:0  REPlACIng COmPOnEntS 

This Chapter shows the easiest way of replacing compo

-

nents in an Alde Comfort boiler.

NOTE! Work on the automatic gas unit may only be 
carried out by Alde’s service department or authorised 
personnel. 

  

:1  REPlACIng thE COmPlEtE BuRnER  
 

unIt 

1.

  Close the main gas tap to the boiler.

.

  Remove the hatch on the control panel by opening it 

straight out and carefully bending it upwards in the 
centre so that the pegs are released (see chapter 6:12).

.

  Remove the lower front plate (see fig 12). Lever with a 

screwdriver in the groove on the bottom of the plate until 

the tabs are clear. Then pull outwards/downwards until 
the plate is free and can be removed. 

.

  Switch off the main current switch or remove the fuse on 

the control panel. Set the thermostat knob in the ignition 
position. Remove screw (fig 15 A) which holds the rod in 
the automatic knob. Press the knob down and carefully 
lift the rod from the knob. 

.

  Unfasten the springs (fig 13 A) which hold the sensor (fig 

13 B) and overheating protection (fig 13 C) and remove 
these from the boiler casing, se fig 14. Disconnect the 
ignition cable from the ignition transformer (fig 13 D), as 
well as the screw to the earthed connection (fig 15 B). 

.

  Remove the remainder of the screws, 13 off B6 x 9 

 

(fig 15 C) in the burner plate. 

7.

  Disconnect the inlet gas pipe to the automatic unit  

(fig 15 D) and remove the burner unit from the boiler, 
see fig 16.

8.

  Check that the front packing (fig 16 A) is intact before 

the burner unit is replaced. Fasten the burner unit and 
earth cable. Attach the inlet gas pipe to the burner unit 
and tighten. Install the overheating protection, sensor 
and ignition cable. Ensure that there is heat-conducting 
paste between the sensor and the boiler. Check that 
the capillary tube to the boiler thermostat, overheating 
protection and ignition cable are correctly installed to 
the right of the automatic unit, and are not trapped or 
damaged. 

9.

  Fit the rod in the automatic knob and insert the screws. 

Carefully turn the knob to the stop position and check 
that the micro-switch ”clicks”, switches off. 

10.

 Fit the fuse and switch on the main switch. Turn the 

thermostat knob to the ignition position and check that 

the indicator lamp flashes and that there is a spark at 
the spark plug. Press down the thermostat knob and 
turn to no. 7 on the scale. Check that the arm of the 
micro-switch does not drag against the knob hub. (If 
necessary adjust the micro-switch, see Chapter 6:10). 

Turn to the stop position and check that the spark is 

switched off and that the lamp stops flashing. 

11.

 Install the lower front plate (fig 12), push the upper 

parts under the edge of the control box, press the plate 
inwards/downwards so that the tabs grip the boiler foot. 
Fit and close the hatch.  

1. 

Open the main gas tap to the boiler. Remove the hose 
from the reducing valve on the gas tube, fit a manome

-

ter and pressure test the LPG installation in accordance 

with instructions. Attach the hose, open the gas pipe 
and test-run the boiler. Check that sparks cease when 

the boiler lights! 

Содержание Comfort 2923

Страница 1: ...SE GB Servicemanual Comfort 2923 2928 ...

Страница 2: ... The handbook may also be of assistance in ordering spare parts in understanding how the boilers operate and how they are installed It also includes general information on how our heating systems are designed and some information on LPG and LPG installations We hope that you will find this manual very useful and that it will save you time during service and fault finding on our boilers Alde Intern...

Страница 3: ...th liquid Ensure that the caravan or boat is level and check that the air screws and drainage tap are closed Remove the upper front plate on the boiler Then slacken the plastic cap on the circulation pump and lift up the pump Then carefully pour the glycol mix into the expansion chamber When the system is being filled air pockets may form depending on how the pipe system was installed A good indic...

Страница 4: ... with a characteristic smell is added it smells like sulphur It can be stored in the cylinder for an unlimited time without any deterioration in quality LPG is non toxic but if bottled in concentrated form it will give rise to some anaesthetic effects breathing difficulties and symptoms of suffocation and therefore may be avoided The LPG cylinder contains LPG both in liquid and in gas form When th...

Страница 5: ...t demands heat the circula tion pump starts The liquid in the system then begins to circulate and cold water enters the boiler A sensor fitted in the water jacket senses that the water is colder than the temperature set on the boiler thermostat The pilot light ignites the main burner which heats up the liquid and circu lates it round the system When the warmth in the caravan reaches the temperatur...

Страница 6: ... thermostat Switch N K Switch 12 230 V 12 V Circula tion pump Relay on el cartridge for 230 V circ pump 12 V Fuse ON OFF Room thermostat Switch N Switch 1 kW 2 kW 1050 W 1050 W 0 Circuit board on el cartridge 4 0 Flow chart LPG Boiler Circulation pump Output electrical cartridge ...

Страница 7: ... hub wipe any excess away If the knob feels springy does not remain in the position in which it is released lubricate the o ring very sparingly with grease Replace the thermostat knob NOTE When the thermostat knob is removed it must be re fitted in the same position otherwise the temperatures setting will change 5 1 General fault finding This guide to general fault finding should be useful in rapi...

Страница 8: ... 6 The pilot burner must burn with a clear blue flame without yellow peaks Check that the tip of the thermo element is in the centre of the pilot flame Adjust if necessary by carefully bending the bracket Check and if necessary clean the contact surfaces in the joint nipple between the thermo element the over heating protection and the magnetic insert in the automa tic unit and that the nuts on th...

Страница 9: ...medial action Check in the expansion chamber that the heating system is filled to the correct level with 40 glycol mix Check that the sensor is attached with heat conducting paste between the boiler and the sensor and that the capillary tube is not damaged Turn the thermostat knob to position 1 and check that the main flame goes out and if it does lower the max temp setting If the flame does not g...

Страница 10: ...cts 5 14 Circulation pump does not start Cause No voltage to boiler Switch on room thermostat off Temperatures setting too low room thermostat has trip ped Room thermostat wrongly calibrated or faulty Switch for circulation pump on control panel in wrong position faulty Cable connections not attached to motor Pump motor faulty Remedial action Check voltage and fuse Check that the switch on the roo...

Страница 11: ...e boiler see fig 16 8 Check that the front packing fig 16 A is intact before the burner unit is replaced Fasten the burner unit and earth cable Attach the inlet gas pipe to the burner unit and tighten Install the overheating protection sensor and ignition cable Ensure that there is heat conducting paste between the sensor and the boiler Check that the capillary tube to the boiler thermostat overhe...

Страница 12: ... temperature With the sensor in a water bath temperature 70 C turn the thermostat knob from position 7 towards 1 switching ticking occurs between positions 6 4 On burner unit with serial numbers 28798 the water bath must be at 65 C 6 Press in the plastic plug fit the rod with the plastic adap ted NOTE The figure 5 must be visible in the hole Turn to the stop position check that the spark shuts off...

Страница 13: ...t fig 19 A from the joint nipple fig 19 B below the automatic unit and pull out the thermo ele ment through the cable opening on the front plate of the burner unit 4 Check the contact surfaces on the joint nipple and the overheating protection clean or replace joint nipple if necessary 5 Install the new thermo element in reverse order NOTE The tip of the thermo element must be pres sed up as far a...

Страница 14: ...te of the burner unit 3 Fit the new ignition cable and connect it to the spark plug and ignition transformer Don t firget the silicone sleeve 4 Push the burner unit into the boiler and install it in accor dance with Chapter 6 1 Check that the capillary tube to the boiler thermostat the temperature limiter and the ignition cable are correctly aligned to the right of the automatic unit and are not t...

Страница 15: ... inner screw on the micro switch fig 27 A a couple of turns adjustment screw remove the outer screw fig 27 B Removed the micro switch note the location of the cables move cables and adjustments screws to the new switch fit and tighten the screws 5 Fit the rod in the automatic knob and replace the screw 6 Adjustment Set the thermostat knob in the ignition position Slacken the adjustment screw and p...

Страница 16: ...e top cover of the boiler Switch on the main power switch turn the ther mostat knob to the ignition position and check that the indicator lamp flashes and that there are sparks at the spark plug If necessary adjust the micro switch Carry out a complete functional check on the control panel to ensure that all functions are OK Test start the boiler and check that the thermostat knob can rotate freel...

Страница 17: ...35 B inwards 6 Transfer the ignition transformer to the new control box note the location of the cables fit the cables 7 Fit the connection block and the earthed connections in the top cover earth cable on the burner unit the cables to the 12 V circulation pump as well as the connection block to the electrical cartridge 8 Install the control box by pressing it into the metal sweep of the boiler un...

Страница 18: ...on the connection pipe before the vessel is fastened properly Then pressed the new expansion vessel down on to the pipe bend and tighten the nut fig 38 B a few turns Attach the support fig 37 A and then tighten the nut Fit the hoses 9 Close the drainage tap and top up the liquid in the expansion vessel Lower the circulation pump into the vessel and screw on the plastic nut fig 36 B Attach the pump...

Страница 19: ...Red Black Fuse 1 A Red Black _ 12 V DC Battery Room thermostat Yellow P Red White N K 12 220 Pump Blue Grey Red 275 ohm 275 ohm 275 ohm 230 pump 1000 W 1000 W Electrical cartridge N 1000 W 2000 W Red Yellow Black K Black Ignition transformer Micro switch Green Yellow L _ ...

Страница 20: ...20 20 8 0 Exploded view 2923 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 ...

Страница 21: ...21 21 9 0 Exploded view 2928 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 31 31 33 34 35 36 30 41 40 39 38 37 40 24 42 43 44 45 ...

Страница 22: ...22 22 10 0 Exploded view 2923 2928 980 1 2 3 4 5 9 10 11 12 13 14 15 17 18 19 20 21 22 23 24 25 26 27 28 29 32 33 34 8 30 31 7 6 16 ...

Страница 23: ...cable 39 2923 112 Control box 2928 page 21 No Part no Designation 1 2923 154 Front plate upper complete 2 2923 111 Hatch 3 2923 153 Front plate lower complete 4 2930 423 Plastic nut 5 2928 405 Circulation pump complete Airpax 6 2930 413 Expansion vessel complete 7 2923 200 Control box complete 4 switches 8 2923 210 Panel complete 4 switches 9 2923 114 Micro switch 10 2923 113 Knob 11 2923 121 Knob...

Страница 24: ...15 2923 208 Ignition cable 16 2920 230 Overheating protection 17 2923 125 Ignition transformer compl 18 2930 133 Spring 19 2930 236 Front packing 20 2923 301 Boiler casing for 2959 warm water supply 2928 201 Boiler casing for 2959 warm water supply 21 2923 025 Bracket 22 2923 173 Spacer 23 2923 174 Spacer strip 24 2920 123 Plug 25 2920 167 Plate sweep 26 2923 197 Escutcheon plate 27 2930 134 Top c...

Страница 25: ... Motor to 2920 410 Dunker 1 2 3 2923 400 Burner unit 2923 980 and 2928 980 1 2920 230 Overheating protection 2 2923 207 Spark plug 3 2923 201 Pilot burner 4 2923 114 Micro switch not mod 980 5 2920 245 Thermo element 6 2900 271 Joint plug 1 2 3 4 5 6 1 2921 216 Ignition transformer compl 2923 980 and 2928 980 2 2923 225 Ignition transformer compl 2923 and 2928 3 2923 417 Ignition cable 2923 980 oc...

Страница 26: ...923 200 Control box compl 3 2921 217 Fuse 1 A 4 2923 115 Ignition lamp 1 2923 112 Control box 2 2923 111 Hatch 1 2 1 3 2 4 1 2921 215 Switch ON OFF 2 2921 219 Switch ON OFF ON 3 2920 215 Control box 2923 2928 980 4 2923 410 Panel 2923 2928 980 4 3 2 1 ...

Страница 27: ...27 27 ...

Страница 28: ...Service 2923 2928 Rev 916 GB Alde International Systems AB Wrangels allé 90 Box 11066 S 291 11 Färlöv Sweden Tel 46 0 44 712 70 Fax 46 0 44 718 48 www alde se info alde se ...

Отзывы: