Publication 1404-UM001D-EN-E - October 2004
Advanced Features
8-23
•
Channel number:
in the range 1 to 7 (1=V1, 2=I1, 3=V2, 4=I2,
5=V3, 6=I3, 7=I4)
•
Block number:
block number of the data contained in the table.
See above.
•
Transient capture identifier:
range 0 to 30,000, rolls over to 0
•
Transient capture data points:
see below
Transient Capture Data Points
The results table contains 20 data points for optional DeviceNet
communications or 50 data points for all other communications
options. Data points are numbered 1 to 20 or 1 to 50 in each block.
The block number ranges from 1 to 70 for DeviceNet and 1 to 28 for
all other communications options. The client calculates each data
point’s place in the transient capture using the following formula:
The total number of data points is 1400. Each data point is expressed
in calibrated analog-to-digital (A/D) converter counts with a resolution
of 8192 (13-bit w/sign). A client may calculate the primary-side
instantaneous voltage or current magnitude of each data point using
the following formula:
For example, consider the following capture:
•
N
datapoint_capture
N
block
1
–
(
)
N
datapoint_this_read
+
=
N
datapoint_capture
= the sequence number of the data point in the capture channel
N
block
= the block number
N
datapoint_this_read
= the data point number (1 to 20 or 1 to 50) in the current read
M
i
M
max rms
(
)
2
•
R
max
--------------------------------------
N
t
M
data
•
•
=
M
i
= instantaneous value of the voltage or current data point
M
(max rms)
= max rms magnitude
= 399.0 line-to-neutral volts for channels 1, 3 and 5
= 691.1 line-to-line volts for channels 1, 3 and 5
=10.6 amperes for channels 2, 4, 6 and 7
R
max
= maximum resolution
= 8192 for 13-bit w/sign
N
t
= PT or CT ratio
= PT or CT primary / PT or CT secondary
M
data
= value of the data point from Table A.46
Содержание 1404-M4
Страница 1: ...Bulletin 1404 Powermonitor 3000 1404 M4 1404 M5 1404 M6 1404 M8 User Manual Allen Bradley HMIs ...
Страница 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Страница 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Страница 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Страница 277: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 23 Ladder Diagram Allen Bradley HMIs ...
Страница 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Страница 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Страница 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Страница 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Страница 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Страница 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Страница 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Страница 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Страница 355: ...Allen Bradley HMIs ...