Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
123
Checklists
Appendix D
No.
Additional Analog Input Module-Only Requirements
Yes
No
Comment
1
Is the Communication Format set to Float Data?
2
Have you calibrated the modules as often as required by your application?
3
Are you using ladder logic to compare the analog input data on two channels to make sure there is concurrence within
an acceptable range and that redundant data is used properly?
4
Have you written application logic to examine bits for any condition that may cause a fault and appropriate fault
routines to handle the fault condition?
5
When two FLEX I/O analog input modules are wired in the same application, are both module on different ControlNet
nodes?
6
When wiring an analog input module in Voltage mode, are transmitter grounds tied together?
7
When wiring an analog input module in Current mode, are loop devices placed properly?
8
When wiring thermocouple modules in parallel, have you wired to the same channel on each module as shown in
Figure 24 on page 52
?
9
When wiring two RTD modules, are two sensors used, as shown in
Figure 25 on page 52
?
Input Module Check List for ControlLogix System
Содержание 1756-L6 Series
Страница 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Страница 60: ...60 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 5 ControlLogix I O Modules Notes ...
Страница 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Страница 120: ...120 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix C PFD Calculations for a SIL 2 System Notes ...
Страница 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Страница 133: ...Allen Bradley Motors ...