Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
33
ControlLogix Controllers, Chassis, and Power Supplies
Chapter 3
ControlLogix Chassis
The ControlLogix 1756-A
xx
chassis provide the physical connections between
controllers and I/O modules. The chassis itself is passive and is not relevant to the
safety discussion because any physical failure would be unlikely under normal
environmental conditions and would be manifested and detected as a failure
within one or more of the active components.
When installing ControlLogix chassis, follow the instructions provided in the
product documentation.
ControlLogix Power Supplies
ControlLogix power supplies are certified for use in SIL 2 applications. No extra
configuration or wiring is required for SIL 2 operation of the ControlLogix
power supplies. If an anomaly occurs in the supplied voltages, the power supply
immediately shuts down.
All ControlLogix power supplies are designed to perform these tasks:
•
Detect anomalies.
•
Communicate to the controllers with enough stored power to allow for an
orderly and deterministic shutdown of the system, including the controller
and I/O modules.
Redundant Power Supplies
ControlLogix redundant power supplies can be used in SIL 2-certified
applications. In a redundant power supply configuration, two power supplies are
connected to the same chassis.
The power supplies share the current load required by the chassis and an internal
solid state relay that can annunciate a fault. Upon detection of a failure in one
supply, the other redundant power supply automatically assumes the full current
load required by the chassis without disruption to installed devices.
The 1756-PSCA and 1756-PSCA2 redundant power supply chassis adapter
modules connect the redundant power supply to the chassis.
IMPORTANT
If you are using any of the 1756-P
x
75 power supplies, with a 1756-L6
x
/B or
1756-L7
x
/B controller, you must use the Series B version of the
nonredundant power supplies, that is, 1756-P
x
75/B power supplies.
IMPORTANT
If you are using a 1756-L6
x
/B controller in a redundant chassis, we
recommend that you
do not
use the redundant power supplies, that is, the
1756-P
x
75R power supplies, in that chassis.
In this case, we recommend that you use the Series B version of the
nonredundant power supplies, that is, the 1756-P
x
75/B power supplies.
Содержание 1756-L6 Series
Страница 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Страница 60: ...60 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 5 ControlLogix I O Modules Notes ...
Страница 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Страница 120: ...120 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix C PFD Calculations for a SIL 2 System Notes ...
Страница 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Страница 133: ...Allen Bradley Motors ...