Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
19
Basic Power Supply 10 A
Specifications
Attribute
Case A
Case B
Load
(1)
(1) Load is placed outside the box.
24V, 10 A
24V, 8 A (=80%)
Temperature inside the box
(2)
(2) In the middle of the right side of the power supply with a distance of 1 cm (0.39 in.)
48.6 °C (199.4 °F)
43.7 °C (110.1 °F)
Temperature outside the box
24.9 °C (76.8 °F)
24.9 °C (76.8 °F)
Temperature rise
23.7 K
18.8 K
Attribute
1606-XLB240E
Notes
Output Voltage
24V DC
Adjustment range
24…28V DC
Output Current
10 A
at 24V, amb <55°C (131°F)
6.25 A
at 24V, amb <70°C (158 °F)
8.6 A
at 28V, amb <55°C (131°F)
5.4 A
at 28V, amb <70°C (158 °F)
Output power
240 W
ambient <55°C (131°F)
150 W
ambient <70°C (158 °F)
Output ripple
< 100 mVpp
20 Hz…20 MHz
AC Input voltage
100…240V AC
±10%
Mains frequency
50…60Hz
±6%
AC Input current
2.17 A/1.18 A
at 120/230V AC
Power factor
0.98/0.93
at 120/230V AC
AC Inrush current
14A/26A peak
at 120/230V AC, 40°C (104 °F)
Efficiency
94.0%/95.2%
at 120/230V AC
Losses
15.3W/12.1W
at 120/230V AC
Temperature range
-25 …+70 °C (-13…+158 °F)
operational
Derating
6W/°C
55…70 °C (131…158 °F)
Hold-up time
typ 32 ms/ 32 ms
at 120/230V AC
Dimensions
49 x 124 x 124 mm (
W x H x D
Weight
540 g/1.2 lb