8
U
SER
C
ONFIGURABLE
I
TEMS
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE
,
OPTIONAL
N
ETWORK
M
ANAGEMENT CARDS
,
OR
T
ERMINAL
M
ODE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELEC TABLE
C
HOICES
D
ESCRIPTION
Automatic Self-Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test
Set the interval at which the
UPS will execute a self-test.
UPS ID
UPS_IDEN
Up to eight characters to
define the UPS
Uniquely identify the UPS, (i.e.
server name or location) for
network management purposes.
Date of Last Battery
Replacement
Manufacture Date
mm/dd/yy
Reset this date when you replace
the battery modules.
Minimum Capacity
Before Return from
Shutdown
0 percent
0, 15, 25, 35, 50, 60, 75,
90 percent
Specify the percentage to which
batteries will be charged
following a low-battery
shutdown before powering
connected equipment.
Alarm Delay After
Line Failure
5 second delay
5 second delay,
30 second delay,
At Low Battery,
Never
Mute ongoing alarms or disable
all alarms permanently.
Shutdown Delay
20 seconds
0, 20, 60, 120, 240, 480,
720, 960 seconds
Set the interval between the time
when the UPS receives a
shutdown command and the
actual shutdown.
Duration of
Low Battery Warning.
2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately two
minutes of battery
runtime remains.
2, 5, 7, 10, 12, 15, 18,
20 minutes.
The low battery warning beeps
become continuous when two
minutes of runtime remains.
Change the warning interval to a
higher setting if the operating
system requires a longer interval
for shutdown.
Synchronized Turn-on
Delay
0 seconds
0, 20, 60, 120, 240, 480,
720, 960 seconds
Specify the time the UPS will
wait after the return of utility
power before turn-on (to avoid
branch circuit overloads).
High Bypass Point
+10% of
output voltage
setting
+5%, +10%, +15%,
+20%
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.