box appears 2 Type a tag name Our example is Process Cell 1 3 Click OK The Process Cell i...

Страница 45: ...ps to add a control module to your project 1 Right click the Process Cell icon and choose Expand The Process Cell window appears 2 Right click the Process Cell icon and choose New Control Module The C...

Страница 46: ...1 In the Process Cell window right click the control module icon and choose Attributes The Control Module dialog box appears 2 Enter a stale count value and click OK The Control Module is added to yo...

Страница 47: ...in the Process Cell window An attached function block in the Process Cell will have a question mark until the block is attached to a device Do these steps to attach a function block to a control modul...

Страница 48: ...icon and choose Strategy The Strategy window appears The Strategy window is similar to graph paper to help you align the blocks that are connected There are three ways to add blocks to the Strategy wi...

Страница 49: ...blocks you want to link for the strategy 3 Once all the blocks are in the Strategy window drag and drop blocks within the window to organize your strategy Create New Blocks in a Strategy Window This...

Страница 50: ...e new block appears in the Strategy window 4 To remove an incorrect block right click the block and choose Delete Import a Template See page 61 for procedures IMPORTANT The Device Rev DD Rev and CF Re...

Страница 51: ...he Output Parameter Selection dialog box appears You can mouse over the pins to read their descriptions at the bottom of the dialog box 3 Select a parameter such as the OUT pin as shown in the example...

Страница 52: ...link is drawn from the first block to the second block Fast Link Do these steps to create links without opening the Parameter Selection window 1 Click the Link icon 2 Right click the first block and...

Страница 53: ...ndow 2 Right click the link and choose Delete A pop up dialog box appears with a message Table 2 Link Attributes Menu Item Sub menu item Action Delete N A Removes the link Labels Show Link Label Displ...

Страница 54: ...You can restore it if necessary To halt the deletion click Cancel 4 To restore links that have been deleted right click the block to which the link was attached and choose Show Hidden Links Edit Line...

Страница 55: ...ter whose value is configured calculated or set by an operator or higher level device Displays dynamic parameters Dynamic parameters values are calculated by the block algorithm and therefore do not n...

Страница 56: ...ns how to configure function block parameters offline Do these steps 1 In the Fieldbus H1 window right click the desired block and choose Off Line Characterization The Off Line Characterization dialog...

Страница 57: ...on dialog box appears 2 Click to view all parameters 3 Select a desired parameter and click Edit at the bottom of the dialog box 4 Enter a value and click End Edit 5 Repeat step 3 and step 4 for all d...

Страница 58: ...g to move available parameters to selected parameters and vice versa Select an Available parameter and click the right arrow to move the parameter to the Selected parameter box Select a Selected param...

Страница 59: ...e or Bridge Template Do these steps to create a device or bridge template This base template can be used for the same block type for other projects 1 From the RSFieldbus main menu click New and choose...

Страница 60: ...ve as Default Template This template will be used as the base of each device or bridge of that type that you add to your projects Edit the Default Template Do these steps to modify the default base te...

Страница 61: ...Do these steps to use a template to create a bridge or device for a project 1 Right click the HSE Network icon and choose New Bridge from Template The Open dialog box appears 2 Browse to the location...

Страница 62: ...te and Import a Strategy Template Do these steps to create a template that you can use to import and export a strategy into projects 1 From the RSFieldbus main menu click New and choose Strategy Templ...

Страница 63: ...ow to use the HSE Network Setup Tool to activate multiple network cards or an inactive1757 FFLD linking device Add Device to the FFLDC ControlNet Setup Tool Do these steps to define the CIP path of th...

Страница 64: ...installation folder If RSFieldbus software was not installed to the default folder you must browse to the folder where it was installed 3 Double click the IDShell HSE ini file The FFLDC ControlNet Set...

Страница 65: ...oject Chapter 3 The FFLDC path is added to the lower window 6 Complete step 4 and step 5 with all other 1757 FFLDC linking devices you plan to use in RSFieldbus projects 7 Click the Save to INI file i...

Страница 66: ...66 Rockwell Automation Publication 1757 UM012A EN P July 2011 Chapter 3 Create an RSFieldbus Software Project Notes...

Страница 67: ...FFLD shown in Figure 6 provides connectivity for fieldbus devices to Logix controllers via H1 networks Figure 6 Linking Device Connectivity Example The table lists the main topics described in this s...

Страница 68: ...make all windows visible at the same time 2 Click the RSFieldbus online icon The Initialize Communication animation begins During this time all devices are located on the network A red x appears next...

Страница 69: ...ing device and choose Attributes The Bridge dialog box appears 4 From the Device Id pull down menu choose the corresponding device ID 5 Click OK Note that the red x in the HSE window has disappeared o...

Страница 70: ...tate in the live list Associate Devices If this is the first time you have initialized communication you must assign the Device Ids 1 In the Project window right click the device and choose Attributes...

Страница 71: ...n the H1 window for all devices in the project 7 You also can assign tags to all the devices at one time rather than individually by right clicking HSE Network and choosing Assign All Tags ATTENTION D...

Страница 72: ...indow right click a project icon and choose Export Tags The Export Tag message window appears 2 Click OK Consolidate the OPC Database If your system has a centralized OPC server and you are using mult...

Страница 73: ...message dialog box appears to confirm that you are adding this project 2 Click Yes When Yes the following configuration occurs Project name is added to the list of configurations and the HseTagInfo_CO...

Страница 74: ...eps to clear the list of consolidated projects and remove all the tag lists from the OPC server 1 Open the Consolidated OPC Database dialog box Projects are listed in the Configurations section of the...

Страница 75: ...art The Download dialog box shows the progress while the configuration downloads After a download it may take up to two minutes for OPC data to be available from the OPC server IMPORTANT The Propagate...

Страница 76: ...76 Rockwell Automation Publication 1757 UM012A EN P July 2011 Chapter 4 RSFieldbus Communication Notes...

Страница 77: ...an communicate with ControlLogix controllers In this illustration the 1757 FFLD linking device does the following Serves as a bridge between the EtherNet IP and H1 networks Provides connectivity for F...

Страница 78: ...alog box 3 Click OK Field Description Field Description Vendor Defaults to Allen Bradley Description Type an optional description for the controller Type Choose the type of controller from the pull do...

Страница 79: ...ler Organizer Conventions for Names Throughout a Logix5000 project you define names for the different elements of the project such as the controller data addresses tags routines I O modules and so for...

Страница 80: ...n Module The communication bridge module establishes the EtherNet IP address to allow the linking device to communicate with the ControlLogix controller If configuring a 1757 FFLDC linking device you...

Страница 81: ...odule Typically although not always a later that is higher Major Revision supports at least all of the data formats supported by an earlier that is lower Major Revision of the same catalog number and...

Страница 82: ...r Revision numbers Choose the appropriate revisions from the pull down menus if necessary Electronic Keying Use the default of Compatible Module or choose Exact Match or Disable Keying from the pull d...

Страница 83: ...steps to add a linking device to communicate to field devices 1 In the Controller Organizer right click Ethernet and choose New Module The Select Module window dialog box appears 2 Click the sign in f...

Страница 84: ...ption Type a description optional for the module Comm Format Use the default or choose a communication format from the pull down menu Revision Defaults both the Major Revision first field and Minor Re...

Страница 85: ...nd a fieldbus environment The Logic Block takes signals generated in either environment and sends them to the other You can use the Logix Block to send or receive 8 analog or 8 discrete signals per Lo...

Страница 86: ...ect Module dialog box appears 2 Click the sign in front of Analog on the Select Module dialog box 3 Select the Logix Block module and then click OK The New Module dialog box appears to let you name th...

Страница 87: ...ng information to configure the linking device and Logix Block module properties Configure Linking Device Properties 1 In the Controller Organizer right click the linking device and choose Properties...

Страница 88: ...the controller if the connection fails in Run mode See page 92 for more information 3 On the Module Properties dialog box click the Fieldbus tab 4 Click the icon to launch RSFieldbus software You can...

Страница 89: ...tab you can view the module s identification information and module s status You must be online for module details to appear 6 On the Module Properties dialog box click the Port Configuration tab In...

Страница 90: ...ostics tab In this tab you can view refresh and reset the module s interface counters and media counters You must be online for these details to appear Maintain Logix Block Data Do these steps to rena...

Страница 91: ...00 Software Project Chapter 5 The Module Properties dialog box appears In the General tab you can rename the Logix Block module change the slot number add a description and choose the type of electron...

Страница 92: ...ction failure with the module while in Run mode For important information on this checkbox see Configure a Major Fault to Occur in the Logix5000 Controllers Information and Status Programming Manual p...

Страница 93: ...d initially to set the network parameters NUT SMAX and UMAX but not with the addition of each unscheduled Logix Block Clear Use Scheduled Connection over ControlNet to select an unscheduled connection...

Страница 94: ...ue to each product revision When a Logix5000 controller begins communicating with a module this set of keying attributes is considered You can find revision information on the General tab of a module...

Страница 95: ...ecisely I O communication is not permitted with the module or with modules connected through it as in the case of a communication module Use Exact Match keying when you need the system to verify that...

Страница 96: ...r and the same or later that is higher Major Revision In some cases the selection makes it possible to use a replacement that is a different catalog number than the original For example you can replac...

Страница 97: ...ng this you can avoid the case of a physical module rejecting the keying request because it is an earlier revision than the one configured in the software EXAMPLE In the following scenario Compatible...

Страница 98: ...le keying allows I O communication The module configuration is for a 1756 IB16D module with module revision 2 1 The physical module is a 1756 IB16D module with module revision 3 2 In this case communi...

Страница 99: ...e In this case communication is allowed because the two digital modules share common data formats Module Configuration Vendor Allen Bradley Product Type Digital Input Module Catalog Number 1756 IA16 M...

Страница 100: ...100 Rockwell Automation Publication 1757 UM012A EN P July 2011 Chapter 5 Create an RSLogix 5000 Software Project Notes...

Страница 101: ...em must be owned by a ControlLogix controller to be useful The Logix Block module s position is located remotely relative to the owner controller s position The owner controller initiates communicatio...

Страница 102: ...the network parameters NUT SMAX and UMAX You do not have to run the software for each additional unscheduled Logix Block See the ControlNet Modules in Logix5000 Control Systems User Manual publicatio...

Страница 103: ...control system that the Logix Block module resides Because a Logix Block module resides in the linking device which acts like a remote chassis the role of a requested packet interval RPI varies slight...

Страница 104: ...e system can listen to the data from a Logix Block module even if the controller does not own the module In other words the controller does not have to own a module s configuration data to listen to i...

Страница 105: ...he attributes used to define each function block parameter If an attribute does not appear for a specific parameter it is not applicable to that parameter Topic Page RES Resource Block 106 LGX Logix B...

Страница 106: ...nitializing or receiving a software download The MANUFAC_ID DEV_TYPE DEV_REV DD_REV and DD_RESOURCE parameters are required to identify and locate the DD so that Device Description Services can select...

Страница 107: ...n FEATURE_SEL that is not set in FEATURES the result will be a block alarm for a configuration error The linking device supports the following features Reports Fault State Soft Write Lock and change o...

Страница 108: ...will be incremented each time a static parameter value in the block is changed 2 TAG_DESC OctString 32 4 bytes Spaces N A AUTO The user description of the intended application of the block 3 STRATEGY...

Страница 109: ...n methods available for this resource block This parameter is reserved for future use See CYCLE_TYPE Bits on page 110 20 CYCLE_SEL Bitstring 2 See CYCLE_SEL Bits on page 111 0 N A A Used to select the...

Страница 110: ...cause of the alert is entered in the subcode field The first alert to become active will set the Active status in the Status attribute As soon as the Unreported status is cleared by the alert reportin...

Страница 111: ...RITE_LOCK parameter 4 7 Reserved 8 Change of bypass in an automatic mode 1 If this feature is selected in FEATURE_SEL it is allowed to write in BYPASS in an automatic mode otherwise only in Man or OOS...

Страница 112: ...Block Schematic 43754 IN_0 IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_D0 IN_D1 IN_D2 IN_D3 IN_D4 IN_D5 IN_D6 IN_D7 OUT_0 OUT_1 OUT_2 OUT_3 OUT_4 OUT_5 OUT_6 OUT_7 OUT_D0 OUT_D1 OUT_D2 OUT_D3 OUT_D4 OUT_D5...

Страница 113: ...rs configured in the Logix Block in the linking device The Logix Block in the controller will fail to make a connection if there is no Logix Block in the linking device configured with a corresponding...

Страница 114: ...x VCRs subscribers Total VCRs x subscribers Output device 1 output PV 1 VCR publisher 1 VCR subscriber from BKCAL 2 inputs PV from Limit Switch 2 VCRs subscribers Total VCRs 1 publisher 3 subscribers...

Страница 115: ...following conditions The Logix Block is inhibited EtherNet IP communication is disrupted Inx Quality is Bad Inx Quality is Uncertain The converse is not true Inx Quality will not go Bad if InxFault i...

Страница 116: ...k Parameter in Chater 2 of the FOUNDATION Fieldbus Design Considerations Reference Manual publication RSFBUS RM001 6 BLOCK_ERR Bitstring 2 E RO Reflects the error status associated with the hardware o...

Страница 117: ...t port If the linking device s Ethernet port is going to be connected to a networked environment and a custom IP address is required contact Rockwell Automation Technical Support for instructions on h...

Страница 118: ...with JavaScript enabled Temporary internet files settings under Tools Internet Options General Every visit to the page Browser security setting under Tools Internet Options Low 1 1 The first time you...

Страница 119: ...011 119 Device Web Pages Chapter 8 Access the Web Pages Follow these steps to access the Home page of the linking device 1 In your Web browser type the IP address of the linking device The IP address...

Страница 120: ...llow these steps to open and close folders 1 Click Expand in the upper left hand corner of the 1757 FFLD Diagnostic Display dialog box to open all folders 1 3 4 2 TIP Examples in this section show the...

Страница 121: ...ssword The default user name and password are listed below Default user name default Default password password Change the User Name and Password In order to secure these web pages change the default u...

Страница 122: ...ears 2 Click Continue if the Web service can be safely restarted The Username Password page appears 3 Enter the following information a Old UserName default b New UserName c Old Password password d Ne...

Страница 123: ...ou forget your user name or password you can reset the default values by resetting the linking device to its factory defaults See page 141 for details on performing a reset Logout IMPORTANT Once confi...

Страница 124: ...124 Rockwell Automation Publication 1757 UM012A EN P July 2011 Chapter 8 Device Web Pages Notes...

Страница 125: ...appears as a device on each network list A device remains in this Live List as long as it responds properly to the token sent from the Link Active Scheduler LAS The LAS will remove a device from the L...

Страница 126: ...connected Device Tag The name you have given to the device ID The fieldbus device ID Address The device s fieldbus address Function The fieldbus function to which the device is set Bridge The 1757 FFL...

Страница 127: ...um number and also indicates how many of each are currently in use on the H1 channels For examples of how the number of used VCRs is calculated see page 114 Rockwell Automation Technical Support can u...

Страница 128: ...ION Fieldbus Specification document FF 007 The HSE VCR Entry tab has a pull down menu that displays the HSE VCRs that are in use The Static and Dynamic Entry tabs have a pull down menu that lets you s...

Страница 129: ...g Ethernet address details Ethernet network configuration Table 10 Ethernet Network Settings Page Field Description Network Interface Ethernet Address MAC Ethernet MAC address of the module IP Address...

Страница 130: ...hernet network This summary includes the following Ethernet network configuration Packets sent and received over the Ethernet network Frames sent and received over the Ethernet network You can set the...

Страница 131: ...ounters Alignment Errors Frames received that are not an integral number of octets in length FCS Errors Frames received that do not pass the FCS check Single Collisions Successfully transmitted frames...

Страница 132: ...ostic Log Files The Diagnostic Log Files consist of the Web Server Log and the Linking Device Log Web Server Log The Web Server Log provides a report of recent requests to the web pages It lists when...

Страница 133: ...may be useful to Technical Support to diagnose anomalies in your linking device It lists when the activity occurred and a description of the activity To download the Linking Device Log right click the...

Страница 134: ...134 Rockwell Automation Publication 1757 UM012A EN P July 2011 Chapter 9 Diagnostic Web Pages Notes...

Страница 135: ...omputers data servers and linking devices The Configure H1 Captures page is used to save H1 information from the linking device to a file Rockwell Automation Technical Support uses this information to...

Страница 136: ...en Web Pages Follow these steps to access the Capture page 1 On the 1757 FFLD Diagnostics Display page click Advanced Diagnostics in the left side pane A sub menu appears 2 Click Configure H1 Capture...

Страница 137: ...capture saves the data of all four ports Follow these steps to capture information about fieldbus communication on a linking device H1 port 1 On the Capture page verify that H1 is selected default as...

Страница 138: ...a specific amount of time type a Capture Time and Size If the file size is reached before the time elapses the capture will stop b To capture a specific sized file type the Capture Size and type a Ca...

Страница 139: ...ockwellautomation com knowledgebase for more information HSE captures are in 5 KB blocks and the file size increases by 5 KB Only one computer connection to the linking device at a time is allowed for...

Страница 140: ...eps to log date and time on web pages 1 To access the Date and Time Zone page type the following address where the IP address is the IP address of your linking device The Date Time page appears 2 Type...

Страница 141: ...page password information through this reset Reset jumper locally See page 149 Web page reset remotely Following procedures RSLogix 5000 reset remotely See page 152 Reset to factory defaults This rese...

Страница 142: ...linking device 1 To access the Reset page type the following address where the IP address is the IP address of your linking device The Linking Device Reset Page appears 2 On the Linking Device Reset P...

Страница 143: ...ou click Continue The linking device restarts and the browser closes Reset Configuration Follow these steps to reset fieldbus configurations and restart the linking device 1 On the Linking Device Rese...

Страница 144: ...et configuration to defaults clear log files and restart the linking device 1 On the Linking Device Reset Page click Reset to Factory Defaults 2 Click Submit A warning message appears 3 Click Continue...

Страница 145: ...vice is connected to the H1 network Flashing green The linking device H1 channel is active STATUS module Off No power Module does not have 24V DC power Flashing green Standby Module is not configured...

Страница 146: ...inking device contact Rockwell Automation Technical Support Table 12 1757 FFLD Status Indicators Indicator Status Description Table 13 1757 FFLDC Status Indicators Indicator Status Description H1 Off...

Страница 147: ...e is connected to the ControlNet network Solid red Duplicate ControlNet node address Flashing red and green Self test MODE Solid green Linking device is operational Flashing green Linking device is ou...

Страница 148: ...dant media if required Solid green Normal operation None Flashing green off Temporary network errors Check media for broken cables loose connectors or missing terminators If condition persists refer t...

Страница 149: ...nfiguration The Reset Configuration removes power from the linking device s battery deleting all downloaded fieldbus configurations The linking device retains its network configuration and Web page pa...

Страница 150: ...tion to use BOOTP erases Web page password information and clears all downloaded fieldbus configurations Follow these steps to complete a factory default reset 1 Verify that the linking device is powe...

Страница 151: ...ntrol of the current linking device process Monitoring processes through the linking device Communication to devices attached to the linking device Value Reset Type Description 1 Run Run appears while...

Страница 152: ...d deletes all downloaded fieldb us configuration The linking device retains its network configuration and web page password information through this reset Do these steps to perform a reset by using RS...

Страница 153: ...box click OK The reset starts and may take a few minutes to complete 5 At the Module Not Found warning click OK This warning appears from RSLogix 5000 software not providing enough time for the reset...

Страница 154: ...154 Rockwell Automation Publication 1757 UM012A EN P July 2011 Appendix A Troubleshoot the Linking Device Notes...

Страница 155: ...16 2 bytes Unsigned32 4 bytes FloatingPoint 4 bytes VisibleString 1 byte per character includes the 7 bit ASCII character set OctetString Octet strings are binary BitString 1 byte Time Value 8 bytes c...

Страница 156: ...data structure consists of the value and status of discrete value parameters DS 69 Mode Structure This data structure consists of bit strings for target actual permitted and normal modes Table 16 Valu...

Страница 157: ...data that describes a static revision alarm Table 19 Access Permissions DS 70 E Element Name Data Type Size bytes 1 Grant Bit String 1 2 Deny Bit String 1 Table 20 Discrete Alarm Structure DS 72 E El...

Страница 158: ...Name Data Type Size bytes 1 Current Bit String 2 2 Unacknowledged Bit String 2 3 Unreported Bit String 2 4 Disabled Bit String 2 Table 23 Test Structure DS 85 E Element Name Data Type Size bytes 1 Val...

Страница 159: ...I In 0 xxxxxx Quality Sub status Limits Quality Substatus WindupL WindupH Init Primary Initializing Initiate Fault State Bad Non Specific Not Limited 0 0 0 0 0 0 0 Low Limited 0 0 1 0 0 0 0 High Limi...

Страница 160: ...nstant 0 6 1 1 0 0 0 Out of Service Not Limited 0 7 0 0 0 0 0 Low Limited 0 7 1 0 0 0 0 High Limited 0 7 0 1 0 0 0 Constant 0 7 1 1 0 0 0 Uncertain Non Specific Not Limited 1 0 0 0 0 0 0 Low Limited 1...

Страница 161: ...0 0 0 Low Limited 1 5 1 0 0 0 0 High Limited 1 5 0 1 0 0 0 Constant 1 5 1 1 0 0 0 Sub normal Not Limited 1 6 0 0 0 0 0 Low Limited 1 6 1 0 0 0 0 High Limited 1 6 0 1 0 0 0 Constant 1 6 1 1 0 0 0 Good...

Страница 162: ...0 0 Unacknowledged Block Alarm Not Limited 2 4 0 0 0 0 0 Low Limited 2 4 1 0 0 0 0 High Limited 2 4 0 1 0 0 0 Constant 2 4 1 1 0 0 0 Unacknowledged Advisory Alarm Not Limited 2 5 0 0 0 0 0 Low Limite...

Страница 163: ...1 1 1 0 0 Not Selected Not Limited 3 4 0 0 1 0 0 Low Limited 3 4 1 0 1 0 0 High Limited 3 4 0 1 1 0 0 Constant 3 4 1 1 1 0 0 Local Override Not Limited 3 6 0 0 1 0 0 Low Limited 3 6 1 0 1 0 0 High Lim...

Страница 164: ...Limited 0 0 0 0 0 0 Low Limited 1 0 0 0 0 0 High Limited 0 1 0 0 0 0 Constant 1 1 0 0 0 0 Initialization Acknowledge Not Limited 0 0 0 1 0 0 Low Limited 1 0 0 1 0 0 High Limited 0 1 0 1 0 0 Constant...

Страница 165: ...ng The number of linking devices that are allowed on a either network depends on the following The bandwidth of the network number of nodes The number of connections that the communication bridge or i...

Страница 166: ...e this module supports 64 connections In Example 2 if a 1756 CNB ControlNet bridge module is being used the network could be considered fully loaded and even too close to the connection limit We recom...

Страница 167: ...ch device type and it consists of the files whose extensions are ffo and sym There is also a capabilities file for each device type and it consists of the files whose extensions are cff which are loca...

Страница 168: ...ldbus software from the ProjectFile menu choose Import Device Support The Browse for Folder dialog box appears 2 Browse to the manufacturer folder containing the extracted DD and capabilities files an...

Страница 169: ...s The HSE Network Setup Tool is found under Start Programs Rockwell Software RSFieldbus HSE Network Setup The HSE Network Setup Tool dialog box appears Activate the Network Card If your computer has o...

Страница 170: ...g device is seen on the RSFieldbus Live List and can be used in RSFieldbus software projects By default linking devices with the same subnet mask as the active network card are active Linking devices...

Страница 171: ...red Network Scheduled Unidirectional One of three classes of VCRs see VCR BOOTP A protocol to boot a diskless workstation and receive the boot information from a server branch line A segment of an H1...

Страница 172: ...facturer assigns Device IDs must be unique to the device no two devices can have the same device ID device tag A character string name that uniquely identifies a device on a fieldbus network DHCP Abbr...

Страница 173: ...25 Kbps H1 field device A fieldbus device connected directly to an H1 FOUNDATION fieldbus such as valves and transmitters host Control system that has FOUNDATION fieldbus capabilities to configure an...

Страница 174: ...rds for data communication over local and metropolitan area networks input parameter A block parameter that receives data from another block input output subsystem interface A device used to connect o...

Страница 175: ...inks directly to a virtual communication relationship VCR logical component Function blocks and algorithms that control a project logix block Facilitates signals between a ControlLogix environment and...

Страница 176: ...data is modeled as contained so there are no links in this block RSFieldbus A graphical software for creating links loops and schedules for a process control network RSLogix Software that provides a p...

Страница 177: ...blocks from the local input output I O function required to read sensors and command output hardware Transducer blocks contain information such as calibration date and sensor type There is usually on...

Страница 178: ...178 Rockwell Automation Publication 1757 UM012A EN P July 2011 Glossary Notes...

Страница 179: ...ies file 167 capture H1 data 137 change user name and password 121 communication RSFieldbus software 67 window 25 configure controller 78 download 74 H1 capture page 135 I O module 80 connections dire...

Страница 180: ...e site 118 J jumper reset 150 K keying attributes 94 electronic 94 L LAS 38 licenses 16 linking device bridge 31 factory defaults 144 log 133 reset page 141 Status indicators 145 web pages 117 listen...

Страница 181: ...gix Blocks 85 fieldbus status codes 159 RSNetWorx software using with RSLogix 5000 102 S security recommendations 118 server define host 30 set user name and password 121 status codes for RSLogix 5000...

Страница 182: ...182 Rockwell Automation Publication 1757 UM012A EN P July 2011 Index Notes...

Страница 183: ......

Страница 184: ...f you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product u...

Отзывы: