32
Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
Chapter 3
ControlLogix Controllers, Chassis, and Power Supplies
A three-position keyswitch on the front of the controller governs ControlLogix
system operational modes. The following modes are available:
•
Run
•
Program
•
Remote - This software-enabled mode can be Program or Run.
Figure 10 - Keyswitch in Run Mode
When a SIL 2-certified ControlLogix application is operating in the Run mode,
the controller keyswitch must be in the RUN position and the key removed.
Outputs are only enabled in this mode.
Requirements for Use
Consider these requirements when using a SIL 2-certified ControlLogix
controller:
•
All components, such as input and output modules, for each safety
function must be owned by the specific controller performing the safety
function.
•
When installing ControlLogix controller, refer to the user manual listed in
Additional Resources on page 10
.
•
There are currently separate firmware revisions for standard and redundant
operation. For more information on the revisions, see
.
For more information on the ControlLogix controllers, see the publications
listed in the
Additional Resources on page 10
OK
FORCE SD
RUN
Logix557x
RU
N REM PROG
1756-L7
x
1756-L6
x
Содержание 1756-L6 Series
Страница 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Страница 60: ...60 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 5 ControlLogix I O Modules Notes ...
Страница 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Страница 120: ...120 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix C PFD Calculations for a SIL 2 System Notes ...
Страница 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Страница 133: ...Allen Bradley Motors ...