TE67X000002150 Ethernet Module 

 

Status and weight transfer using EtherNetIP 

 

IM-TE91K013-EN2 

9) Appendices 

9.1 Appendix A – Status Codes 

Status codes are shown as a 4 digit hex number. If more than one error condition is present the error 
codes are OR’ed together. 

 

CODE 

(Hex) 

CAUSE 

0001 

Invalid/missing ’sample’ ID 

Bad connection between TE67X000002029 analog module and load cell module.  

0002 

Load cell timeout  

Bad connection between load cell and load cell module. 

0004 

Load cell not synchronized 

Bad connection between load cell and load cell module. 

0008 

Hardware synchronization error 

Cable between load cell modules shorted or disconnected. 

0010 

Power failure 

Supply voltage to load cells is to low. 

0020 

Overflow in weight calculation 

Internal error in load cell module. 

0026 

No communication to a load cell 

 

Wrongly mounted BNC-connecter 

 

Defect cable 

 

Defect 2010 module 

 

Defect load cell

 

0040 

Invalid/missing ’latch’ ID 

Bad connection between TE67X000002029 analog module and load cell module.  

0080 

No answer from load cell module 

No data is received from load cell module. This can be caused by the removal of a load cell module, 
no power to the module or that the connection between load cell module and TE67X000002029 
analog module is broken. 

0100 

Reserved for future use 

0200 

Reserved for future use 

0400 

Reserved for future use 

0800 

No load cell modules answer 

Bad connection between TE67X000002029 analog module and load cell module. Not all telegrams 
from TE67X000002029 analog module are received in load cell module. 

1000 

Reserved for future use 

2000 

Reserved for future use 

4000 

Reserved for future use 

8000 

Wrong number of load cells 

The expected number of load cells found during power-on does not match the number indicated by 
the ”n.Lc.” parameter. If the ”n.Lc.” parameter setting is correct, it must be examined that all load 
cell module addresses are correct. 

 

 

Содержание TE67X000002150

Страница 1: ...ion manual TE67X000002150 Ethernet module Instruction manual no IM TE91K013 EN2 ESE02419EN Date of issue August 19 2014 First published March 6 2013 Status and weight transfer using EtherNetIP Origina...

Страница 2: ......

Страница 3: ...nt time 7 3 7 Filtering 8 4 Data Processing 9 4 1 Zeroing calibration and weight calculation 9 4 2 Corner calibration of weighing system 9 4 3 Calculation of uncalibrated system weight 10 4 4 System c...

Страница 4: ...Appendices 20 9 1 Appendix A Status Codes 20 9 2 Appendix B Setup with Terminal Interface 21 9 3 Appendix C Allen Bradley connection 25 9 4 Appendix D Omron connection 25 9 5 Appendix E Download of ne...

Страница 5: ...re effective at the date of printing However as continuous improvements are our policy we reserve the right to alter or modify any unit specification on any product without prior notice or any obligat...

Страница 6: ...ata listed in the current data sheet are engaging and must be complied with If the data sheet is not available please order or download it from our homepage http www alfalaval com 2 5 EtherNetIP speci...

Страница 7: ...ed integer format Furthermore bit 15 will be always ON while bit 14 will toggle ON and OFF with 1hz 500ms ON 500ms OFF LcStatus X is a word two bytes that constitute a register containing the actual s...

Страница 8: ...ers represented on 32 bit signed integer format Decimal Hexadecimal Binary MSB first 20000000 0xFECED300 11111110 11001110 11010011 00000000 2000000 0xFFE17B80 11111111 11100001 01111011 10000000 2000...

Страница 9: ...nding on switch settings Weight gram SW1 1 OFF SW1 2 OFF 1 gram SW1 1 ON SW1 2 OFF 1 10 gram SW1 1 OFF SW1 2 ON 1 100 gram SW1 1 ON SW1 2 ON 10 gram 1 0 1 10 100 0 123 4 123 1234 12340 12 12341 12341...

Страница 10: ...SW1 6 No Taps Frequency Damping Tavg 20ms Tavg 200ms OFF OFF OFF OFF 0 ON OFF OFF OFF 1 7 12 0 Hz 1 2 Hz 60dB OFF ON OFF OFF 2 9 10 0 Hz 1 0 Hz 60dB ON ON OFF OFF 3 9 12 0 Hz 1 2 Hz 80dB OFF OFF ON O...

Страница 11: ...hich it reads and stores the actual weight signals for the load cells of the actual system in corresponding zeroing registers LcZero x LcSignal x 3 After this the uncalibrated gross weight for load ce...

Страница 12: ...chieve a correct calibration of the system it is recommended that the used calibration load is at least 50 of the system capacity 3 Calculate the calibration factor that should be multiplied on the un...

Страница 13: ...6 The TE67X000002150 Ethernet module is connected to the EtherNetIP network using the RS45 Ethernet connector in the front panel 7 Power 24VDC is applied through the two pole connector J2 The EtherNet...

Страница 14: ...r using EtherNetIP IM TE91K013 EN2 6 Hardware description 6 1 TE67X000002150 overview The following figure is an overview of how a TE67X000002150 Ethernet system is made using four load cell interface...

Страница 15: ...C GNDin IMPORTANT The used power supply must be stable and free of transients It may therefore be necessary to use a separate power supply dedicated to the weighing system and not connected to any oth...

Страница 16: ...1 on the TE67X000002150 Ethernet module has these connections J1 CONNECTER FUNCTION J1 1 RS485 B DATA J1 2 RS485 A DATA J1 3 0 VDC GNDin 6 5 RS232 connector J4 The small 4 pole connector J4 at the bot...

Страница 17: ...is named SW2 and has the following function SWITCH FUNCTION Sw2 1 Sw2 8 Reserved for future use 6 8 Light Emitting Diodes LEDs The TE67X000002150 Ethernet module is equipped with a number of status l...

Страница 18: ...le may need replacing Flash ing Recoverable fault Configuration error DIP switch not set correct IP Address error or similar error Correct error and restart module OFF No power The power is disconnect...

Страница 19: ...Green RS232 TX RS232 data is transmitted D10 Red Power 3 3 VDC internal power supply is on 6 9 Hardware Self test During power on the TE67X000002150 Ethernet module will perform a hardware self test...

Страница 20: ...fy that all legs of the tanks all are in physical contact with load cells 7 2 Service Repair 7 2 1 Return Upon every return of the device no matter if for recalibration modifications or repair it is n...

Страница 21: ...t For further information please feel free to contact Alfa Laval Tank Equipment Alfa Laval Kolding A S 31 Albuen DK 6000 Kolding Denmark Registration number 30938011 Tel switchboard 45 79 32 22 00 Fax...

Страница 22: ...ed BNC connecter Defect cable Defect 2010 module Defect load cell 0040 Invalid missing latch ID Bad connection between TE67X000002029 analog module and load cell module 0080 No answer from load cell m...

Страница 23: ...range The default settings for IP address etc are These defaults can be altered by connecting the RS232 connector J4 to a COM port on a PC and starting a terminal emulation program like Hyper Terminal...

Страница 24: ...n press 2 to the Change Settings Menu displayed CHANGE SETTINGS MENU 1 change Mac address 2 select enable of Dhcp 3 change Ip address 4 change Subnet mask 5 change Gateway address 6 Return to Main Men...

Страница 25: ...etting To check all settings re power the device and in the Main Menu press 1 to select the System Info display looking like this SYSTEM INFO MAC Address 00 50 c2 c5 30 10 Use DHCP No use statically a...

Страница 26: ...ng the load cell signals like this LC signals 0000 22868 0000 23281 0000 24449 0000 8216 0000 22871 0000 23277 0000 24448 0000 8215 0000 22868 0000 23279 0000 24450 0000 8216 0000 22871 0000 23280 000...

Страница 27: ...6 8 bit 4 Set Output Assembly instance to 102 Size 2 8 bit 5 Set Configuration Assembly instance to 101 Size 1 8 bit 9 4 Appendix D Omron connection The supplied EDS file can be used in the Omron conf...

Страница 28: ...ial settings are set to Baudrate 9600 Databits 7 Parity Even Stopbits Flow control None 1 3 When the TE67X000002150 is powered the following will be displayed or press Enter one or more times until th...

Страница 29: ...9 Appendices continued 9 5 1 Download procedure 7 Once the Flash Loader Demonstrator is started the following screen should appear 8 Click the Next button to open the connection Once the connection is...

Страница 30: ...9 5 1 Download procedure 10 Ensure target indicates STM32_High density_384K and click the Next button to proceed causing the following screen to appear 11 Select Erase and ensure All is selected Perfo...

Страница 31: ...nued 9 5 1 Download procedure 12 Click the Back button in order to return to the following screen where the Erase option was selected 13 Now select Download to device and click the button and use the...

Страница 32: ...and verify process has been completed the screen will appear as follows 15 Click the Close button to terminate the Flash Loader Demonstrator program 16 Remove power from the TE67X000002150 module 17 S...

Страница 33: ...Instructio TE67X00 Status an IM TE91 10 E on manual 00002150 Ether nd weight transf K013 EN2 C Declara rnet Module fer using EtherN ation of c NetIP conformit ty P Page 31...

Страница 34: ...s the responsibility of the user of this document to comply with all applicable intellectual property laws Without limiting any rights related to this document no part of this document may be copied r...

Отзывы: