29
Electrical installation
Type 8692, 8693
Circular plug M8 - 4-pole (process actual value) - only Type 8693
input
type
13)
pin
Wire
color
14)
configuration
switch
4 – 20 mA
- internally
supplied
1
2
3
4
brown
white
blue
black
+ 24 V transmitter supply
Transmitter output
GND
Bridge after GND
Switch
on left
4 – 20 mA
- externally
supplied
1
2
3
4
brown
white
blue
black
not assigned
Process
not assigned
Process actual -
Switch
on right
Frequency
- internally
supplied
1
2
3
4
brown
white
blue
black
+ 24 V sensor supply
Clock input +
Clock input - (GND)
not assigned
Switch
on left
Frequency
- externally
supplied
1
2
3
4
brown
white
blue
black
not assigned
Clock input +
Clock input -
not assigned
Switch
on right
Pt 100
(see infor-
mation
below)
1
2
3
4
brown
white
blue
black
not assigned
Process actual 1 (current feed)
Process actual 2 (GND)
Process actual 3 (compensation)
Switch
on right
Tab. 14: Circular plug M8 - 4-pole (process actual value) - Type 8693
For reasons of wire compensation connect the Pt 100 sensor
via 3 wires. Always bridge Pin 3 and Pin 4 on the sensor.
10.4. electrical installation devicenet
The Quickstart only describes the electrical installation of the posi-
tioner / process controller and the specification of the basic settings.
The settings of the bus communication are described in the
operating instructions for Type 8692 / 8693.
procedure:
→
Connect the positioner according to the tables.
The electrical connection module of types 8692 and 8693 features
a setscrew with nut which is used to connect the function earth (see
“Fig. 17: Connection DeviceNet”).
→
Connect the setscrew to a suitable grounding point. For
ensuring electromagnetic compatibility (EMC), make sure that
the cable is as short as possible (max. 30 cm, Ø 1.5 mm2).
When the supply voltage is applied, the positioner / process con-
troller is operating.
→
Make the required basic settings and actuate the automatic
adjustment of the positioner / process controller, as described in
the chapter entitled “11. Start-up Type 8692”.
The settings in the BUS.COMM menu item are described in
the operating instructions of type 8692 / 8693.