Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input

Output

The output provides a SELV/PELV/ES1 rated voltage, which is galvanically 
isolated from the input voltage. The output of the devices includes a 
decoupling MOSFET for building 1+1 or n+1 redundant power supply systems.

The device is designed to supply any kind of loads, including capacitive and 
inductive loads. If extreme large capacitors, such as EDLCs (electric double 
layer capacitors or “UltraCaps”) with a capacitance > 1F are connected to the 
output, the unit might charge the capacitor in the HiccupPLUS mode.

The device is featured with a “soft output regulation characteristic” to achieve 
current share between multiple devices when they are connected in parallel. 
The “soft output regulation characteristic” regulates the output voltage in such 
a manner that the voltage at no load is approximately 4% higher than at 
nominal load.

Output voltage

Nom

DC 24V

23.8…25.2V

Adjustment range

See

Adjusting the Output Voltage on page 26

Factory settings

24.1V

±0.2%, at 10 A, cold unit (results to Typ 23.9V±0.2% at 24 
A and Typ 25.1V±0.2% at no load)

Line  regulation

Max

10 mV

85…300V AC

Load  regulation

Typ

1000 mV

Static value, 0 A --> 10 A; see 

Figure 8

.

Ripple and noise 

Max

50 mVpp

20 Hz to 20 MHz, 50 Ω

Output current

Nom

12 A

(1)

(1)

This current is also available for temperatures up to +70 °C with a duty cycle of 10% and/ or not longer than 1 minute every 10 
minutes.

Below 45 °C ambient temperature, see 

Figure 23

.

Nom

10 A

At 60 °C ambient temperature, se

Figure 23

.

Nom

7.5 A

At 70 °C ambient temperature, see 

Figure 23

.

Fuse breaking

(2)

 

(2) The fuse braking current is an enhanced transient current which helps to start heavy loads or to trip fuses on faulty output 

branches. The output voltage stays above 20V. See 

Peak Current Capability on page 25

 for additional measurements.

Typ

30 A

Up to 12 ms once every 5 seconds, se

Figure 10

.

Overload protection

Included

Electronically helps protected against overload, no-load, 
and short-circuits. In a protection event, audible noise 
can occur.

Overload behavior

Continuous current

Output voltage >13V DC, see 

Figure 8

.

Intermittent current

(3)

(3) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2 s. After 

this, the output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated 
as long as the overload exists. If the overload has been cleared, the device will operate normally. See 

Figure 8

.

Output voltage <13V DC, see 

Figure 8

.

Overload/ short-
circuit current

Max

15.5 A

Continuous current, see 

Figure 8

.

Typ

14 A

Intermittent current peak value for Typ 2 s Load 
impedance 10mΩ, see 

Figure 9

.

Discharge current of output capacitors is not included

Max

5 A

Intermittent current average value (R.M.S.) Load 
impedance 10mΩ, see 

Figure 9

.

Output capacitance

Typ

4400 µF

Included inside the power supply

Back-feeding loads

Max

35V

The unit is resistant and does not show malfunctioning 
when a load feeds back voltage to the power supply. It 
does not matter whether the power supply is on or off. 
The absorbing energy can be calculated according to the 
built-in large sized output capacitor.

Содержание 1606-XLE240CRZ

Страница 1: ...Redundancy Power Supply 24V 10 A 240 W Single phase Input Catalog Numbers 1606 XLE240ERL 1606 XLE240ERZ 1606 XLE240CRZ 1606 XLE240EDRZ Reference Manual Original Instructions...

Страница 2: ...by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written p...

Страница 3: ...is Running 17 Replacement Instructions Example for left power supply 17 Front Side and User Elements 18 Electromagnetic Compatibility 19 Environment 20 Safety and Protection Features 21 Dielectric Str...

Страница 4: ...4 Rockwell Automation Publication 1606 RM110A EN P July 2020 Notes...

Страница 5: ...tor terminals that allow replacement on an active application Catalog number 1606 XLE240EDRZ features an enhanced DC input voltage range and catalog number 1606 XLE240ECRZ is additionally equipped wit...

Страница 6: ...240EDxx Input current DC 2 35 A 0 84 A At 110 300V DC AC Inrush current 6 9 Apk At 120 230V AC Efficiency 93 0 94 7 At 120 230V AC Losses 18 1 13 4 W At 120 230V AC Hold up time 37 37ms At 120 230V AC...

Страница 7: ...e tripping of the circuit breaker AC 100V AC 120V AC 230V Notes Input current Typ 2 63 A 2 17 A 1 14 A At 10 A see Figure 3 Power factor Typ 0 99 0 99 0 97 At 10 A see Figure 4 Crest factor Typ 1 5 1...

Страница 8: ...earth wire or to the machine ground Figure 5 Wiring for DC Input DC input Nom DC 110 150V 20 for 1606 XLE240ER Nom DC 110 300V 20 for 1606 XLE240EC DC input range Min 88 180V DC Continuousoperation fo...

Страница 9: ...Nominal Load 120V AC Input and 25 C 77 F Ambient Figure 7 Typical Turn on Behavior at Nominal Load 230V AC Input and 25 C 77 F Ambient Attribute AC100V AC120V AC230V Temperature Inrush current Max 11...

Страница 10: ...ure 23 Nom 10 A At 60 C ambient temperature see Figure 23 Nom 7 5 A At 70 C ambient temperature see Figure 23 Fuse breaking 2 2 The fuse braking current is an enhanced transient current which helps to...

Страница 11: ...operation Figure 10 Dynamic Overcurrent Capability Typ Output Voltage dynamic behavior 12ms 0 4 8 12 28V 16 20 24 0 50A 20 10 30 40 5 15 25 35 45 Output Current AC100V AC120V AC230V Hold up Time Typ 7...

Страница 12: ...act Behavior Contact closes As soon as the output voltage reaches Typ 22V DC Contactopens As soon as the output voltage dips below 22V DC Short dips will be extended to a signal length of 100 ms Dips...

Страница 13: ...the time Typ 91 8 92 4 93 9 25 at 2 5 A 25 at 5 A 25 at 7 5 A 25 at 10 A Power losses Typ 4 W 3 7 W 2 9 W At 0 A Typ 11 3 W 10 7 W 8 6 W At5 A Typ 20 3 W 18 1 W 13 4 W At10 A Typ 25 4 W 22 3 W 16 4 W...

Страница 14: ...ation of the likelihood of a device to fail An MTBF figure of for example 1 000 000h means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field However it c...

Страница 15: ...rter Output Filter Output Power Manager Temper ature Shut down Input Fuse Input Filter Input t r Active Inrush Limiter L N Decoupling Output Voltage Regulator Output Voltage Monitor V OUT DC ok Contac...

Страница 16: ...Input Output DC OK Signal Type Quick connect spring clamp termination Push in termination Solid wire max 6 mm2 1 5 mm2 Stranded wire max 4 mm2 1 5 mm2 American Wire Gauge AWG 20 10 AWG 24 16 Max wire...

Страница 17: ...odule while the system is running Replacement Instructions Example for left power supply 1 Switch off circuit breaker 1a 2 Remove plug 2a 3 Remove plug 3a The plug helps prevent the cables from shorti...

Страница 18: ...1 Input Terminals N L N L Line Input PE Protective Earth Input 2 Output Terminals Two identical poles and two identical poles Positive Output Negative return Output 3 Output Voltage Potentiometer 4 D...

Страница 19: ...f 120V AC 84V AC 50 of 120V AC 60V AC 1000 ms 500 ms 200 ms Criterion A Criterion A Criterion A Powerful transients VDE 0160 Over entire load range 750V 0 3 ms Criterion A 1 Criterion A Power supply s...

Страница 20: ...2 17 8Hz 1 6 mm 17 8 500Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 2 30 g 6 ms 20 g 11 ms 3 bumps per direction 18 bumps in total According to IEC 60068 2 27 Shock and vibration are tested i...

Страница 21: ...n ambient temperature is too high ventilation is obstructed or the derating requirements are not followed There is no correlation between the operating temperature and turn off temperature since this...

Страница 22: ...le below Figure 25 Dielectric Strength A B C D 1 1 When testing input to DC OK ensure that the maximal voltage between DC OK and the output is not exceeded column D We recommend connecting DC OK pins...

Страница 23: ...E File E56639 ANSI ISA 12 12 01 Class I Div 2 Listed for use in Hazardous Location Class I Div 2 EN 60079 0 EN 60079 7 ATEX II 3G Ex ec nC II T4 Gc Approval for use in hazardous locations Zone 2 Categ...

Страница 24: ...eel Installationclearances Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on the left and right sides are recommended when the device is loaded permanently with more tha...

Страница 25: ...nch circuit the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner This avoids voltage loss in adjacent circuits The extra current peak current is supplied by the...

Страница 26: ...l mode feature a setting to 24 0V results to an output voltage of 23 8V 0 2 at 24 A and 25 0V 0 2 at no load See Figure 33 Output current Min 12 A At 45 C 113 F Min 10 A At 60 C 140 F Min 7 55 A At 70...

Страница 27: ...atteries when following these instructions Set output voltage measured at disconnected battery very precisely to the end of charge voltage Use the potentiometer which is hidden behind the flap on the...

Страница 28: ...y to the ride through time of PLCs This requires power supplies with high current reserves and large output capacitors Furthermore the impedance of the faulty branch must be sufficiently small in orde...

Страница 29: ...a protection against touching Avoid return voltage for example from a decelerating motor or battery which is applied to the output terminals Keep an installation clearance of 15 mm left right between...

Страница 30: ...it Keep an installation clearance of 15 mm left right between two power supplies and avoid installing the power supplies on top of each other Do not use power supplies in parallel in mounting orientat...

Страница 31: ...ual power supply units by utilizing the built in DC OK relay contacts on each power supply Figure 38 Wiring Diagram 1 1 Redundancy for 10 A Output Current Figure 39 Wiring Diagram N 1 Redundancy for 2...

Страница 32: ...uations the inside temperature defines the ambient temperature for the power supply The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure T...

Страница 33: ...lifetime expectancy of A1 Figure 41 Mounting Orientation A Standard Orientation Figure 42 Mounting Orientation B Upside Down Figure 43 Mounting Orientation C Table top Mounting Figure 44 Mounting Ori...

Страница 34: ...34 Rockwell Automation Publication 1606 RM110A EN P July 2020 Redundancy Power Supply 24V 10 A 240 W Single phase Input Notes...

Страница 35: ...Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Installation and Maintenance of Solid state Control publication SG...

Страница 36: ...e articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation instructions manuals bro...

Отзывы: