Publication 1404-UM001D-EN-E - October 2004
8-2
Advanced Features
•
Capture number:
selects a capture for read-back or returns the
last capture selected. Range 1 to 8 (M6) or 1 to 2 (M8). Default 1.
•
Channel number:
selects a channel number or returns the last
channel number selected. Range: 1 = V1, 2 = I1, 3 = V2, 4 = I2, 5
= V3, 6 = I3, 7 = I4. Default 1.
•
Block number:
selects a data block for the next read or returns
the last block selected. Range depends on communications type.
See below. Default 1.
•
Read-back mode:
selects a read-back mode or returns the last
mode selected. Range 0 to 2, default 0. See below.
•
Clear / trigger command:
clears one or all captures or triggers a
new capture. Always returns 0. In the M8 model, values of 3
through 8 have same meaning as 0. Options are listed below:
0 - no action
1 - clear capture 1
2 - clear capture 2
3 - clear capture 3 (M6 only)
4 - clear capture 4 (M6 only)
5 - clear capture 5 (M6 only)
6 - clear capture 6 (M6 only)
7 - clear capture 7 (M6 only)
8 - clear capture 8 (M6 only)
9 - clear all captures
10 - initiate a new capture
•
Capture type:
selects sample rate and data resolution or indicates
selected sample rate and resolution. Range -1 to 5, default 0. -1
disables oscillography. See Table 8.1.
•
Pre-trigger:
specifies how much of the captured waveform
occurred before the triggering event. Range 0 to 100 per cent,
default 90%.
•
Reserved:
must be zero (0) on a write, returns 0.
•
Capture clear status:
Read-only bitfield that indicates which
capture numbers are clear. Bit 0 (LSB) corresponds to capture 1,
bit 1 to capture 2 and so on. For each bit, 1 indicates clear, 0
indicates not clear.
•
Capture ready status:
read-only bitfield that indicates which
capture numbers contain captures that are ready to read. Same
bit correspondence as above. For each bit, 1 indicates the
capture is ready, 0 indicates no capture or not yet ready. If a
client reads a capture that is not ready, -1 is returned for all data
points.
Содержание 1404-M4
Страница 1: ...Bulletin 1404 Powermonitor 3000 1404 M4 1404 M5 1404 M6 1404 M8 User Manual Allen Bradley HMIs ...
Страница 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Страница 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Страница 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Страница 277: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 23 Ladder Diagram Allen Bradley HMIs ...
Страница 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Страница 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Страница 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Страница 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Страница 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Страница 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Страница 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Страница 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Страница 355: ...Allen Bradley HMIs ...