Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
Terminals and Wiring
The terminals are IP20 fingersafe constructed and suitable for field- and factory
wiring.
Instructions for Wiring
•
Use appropriate copper cables that are designed for minimum operating
temperatures of: 60 °C for ambient up to 45 °C, 75 °C for ambient up to 60
°C and 90 °C for ambient up to 70 °C minimum.
•
Follow national installation codes and installation regulations!
•
Confirm that all strands of a stranded wire enter the terminal
connection!
•
Verify unused terminal compartments are securely tightened.
•
Ferrules are allowed and recommended.
1606-XLE240ERL
Input
Output
DC OK-Signal
Type
Quick-connect spring-clamp termination
Push-in termination
Solid wire max
6 mm
2
1.5 mm
2
Stranded wire max
4 mm
2
1.5 mm
2
American Wire Gauge
AWG 20-10
AWG 24-16
Max wire diameter (including
ferrules)
2.8 mm
1.6 mm
Wire stripping length
10 mm (0.4 in.)
7 mm (0.28 in.)
Screwdriver
—
3 mm slotted to open the
spring
1606-XLE240ERZ, -XLE240EDRZ,
-XLE240ECRZ
Input
Output
DC OK-Signal
Type
Plug connector with screw termination
(1)
(1)
Do not unplug the connectors more than 20 times in total.
Solid wire max
4 mm
2
6 mm
2
1.5 mm
2
Stranded wire max
2.5 mm
2
4 mm
2
1.5 mm
2
American Wire Gauge
AWG 20-12
AWG 20-10
AWG 24-16
Wire diameter max (including
ferrules)
2.4 mm
2.4 mm
1.8 mm
Recommended tightening torque,
Max
0.5 Nm, 4.5 lb-in
0.5 Nm, 4.5 lb-in
0.8 Nm, 7 lb-in
Wire stripping length
7 mm (0.28 in.)
7 mm (0.28 in.)
6 mm (0.24 in.)
Screwdriver
3 mm slotted or cross-head No 2
3 mm slotted