Page 16
Instruction manual
TE67X000002150 Ethernet Module
Status and weight transfer using EtherNetIP
IM-TE91K013-EN2
6) Hardware description
(continued)
6.8 Light Emitting Diodes (LEDs)
The MS and NS LED’s can in conjunction with the table below be used for error finding.
Light
emit-
ting di-
ode
Color
Status Description
MS
Green
ON Normal Operation. Communication performed normally.
Flash-
ing
Standby State. The module needs supervision.
Red
ON Unrecoverable fault. A timer error, memory error or
other system error. The module may need replacing.
Flash-
ing
Recoverable fault. Configuration error, DIP-switch not set
correct, IP-Address error or similar error. Correct error and
restart module.
---
OFF No power. The power is disconnected or the module is
being restarted.
NS
Green
ON On-Line, Connection OK. The module is On-Line and a
connection with the master has been established.
Flash-
ing
On-Line, No Connection. The module is On-Line but no
connection to the master has been established.
Red
ON Critical Communication Error. The module has detected
an error that makes it impossible to communicate on the
network.
Flash-
ing
Communication Time-Out. One or more I/O connections
are in the Time-Out state.
---
OFF No power/Off-line. The device may not be powered.
Содержание TE67X000002150