Safety Information - 

SAVE THIS GUIDE

 

This Safety Guide contains important instructions that should be followed during installation and maintenance of the 
equipment and batteries.  It is intended for customers who setup, install, relocate, or maintain equipment.  

Changes and modifications to this unit not expressly approved could void the warranty. 

Handling Safety

 

  <18 kg (<40 lb) 

  32–55 kg (70–120 lb) 

 

  18–32 kg (40–70 lb) 

  >55 kg (>120 lb) 

  >10º 

CAUTION! Electrical Safety 

 

Do not work alone under hazardous conditions.  

 

High current through conductive materials could cause severe burns. 

 

Check that the power cord(s), plug(s), and sockets are in good condition. 

 

Use qualified service personnel to change the plug on the UPS and to install permanently wired equipment. 

 

When grounding cannot be verified, disconnect the equipment from the utility power outlet before installing or 
connecting to other equipment. Reconnect the power cord only after all connections are made. 

 

Do not handle any metallic connector before the power has been disconnected. 

 

Connect the equipment to a three wire utility outlet (two poles plus ground). The receptacle must be connected to 
appropriate branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of receptacle may 
result in risk of electrical shock. 

 

230V models only: 

In order to maintain compliance with the Electro Magnetic Compliance directive for products sold in 

Europe, output cords attached to the UPS should not exceed 10 meters in length.

 

 

230V models only: 

Total leakage current from connected equipment and the UPS must not exceed 3.5 mA for a 

pluggable A Type UPS.

 

CAUTION! Deenergizing Safety 

 

If the UPS has an internal energy source (battery), the output may be energized when the unit is not connected to a utility 
power outlet. 

 

To deenergize a 

pluggable UPS , 

press the OFF button or switch to shut the equipment off. Unplug the UPS from the 

utility power outlet. Disconnect the external batteries where applicable and disconnect the internal battery (see User 
Manual). Push the ON button to deenergize the capacitors. 
To deenergize a 

permanently wired UPS, 

press the OFF button or switch to shut the equipment off. Switch off the 

utility circuit breaker that supplies power to t he UPS

.

 Disconnect the external batteries where applicable and disconnect 

the internal battery (see User Manual).

 

WARNING! Battery Safety 

 

This equipment contains potentially hazardous voltages

. Do not attempt to disassemble the unit. The 

only exception

 

is for a UPS containing batteries. Refer to the battery replacement procedures detailed in the User’s Manual. Except for 
the battery, the unit contains no user serviceable parts

. Repairs are to be performed only by qualified service 

personnel. 

 

Do not dispose of batteries in a fire. The batteries may explode. 

 

Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin and eyes. 

 

To avoid personal injury due to energy hazard, remove wrist watches and jewelry such as rings when replacing the 
batteries. Use tools with insulated handles. 

 

Replace batteries with the same number and type of batteries as originally installed in the equipment. 

Replacement and Recycling of Batteries

 

See your dealer or contact Rockwell Automation at  440-646-5800, for information on replacement battery kits and battery 
recycling.

 

 

Be sure to deliver the spent battery to a recycling facility in the re placement battery packing material.

 

 
 
 
 
41063-261-01(1) 

Содержание 1609-P10000E

Страница 1: ...41063 261 01 1 990 2672 09 2005 Allen Bradley User Manual for 8000 10000 VA UPS 1609 P8000E 8000 VA 200 240 VAC 1609 P10000E 10000 VA 200240 VAC Tower Rack Mount 6U Uninterruptible Power Supply...

Страница 2: ...rt Guide Removing the Batteries The unit is heavy To lighten the unit remove the batteries Refer to the unpacking instructions on the carton in which the unit is shipped Environmental Specifications T...

Страница 3: ...6 Use appropriate glands to achieve strain relief on the hardwired input and output power cables Input Connection Output Connection optional Wire to L1 L2 Wire to L1A L2A System Wiring Voltage Current...

Страница 4: ...3 Installing and Connecting the Batteries and Attaching the Front Bezel...

Страница 5: ...up the UPS The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period OPTIONS q External Battery Pa...

Страница 6: ...ely de energized from a remote location without switching to battery operation see EPO Option TVSS Screw The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lea...

Страница 7: ...ch Battery operation is not available while the UPS is in bypass mode see Troubleshooting Fault The UPS detects an internal fault see Troubleshooting Overload The connected loads are drawing more powe...

Страница 8: ...ltage display Press and hold the button to view the utility voltage bar graph display After a few seconds the five LED Battery Charge display on the right of the front panel shows the utility input vo...

Страница 9: ...nt Alarm Delay After Line Failure 5 second delay 5 second delay 30 second delay At Low Battery Never Mute ongoing alarms or disable all alarms permanently Shutdown Delay 20 seconds 0 20 60 120 240 480...

Страница 10: ...bypass operation Output Voltage 208 230 V models 230 VAC 208 230 V models 200 208 220 230 240 VAC Allows the user to select the UPS output voltage while online Output Frequency Automatic 50 3 Hz or 6...

Страница 11: ...uit UL CSA standards and an SELV circuit IEC standard Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be c...

Страница 12: ...nal battery packs Once the blank terminal window is open follow these steps to enter the number of battery packs Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User...

Страница 13: ...outages Use caution when handling heavy battery modules Refer to Installing and Connecting the Batteries and Attaching the Front Bezel for battery replacement procedure reverse instructions for batte...

Страница 14: ...or are near the end of service life Charge the battery module s Modules require recharging after extended outages and wear faster when put into service often or when operated at elevated temperatures...

Страница 15: ...he battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery Failure of a batte...

Страница 16: ...Support Refer to Contact Information below 3 Pack the UPS in its original packaging Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transi...

Страница 17: ...N Deenergizing Safety If the UPS has an internal energy source battery the output may be energized when the unit is not connected to a utility power outlet To deenergize a pluggable UPS press the OFF...

Отзывы: