Vol. VI-B-18
Alcatel-Lucent
to the node. Confirm by measuring the -48 Vdc supply with a voltmeter.
If the alarm is not supported by other indications and measurement, the
voltage sensing circuit is faulty. Replace the RAC.
ODU -48V Supply
ODU -48 volt supply out of tolerance. This is a warning alarm.
Probable Cause
Main 48 Vdc power supply is outside limits of -40.5 to -60 Vdc, or the voltage
drop on the ODU cable is excessive due to poor connections or a combination of
poor connections and a low -48Vdc power supply.
Recommended Actions
1.
Check for other alarms to determine how critical the alarm is. In particular,
check the NCC/IDU -48V alarm, and for a Node check the RAC -48V Supply
alarm. Depending on the malfunction, the node may otherwise operate
satisfactorily.
2.
Check the -48V ODU Supply voltage in the CT Performance screen, and use
a voltmeter to measure the -48V supply at the front panel power connector.
• If the -48V supply is normal, (and for the Node there is no RAC -48V
Supply alarm), suspect excessive voltage drop on the ODU cable, or the
voltage sensor circuit in the ODU.
3.
If a cable related problem is suspected check the ODU cable, connectors, and
connector weatherproofing. Disconnnect the cable at the ODU and apply a
short-circuit between inner and outer conductors. Measure the resistance at
the node end. For 9913 coax, resistance should be not more than 0.01 ohms
per meter (0.003 ohms per ft). Bear in mind that for a 100m run, a resistance
of about 1 ohm is expected so care must be taken to ensure correct
measurement.
4.
If there are no other alarms, the node is operating normally, and the ODU
cable is OK, then the voltage sensor circuit and/or its processing in the ODU
is the likely cause. Replace the ODU.
Additional Information
CAUTION
: use extreme care if attempting to measure voltage at the RAC/IDU
front panel ODU connector, or at the ODU end of the cable. Inadvertently
shorting the inner to outer will blow the surface-mounted PCB fuse on the RAC,
which is not a field replaceble item. Repair will not be covered by warranty.
Содержание 9500 MXC
Страница 5: ......
Страница 6: ......
Страница 28: ......
Страница 29: ...Volume I 9500 MXC Health and Safety Requirements...
Страница 30: ......
Страница 39: ...Volume II 9500 MXC System Description...
Страница 40: ......
Страница 56: ...Chapter 1 9500 MXC System Overview Vol II 1 16 Alcatel Lucent...
Страница 94: ...Chapter 2 9500 MXC Terminals Vol II 2 38 Alcatel Lucent...
Страница 218: ...Chapter 4 Outdoor Units Vol II 4 4 Alcatel Lucent...
Страница 236: ...Chapter 6 9500 MXC Performance and Diagnostic Features Vol II 6 14 Alcatel Lucent...
Страница 237: ...Volume III 9500 MXC Installation...
Страница 238: ......
Страница 268: ...Chapter 2 Outdoor Installations Vol III 2 26 Alcatel Lucent Figure 2 16 BGXZ Surge Suppressor...
Страница 282: ...Chapter 2 Outdoor Installations Vol III 2 40 Alcatel Lucent...
Страница 300: ...Chapter 4 Installing the IDU Vol III 4 6 Alcatel Lucent...
Страница 321: ...Volume IV 9500 MXC CT...
Страница 322: ......
Страница 326: ...Chapter 1 9500 MXC CT Introduction Vol IV 1 4 Alcatel Lucent Figure 1 3 Standardized 9500 MXC Logos...
Страница 332: ...Chapter 1 9500 MXC CT Introduction Vol IV 1 10 Alcatel Lucent...
Страница 362: ...Chapter 2 Setting Up 9500 MXC CT Vol IV 2 30 Alcatel Lucent...
Страница 368: ...Chapter 3 Installation and Configuration Process Vol IV 3 6 Alcatel Lucent Figure 3 1 9500 MXC CT Menu Bar Menus...
Страница 374: ...Chapter 3 Installation and Configuration Process Vol IV 3 12 Alcatel Lucent...
Страница 384: ...Chapter 4 Licensing Vol IV 4 10 Alcatel Lucent...
Страница 388: ......
Страница 390: ......
Страница 508: ...Chapter 8 Protection Vol IV 8 26 Alcatel Lucent...
Страница 542: ...Chapter 10 Networking Configuration Vol IV 10 18 Alcatel Lucent...
Страница 546: ......
Страница 550: ...Chapter 12 Date and Time Configuration Vol IV 12 4 Alcatel Lucent...
Страница 558: ...Chapter 13 Software Management Vol IV 13 8 Alcatel Lucent...
Страница 561: ...9500 MXC User Manual 3DB 23063 ADAA Rev 004 July 2007 Vol IV 14 3 Figure 14 2 Login Screen for Admin...
Страница 562: ......
Страница 632: ...Chapter 15 Diagnostics Vol IV 15 70 Alcatel Lucent Figure 15 27 Example Parts Screen...
Страница 636: ...Chapter 15 Diagnostics Vol IV 15 74 Alcatel Lucent...
Страница 637: ...Volume V Commissioning and Troubleshooting...
Страница 638: ......
Страница 688: ...Chapter 2 9500 MXC Troubleshooting Vol V 2 32 Alcatel Lucent Terminal FAN Alarm Hierarchy FAN Hardware Fan Failure FAN...
Страница 699: ...Volume VI Appendices...
Страница 700: ......
Страница 706: ...Vol VI A 6 Alcatel Lucent Figure A 2 Excerpt from a Circuit Allocation Sheet for the Example Ring in Figure A 1...
Страница 791: ...9500 MXC User Manual 3DB 23063 ADAA Rev 004 July 2007 Vol VI B 65...
Страница 792: ......
Страница 826: ......
Страница 836: ...Vol VI D 10 Alcatel Lucent Figure D 3 Static Routing Screen for Node B in Figure D 2 3 192 168 2 1 Lyons Dpt...
Страница 846: ...Vol VI D 20 Alcatel Lucent...
Страница 856: ...Vol VI E 10 Alcatel Lucent...
Страница 873: ...9500 MXC User Manual 3DB 23063 ADAA Rev 004 July 2007 Vol VI F 17...
Страница 874: ......