Allen-Bradley 1606-XLB240E Скачать руководство пользователя страница 15

Rockwell Automation Publication 1606-RM056A-EN-P - December 2016

15

Basic Power Supply 10 A

Application Notes

Peak Current Capability

The unit can deliver peak currents (up to several milliseconds) which are 
higher than the specified short-term currents.

This helps to start current demanding loads. Solenoids, contactors, and 
pneumatic modules often have a steady state coil and a pick-up coil. The inrush 
current demand of the pick-up coil is several times higher than the steady-state 
current and usually exceeds the nominal output current. The same situation 
applies when starting a capacitive load.

The peak current capability also delivers the safe operation of subsequent 
circuit breakers of load circuits. The load branches are often individually 
protected with circuit breakers or fuses. If there is a short or an overload in one 
branch circuit, the fuse or circuit breaker need a certain amount of overcurrent 
to open in a timely manner. This avoids voltage loss in adjacent circuits.

The extra current (peak current) is supplied by the power converter and the 
built-in large sized output capacitors of the power supply. The capacitors get 
discharged during such an event, which causes a voltage dip on the output. The 
following two examples show typical voltage dips:

Figure 17 - Peak Load with 2x the Nominal Current for 50 ms, typ

Figure 18 - Peak Load with 5x the Nominal Current for 5 ms, typ

10ms/DIV

Output
Voltage

Output
Current

24V

0A

20A

14.9V

 

20A Peak load (resistive) for 50ms 
Output voltage dips from 24V to 14.9V. 

 

1ms/DIV

Output
Voltage

Output
Current

24V

0A

50A

3.7V

 

50A Peak load (resistive) for 5ms 
Output voltage dips from 24V to 3.7V. 

Peak Current Capability

Voltage Dip

Peak Load

Peak current voltage dips

typ

24…14.9V

at 20 A for 50 ms, resistive load

typ

24…7.1V

at 50 A for 2 ms, resistive load

typ

24…3.7V

at 50 A for 5 ms, resistive load

Содержание 1606-XLB240E

Страница 1: ...Basic Power Supply 10 A Catalog Number 1606 XLB240E Reference Manual OriginalInstructions...

Страница 2: ...nformation circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited T...

Страница 3: ...Mean Time Between Failure MTBF 13 Protection Features 6 Functional Diagram 13 Safety Features 7 EMC 14 Installation Notes 7 Application Notes 15 Terminals and Wiring 7 Specifications 15 Installation N...

Страница 4: ...Hz mains frequency AC 120V parameters are valid for 60 Hz mains frequency AC 230V A figure that is displayed with the AC or DC before the value represents a nominal voltagewith standardtolerances inc...

Страница 5: ...158 F This power supply features a wide input voltage range which makes it suitable for global use The addition of a DC OK signal makes the power supply ideal for many industry applications such as pr...

Страница 6: ...E Output protection Electronically protected against overload no load and short circuits 1 1 If there is a protection event audible noise can occur Output overvoltage protection typ 30 5V DC max 32 V...

Страница 7: ...einforced insulation IEC EN 60204 1 EN 50178 IEC 62103 IEC 60364 4 41 Class of protection I PE Protective Earth connection required Isolation resistance 5 MOhm input to output 500V DC Touch current le...

Страница 8: ...t 24V 10 A Start up delay typ 400 ms 260 ms 200 ms see Figure 4 Rise time typ 60 ms at 24V 10 A const current load 0 mF load capacitance seeFigure 4 typ 230 ms at 24V 10 A const current load 5 mF load...

Страница 9: ...on max 14 5 A peak 17 A peak 32 A peak 40 C 104 F ambient cold start typ 7 A peak 8 5 A peak 16 A peak 40 C 104 F ambient cold start Inrush energy typ 11 5 A peak 14 A peak 26 A peak 25 C 77 F ambien...

Страница 10: ...continuous current output voltage 13V DC see Figure 7 HiccupPLUS mode output voltage 13V DC see Figure 7 Short circuit current min 11 A 2 load impedance 50mOhm see Figure 7 max 15 A load impedance 50m...

Страница 11: ...s 53 ms 53 ms 24V 10 A typ 32 ms 32 ms 32 ms min 26 ms 26 ms 26 ms Figure 9 Hold up Time vs Input Voltage Figure 10 Shut down Behavior Definitions 0 10 20 30 40 80ms 90 120 230Vac Input Voltage 50 60...

Страница 12: ...ad for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time Figure 12 Efficiency...

Страница 13: ...Lifetime expectancy is specified in operational hours and is calculated accordingtothecapacitor smanufacturerspecification Themanufactureroftheelectrolyticcapacitorsonlyguaranteesamaximum life of up...

Страница 14: ...ge sags SEMI F47 0706 dips on the input voltage according to SEMI F47 standard 80 of 120V AC 96V AC 70 of 120V AC 84V AC 50 of 120V AC 60V AC 50 of 120V AC 60V AC 1000ms 500ms 200ms 200ms Criterion A...

Страница 15: ...in one branch circuit the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner This avoids voltage loss in adjacent circuits The extra current peak current is suppl...

Страница 16: ...If an external fuse is necessary or utilized minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker A minimum value of 10A B characteristic or 6A C characteristic...

Страница 17: ...ect as many units in series as needed providing the sum of the output voltage does not exceed 150V DC Voltages with a potential above 60V DC are not SELV any more and can be dangerous Such voltages mu...

Страница 18: ...three phase system Such a phase to phase connection is allowed as long as the supplying voltage is below 240V 10 Figure 20 Operation on Two Phases Use in a Tightly Sealed Enclosure When the power sup...

Страница 19: ...24 28V DC Output Current 10 A at 24V amb 55 C 131 F 6 25 A at 24V amb 70 C 158 F 8 6 A at 28V amb 55 C 131 F 5 4 A at 28V amb 70 C 158 F Output power 240 W ambient 55 C 131 F 150 W ambient 70 C 158 F...

Страница 20: ...1000 m 2000 m 6500 ft seeFigure 22 Overvoltage category III IEC 62103 EN 50178 altitudes up to 2000 m II altitudes from 2000 m to 6000 m Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS co...

Страница 21: ...testing set the cutoff current settings to the value in the following table Figure 23 Dielectric Strength To meet the PELV requirements according to EN60204 1 6 4 1 we recommend that either the pole t...

Страница 22: ...EN 60950 1 EN 61000 6 UL 508 Listed for use as Industrial Control Equipment U S A UL 508 and Canada C22 2 No 14 15 File E56639 UL 60950 1 Recognized for use as Information Technology Equipment U S A U...

Страница 23: ...aterial of Housing FlameretardantPolycarbonate PC UL94 V0Vicatsofteningtemperaturespecifiedwith149 C 300 F according to ASTM D1525 Installation Clearances Keep the following installation clearances 40...

Страница 24: ...24 Rockwell AutomationPublication 1606 RM056A EN P December 2016 Basic Power Supply 10 A Notes...

Страница 25: ......

Страница 26: ...al Code for your product Use the code to route your call directly to a technical support engineer http www rockwellautomation com global support direct dial page Literature Library Installation Instru...

Отзывы: