Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input

Product Overview

The Bulletin 1606-XLE line features cost optimized power supplies without 
compromising quality, reliability, and performance. The 1606-XLE240ERL and 
1606-XLE240ERZ power supplies offer high efficiency, electronic inrush 
current limitation, active PFC, wide operational temperature range, and 
compact size. The units include a decoupling MOSFET for building 1+1 or n+1 
redundant power supply systems.

These redundancy power supplies come with three connection terminal 
options; screw terminals, spring-clamp terminals, or plug connector terminals 
that allow replacement on an active application.

Catalog number 1606-XLE240EDRZ features an enhanced DC input voltage 
range and catalog number 1606-XLE240ECRZ is additionally equipped with 
conformal coated printed circuit boards.

These power supplies are suitable for a wide range of applications due to high 
immunity to transients and power surges, low electromagnetic emission, a DC 
OK signal contact for remote monitoring, and extensive international 
approvals.

AC 100…240V Wide-range Input

Width only 39 mm

Built-in Decoupling Mosfet for 1+1 and n+1 Redundancy

Efficiency up to 95.2%

20% Output Power Reserves

Safe HiccupPLUS Overload Mode

Easy Fuse Breaking – 3 times nominal current for 12 ms

Active Power Factor Correction (PFC)

Minimal Inrush Current Surge

Full Power Between -25…+60 °C (-13…+140 °F)

DC OK Relay Contact

Current Sharing Feature Included

Содержание 1606-XLE240CRZ

Страница 1: ...Redundancy Power Supply 24V 10 A 240 W Single phase Input Catalog Numbers 1606 XLE240ERL 1606 XLE240ERZ 1606 XLE240CRZ 1606 XLE240EDRZ Reference Manual Original Instructions...

Страница 2: ...by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written p...

Страница 3: ...is Running 17 Replacement Instructions Example for left power supply 17 Front Side and User Elements 18 Electromagnetic Compatibility 19 Environment 20 Safety and Protection Features 21 Dielectric Str...

Страница 4: ...4 Rockwell Automation Publication 1606 RM110A EN P July 2020 Notes...

Страница 5: ...tor terminals that allow replacement on an active application Catalog number 1606 XLE240EDRZ features an enhanced DC input voltage range and catalog number 1606 XLE240ECRZ is additionally equipped wit...

Страница 6: ...240EDxx Input current DC 2 35 A 0 84 A At 110 300V DC AC Inrush current 6 9 Apk At 120 230V AC Efficiency 93 0 94 7 At 120 230V AC Losses 18 1 13 4 W At 120 230V AC Hold up time 37 37ms At 120 230V AC...

Страница 7: ...e tripping of the circuit breaker AC 100V AC 120V AC 230V Notes Input current Typ 2 63 A 2 17 A 1 14 A At 10 A see Figure 3 Power factor Typ 0 99 0 99 0 97 At 10 A see Figure 4 Crest factor Typ 1 5 1...

Страница 8: ...earth wire or to the machine ground Figure 5 Wiring for DC Input DC input Nom DC 110 150V 20 for 1606 XLE240ER Nom DC 110 300V 20 for 1606 XLE240EC DC input range Min 88 180V DC Continuousoperation fo...

Страница 9: ...Nominal Load 120V AC Input and 25 C 77 F Ambient Figure 7 Typical Turn on Behavior at Nominal Load 230V AC Input and 25 C 77 F Ambient Attribute AC100V AC120V AC230V Temperature Inrush current Max 11...

Страница 10: ...ure 23 Nom 10 A At 60 C ambient temperature see Figure 23 Nom 7 5 A At 70 C ambient temperature see Figure 23 Fuse breaking 2 2 The fuse braking current is an enhanced transient current which helps to...

Страница 11: ...operation Figure 10 Dynamic Overcurrent Capability Typ Output Voltage dynamic behavior 12ms 0 4 8 12 28V 16 20 24 0 50A 20 10 30 40 5 15 25 35 45 Output Current AC100V AC120V AC230V Hold up Time Typ 7...

Страница 12: ...act Behavior Contact closes As soon as the output voltage reaches Typ 22V DC Contactopens As soon as the output voltage dips below 22V DC Short dips will be extended to a signal length of 100 ms Dips...

Страница 13: ...the time Typ 91 8 92 4 93 9 25 at 2 5 A 25 at 5 A 25 at 7 5 A 25 at 10 A Power losses Typ 4 W 3 7 W 2 9 W At 0 A Typ 11 3 W 10 7 W 8 6 W At5 A Typ 20 3 W 18 1 W 13 4 W At10 A Typ 25 4 W 22 3 W 16 4 W...

Страница 14: ...ation of the likelihood of a device to fail An MTBF figure of for example 1 000 000h means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field However it c...

Страница 15: ...rter Output Filter Output Power Manager Temper ature Shut down Input Fuse Input Filter Input t r Active Inrush Limiter L N Decoupling Output Voltage Regulator Output Voltage Monitor V OUT DC ok Contac...

Страница 16: ...Input Output DC OK Signal Type Quick connect spring clamp termination Push in termination Solid wire max 6 mm2 1 5 mm2 Stranded wire max 4 mm2 1 5 mm2 American Wire Gauge AWG 20 10 AWG 24 16 Max wire...

Страница 17: ...odule while the system is running Replacement Instructions Example for left power supply 1 Switch off circuit breaker 1a 2 Remove plug 2a 3 Remove plug 3a The plug helps prevent the cables from shorti...

Страница 18: ...1 Input Terminals N L N L Line Input PE Protective Earth Input 2 Output Terminals Two identical poles and two identical poles Positive Output Negative return Output 3 Output Voltage Potentiometer 4 D...

Страница 19: ...f 120V AC 84V AC 50 of 120V AC 60V AC 1000 ms 500 ms 200 ms Criterion A Criterion A Criterion A Powerful transients VDE 0160 Over entire load range 750V 0 3 ms Criterion A 1 Criterion A Power supply s...

Страница 20: ...2 17 8Hz 1 6 mm 17 8 500Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 2 30 g 6 ms 20 g 11 ms 3 bumps per direction 18 bumps in total According to IEC 60068 2 27 Shock and vibration are tested i...

Страница 21: ...n ambient temperature is too high ventilation is obstructed or the derating requirements are not followed There is no correlation between the operating temperature and turn off temperature since this...

Страница 22: ...le below Figure 25 Dielectric Strength A B C D 1 1 When testing input to DC OK ensure that the maximal voltage between DC OK and the output is not exceeded column D We recommend connecting DC OK pins...

Страница 23: ...E File E56639 ANSI ISA 12 12 01 Class I Div 2 Listed for use in Hazardous Location Class I Div 2 EN 60079 0 EN 60079 7 ATEX II 3G Ex ec nC II T4 Gc Approval for use in hazardous locations Zone 2 Categ...

Страница 24: ...eel Installationclearances Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on the left and right sides are recommended when the device is loaded permanently with more tha...

Страница 25: ...nch circuit the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner This avoids voltage loss in adjacent circuits The extra current peak current is supplied by the...

Страница 26: ...l mode feature a setting to 24 0V results to an output voltage of 23 8V 0 2 at 24 A and 25 0V 0 2 at no load See Figure 33 Output current Min 12 A At 45 C 113 F Min 10 A At 60 C 140 F Min 7 55 A At 70...

Страница 27: ...atteries when following these instructions Set output voltage measured at disconnected battery very precisely to the end of charge voltage Use the potentiometer which is hidden behind the flap on the...

Страница 28: ...y to the ride through time of PLCs This requires power supplies with high current reserves and large output capacitors Furthermore the impedance of the faulty branch must be sufficiently small in orde...

Страница 29: ...a protection against touching Avoid return voltage for example from a decelerating motor or battery which is applied to the output terminals Keep an installation clearance of 15 mm left right between...

Страница 30: ...it Keep an installation clearance of 15 mm left right between two power supplies and avoid installing the power supplies on top of each other Do not use power supplies in parallel in mounting orientat...

Страница 31: ...ual power supply units by utilizing the built in DC OK relay contacts on each power supply Figure 38 Wiring Diagram 1 1 Redundancy for 10 A Output Current Figure 39 Wiring Diagram N 1 Redundancy for 2...

Страница 32: ...uations the inside temperature defines the ambient temperature for the power supply The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure T...

Страница 33: ...lifetime expectancy of A1 Figure 41 Mounting Orientation A Standard Orientation Figure 42 Mounting Orientation B Upside Down Figure 43 Mounting Orientation C Table top Mounting Figure 44 Mounting Ori...

Страница 34: ...34 Rockwell Automation Publication 1606 RM110A EN P July 2020 Redundancy Power Supply 24V 10 A 240 W Single phase Input Notes...

Страница 35: ...Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Installation and Maintenance of Solid state Control publication SG...

Страница 36: ...e articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation instructions manuals bro...

Отзывы: