Application logic is used to compare input values for concurrence.
Figure 13 - Logic Comparing Input Values or States
The user program must also contain rungs to annunciate a fault in the event of a
sustained miscompare between two points.
Figure 14 - Rungs Annunciating a Fault
The control, diagnostics and alarming functions must be performed in sequence.
For more information on faults, see
Using 1756 Digital Output
Modules
ControlLogix digital output modules are divided into two categories:
•
Diagnostic output modules
•
Standard output modules
These modules share many of the same inherent architectural characteristics.
However, the diagnostic output modules incorporate features that allow
diagnosing of field-side failures, including:
•
No-Load (loss of load) reporting.
•
Blown Fuse reporting.
•
Output verify.
•
Output pulse test.
To achieve SIL 2, the output module must be wired back to an input module for
monitoring. An exception is to use a diagnostic digital input module.
Input B
Input A
Actuator
No Faults
Input B
Input A
Input B
Input A
Timer
Timer preset in milliseconds to
compensate for filter time and
hardware delay differences.
Fault
Timer Done
Alarm to Operator
Fault
Содержание 1756-L6 Series
Страница 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Страница 60: ...60 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 5 ControlLogix I O Modules Notes ...
Страница 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Страница 120: ...120 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix C PFD Calculations for a SIL 2 System Notes ...
Страница 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Страница 133: ...Allen Bradley Motors ...