Page 20
Instruction manual
TE67X000002150 Ethernet Module
Status and weight transfer using EtherNetIP
IM-TE91K013-EN2
9) Appendices
9.1 Appendix A – Status Codes
Status codes are shown as a 4 digit hex number. If more than one error condition is present the error
codes are OR’ed together.
CODE
(Hex)
CAUSE
0001
Invalid/missing ’sample’ ID
Bad connection between TE67X000002029 analog module and load cell module.
0002
Load cell timeout
Bad connection between load cell and load cell module.
0004
Load cell not synchronized
Bad connection between load cell and load cell module.
0008
Hardware synchronization error
Cable between load cell modules shorted or disconnected.
0010
Power failure
Supply voltage to load cells is to low.
0020
Overflow in weight calculation
Internal error in load cell module.
0026
No communication to a load cell
•
Wrongly mounted BNC-connecter
•
Defect cable
•
Defect 2010 module
•
Defect load cell
0040
Invalid/missing ’latch’ ID
Bad connection between TE67X000002029 analog module and load cell module.
0080
No answer from load cell module
No data is received from load cell module. This can be caused by the removal of a load cell module,
no power to the module or that the connection between load cell module and TE67X000002029
analog module is broken.
0100
Reserved for future use
0200
Reserved for future use
0400
Reserved for future use
0800
No load cell modules answer
Bad connection between TE67X000002029 analog module and load cell module. Not all telegrams
from TE67X000002029 analog module are received in load cell module.
1000
Reserved for future use
2000
Reserved for future use
4000
Reserved for future use
8000
Wrong number of load cells
The expected number of load cells found during power-on does not match the number indicated by
the ”n.Lc.” parameter. If the ”n.Lc.” parameter setting is correct, it must be examined that all load
cell module addresses are correct.
Содержание TE67X000002150