8
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Basic Power Supply 10 A
Input
Attribute
1606-XLB240E
AC input
nom
100…240V AC
Auto-select, suitable for TN-, TT- and IT mains networks
AC input range
min
90…264V AC
continuous operation
min
264…300V AC
< 500 ms
Allowed voltage L or N to earth
max
300V AC
continuous, IEC 62103
Input frequency
nom
50…60 Hz
±6%
Turn-on voltage
typ
81V AC
at 24V 10 A, steady-state value, see
Figure 2
Shut-down voltage
typ
63V AC/71V AC
at no load/nominal load, steady-state value, see
Figure 2
External input protection
See recommendations in
External Input Protection on page 16
.
Attribute
AC 100V
AC 120V
AC 230V
Input current
typ
2.60 A
2.17 A
1.18 A
at 24V, 10 A, see
Figure 3
Power factor
(1)
typ
0.99
0.98
0.93
at 24V, 10 A, see
Figure 5
Crest factor
(2)
typ
1.6
1.7
2.0
at 24V, 10 A
Start-up delay
typ
400 ms
260 ms
200 ms
see
Figure 4
Rise time
typ
60 ms
at 24V, 10 A const. current load, 0 mF load capacitance, see
Figure 4
typ
230 ms
at 24V, 10 A const. current load, 5 mF load capacitance, see
Figure 4
Turn-on overshoot
max
200 mV
see
Figure 4
(1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
(2) The crest factor is the mathematical ratio of the peak value to the T ms value of the input current waveform.
Figure 2 - Input Voltage Range, typ
Figure 4 - Turn-on Behavior, Definitions
Figure 3 - Input Current vs. Output Load at 24V
Figure 5 - Power Factor vs. Output Load
Turn-on
90V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Shut
-down
Start-up
delay
Rise
Time
Ov
ersh
oot
- 5%
Output
Voltage
Input
Voltage
10A
0
1
2
3
4
5
6
7
0
0.5
1.0
1.5
2.0
2.5
3A
Input Current, typ.
8
9
Output Current
a) 100Vac
b) 120Vac
c) 230Vac
c
a
b
10A
2
3
4
6
8
0.70
0.75
5
7
9
0.80
0.85
0.90
0.95
1.00
Power Factor, typ.
1
Output Current
b
a
a) 100Vac
b) 120Vac
c) 230Vac
c