I/O Operations
The Powermonitor 3000 is equipped with two relay outputs and two
status inputs designed to provide a discrete interface with your
application.
Relay and KYZ Output
Operations
The Relay output is an electromechanical Form C relay with contacts
rated at 10 amperes at 240 VAC or 250 VDC. This set of contacts is also
rated to meet IEEE C37.90 requirements for power circuit breaker
tripping duty. The KYZ output is a solid-state relay rated at 80 mA at
240 VAC or 250 VDC that provides higher reliability and long life for
low-power signaling duty such as a kWh pulse output.
The two outputs operate independently and you may configure each
output
’
s operation individually. You may use the Display Module or
communications to set the output configuration parameters in the
Advanced Device Configuration table. The output configuration
options for the relay and KYZ outputs include:
•
Control source:
specifies what controls the selected output.
Options are 0= none; 1 through 6= pulsed output; 7= setpoint
control; 8 discrete I/O control. Default = 7
•
Output scale:
specifies the scaling factor for pulsed operation.
Range 1 to 30,000; default = 10
•
Output width:
specifies the pulse width for pulsed operation.
Range 0 or 40 to 2,000 mSec
•
Force command:
overrides setpoint, communications, discrete or
pulsed control until the force is released. Options are: 0 = no
change; 1 = force the output energized; 2 = forced the output
de-energized; 3 = release the force
•
Default output state on communications loss:
specifies response
to a loss of communications. Options are 0= last state/ resume;
1= last state/ freeze; 2= de-energize/ resume; 3= de-energize/
freeze. See below.
Содержание 1404-M4
Страница 1: ...Bulletin 1404 Powermonitor 3000 1404 M4 1404 M5 1404 M6 1404 M8 User Manual Allen Bradley HMIs ...
Страница 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Страница 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Страница 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Страница 277: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 23 Ladder Diagram Allen Bradley HMIs ...
Страница 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Страница 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Страница 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Страница 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Страница 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Страница 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Страница 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Страница 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Страница 355: ...Allen Bradley HMIs ...