![Allen-Bradley 1404-M4 Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/allen-bradley/1404-m4/1404-m4_user-manual_2900452073.webp)
Publication 1404-UM001D-EN-E - October 2004
Communications
4-13
Optional Ethernet Communications
Powermonitor 3000 units with a catalog number ending in “-ENT” are
equipped with an optional Ethernet 10BaseT communication port and
a native RS-485 port in a dual-port configuration that allows
simultaneous operation of the ports. You must configure the
communications parameters before you connect your Powermonitor
3000 to an Ethernet network. Use the Display Module under the
PROGRAM > OPTIONAL COMMUNICATIONS
menu. See your
network administrator for assistance in setting the communications
options.
Configuration parameters include:
•
IP (Internet Protocol) address
•
Subnet Mask
•
Gateway IP address
•
Keep-alive Time (Series A only)
•
Protocol Select (Series A only)
The
IP Address
uniquely identifies your Powermonitor 3000 on the
network. You configure the unit’s IP address the way it is most
commonly expressed, as four decimal numbers connected by decimal
points:
aaa.bbb.ccc.ddd.
You may set each number (also called byte
or octet) within the range of 0 to 255 decimal. The default IP address
is 128.1.1.
x
, where
x
is the factory-assigned Unit ID number. A
Powermonitor 3000 (Series A, only) with an IP address of 0.0.0.0 will
get its operating IP address, subnet mask and gateway IP address from
a bootp server on power-up. An IP address of 255.255.255.255 is not
permitted.
The IP address is a 32-bit binary number, which consists of the
network address (“NetID”) and the machine address (“HostID”). The
Subnet Mask
defines the boundary between the NetID and HostID in
the IP address. Each “1” bit in the subnet mask represents the NetID
and each “0” represents the HostID. Here is an example:
IMPORTANT
The IP address for your Powermonitor 3000 must not
conflict with the IP address of any other device on
the network. Contact your network administrator to
obtain a unique IP address for your unit.
Содержание 1404-M4
Страница 1: ...Bulletin 1404 Powermonitor 3000 1404 M4 1404 M5 1404 M6 1404 M8 User Manual Allen Bradley HMIs ...
Страница 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Страница 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Страница 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Страница 277: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 23 Ladder Diagram Allen Bradley HMIs ...
Страница 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Страница 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Страница 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Страница 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Страница 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Страница 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Страница 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Страница 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Страница 355: ...Allen Bradley HMIs ...