Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
11
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
Hold-up Time
Figure 8 - Output Voltage Versus Output Current, Typ
Figure 9 - Short-circuit on Output, Hiccup
PLUS
Mode, Typ
Output Voltage
0
4
8
12
28V
16
20
24
0
12.5
20A
7.5
2.5
5
10
15 17.5
A
B
A: continuous current
B: intermitted current
Output
Current
Output
Current
0
14A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
Figure 10 - Dynamic Overcurrent, Capability, Typ
Output Voltage
(dynamic behavior, < 12ms)
0
4
8
12
28V
16
20
24
0
50A
20
10
30
40
5
15
25
35
45
Output
Current
AC 100V
AC 120V
AC 230V
Hold-up Time
Typ
73 ms
73 ms
73 ms
Min
55 ms
55 ms
55 ms
Typ
37 ms
37 ms
37 ms
Min
28 ms
28 ms
28 ms
Figure 11 - Hold-up Time Versus Input Voltage
Figure 12 - Shut-down Behavior, Definitions
0
10
20
30
40
80ms
90
120
155
190
230V AC
Input Voltage
50
60
Hold-up Time
a) At 5A typ.
b) At 5A min.
70
a
c) At 10A typ.
d) At 10A min.
b
c
d
- 5%
Zero Transition
Output
Voltage
Input
Voltage
Hold-up Time