9500 MXC User Manual
3DB 23063 ADAA - Rev 004 July 2007
Vol. III-3-5
Installing an INU
To install an INU:
1.
Fit the rack mounting ears to the chassis with the grounding stud to left or
right side for the most direct ground wire path to the rack ground bar.
2.
Locate the INU/INUe in the equipment rack and secure it using four No.12
Phillips dome-head screws from the IDC installation kit.
3.
Ground the INU/INUe from the grounding stud to the rack/frame ground bar
using a length of 4 mm
2
(AWG 12) green PVC insulated stranded copper wire
with a suitably sized ground lug at each end (supplied by the installer).
4.
If the equipment rack/frame requires grounding, use 16 mm
2
(AWG 6) wire
from its ground bar to the station ground.
5.
Install the plug-ins in their assigned slot positions, and check that their front
panels are flush-fitted (not protruding) and held secure by their fasteners.
Ensure unused slots are covered by blanking panels. Refer to Plug-in Slot
Configuration on page 3-8, and Plug-in Installation Requirements on
Power Supply Compliance and
Loading
The dc power supply must be UL or IEC compliant for a -48 Vdc SELV output
(60 Vdc maximum).
Check to ensure that connection of a 9500 MXC system to an existing dc
supply does not overload the supply, circuit protection devices and wiring.
Where a new dc power supply is to be installed for a 9500 MXC Node, the
power supply must be rated to supply:
• 12.5 A for the INU
• 25 A for the INUe
Grounding
The INU must be grounded to the station or master ground, which must be the
same ground as used for the dc power supply. Normally this is achieved by
grounding the INU to the ground bar in its equipment rack or frame. This bar
is most often located to one side of the rack or at rack top or bottom. In turn,
the ground bar is grounded to the station ground.
Function/Requirement
Details
Do not assume that an existing rack or mounting frame is correctly grounded.
Always check the integrity of the ground connections, which must include a check
through to the master ground for the station, which should be located at the point
of cable entry to the equipment building.
Содержание 9500 MXC
Страница 5: ......
Страница 6: ......
Страница 28: ......
Страница 29: ...Volume I 9500 MXC Health and Safety Requirements...
Страница 30: ......
Страница 39: ...Volume II 9500 MXC System Description...
Страница 40: ......
Страница 56: ...Chapter 1 9500 MXC System Overview Vol II 1 16 Alcatel Lucent...
Страница 94: ...Chapter 2 9500 MXC Terminals Vol II 2 38 Alcatel Lucent...
Страница 218: ...Chapter 4 Outdoor Units Vol II 4 4 Alcatel Lucent...
Страница 236: ...Chapter 6 9500 MXC Performance and Diagnostic Features Vol II 6 14 Alcatel Lucent...
Страница 237: ...Volume III 9500 MXC Installation...
Страница 238: ......
Страница 268: ...Chapter 2 Outdoor Installations Vol III 2 26 Alcatel Lucent Figure 2 16 BGXZ Surge Suppressor...
Страница 282: ...Chapter 2 Outdoor Installations Vol III 2 40 Alcatel Lucent...
Страница 300: ...Chapter 4 Installing the IDU Vol III 4 6 Alcatel Lucent...
Страница 321: ...Volume IV 9500 MXC CT...
Страница 322: ......
Страница 326: ...Chapter 1 9500 MXC CT Introduction Vol IV 1 4 Alcatel Lucent Figure 1 3 Standardized 9500 MXC Logos...
Страница 332: ...Chapter 1 9500 MXC CT Introduction Vol IV 1 10 Alcatel Lucent...
Страница 362: ...Chapter 2 Setting Up 9500 MXC CT Vol IV 2 30 Alcatel Lucent...
Страница 368: ...Chapter 3 Installation and Configuration Process Vol IV 3 6 Alcatel Lucent Figure 3 1 9500 MXC CT Menu Bar Menus...
Страница 374: ...Chapter 3 Installation and Configuration Process Vol IV 3 12 Alcatel Lucent...
Страница 384: ...Chapter 4 Licensing Vol IV 4 10 Alcatel Lucent...
Страница 388: ......
Страница 390: ......
Страница 508: ...Chapter 8 Protection Vol IV 8 26 Alcatel Lucent...
Страница 542: ...Chapter 10 Networking Configuration Vol IV 10 18 Alcatel Lucent...
Страница 546: ......
Страница 550: ...Chapter 12 Date and Time Configuration Vol IV 12 4 Alcatel Lucent...
Страница 558: ...Chapter 13 Software Management Vol IV 13 8 Alcatel Lucent...
Страница 561: ...9500 MXC User Manual 3DB 23063 ADAA Rev 004 July 2007 Vol IV 14 3 Figure 14 2 Login Screen for Admin...
Страница 562: ......
Страница 632: ...Chapter 15 Diagnostics Vol IV 15 70 Alcatel Lucent Figure 15 27 Example Parts Screen...
Страница 636: ...Chapter 15 Diagnostics Vol IV 15 74 Alcatel Lucent...
Страница 637: ...Volume V Commissioning and Troubleshooting...
Страница 638: ......
Страница 688: ...Chapter 2 9500 MXC Troubleshooting Vol V 2 32 Alcatel Lucent Terminal FAN Alarm Hierarchy FAN Hardware Fan Failure FAN...
Страница 699: ...Volume VI Appendices...
Страница 700: ......
Страница 706: ...Vol VI A 6 Alcatel Lucent Figure A 2 Excerpt from a Circuit Allocation Sheet for the Example Ring in Figure A 1...
Страница 791: ...9500 MXC User Manual 3DB 23063 ADAA Rev 004 July 2007 Vol VI B 65...
Страница 792: ......
Страница 826: ......
Страница 836: ...Vol VI D 10 Alcatel Lucent Figure D 3 Static Routing Screen for Node B in Figure D 2 3 192 168 2 1 Lyons Dpt...
Страница 846: ...Vol VI D 20 Alcatel Lucent...
Страница 856: ...Vol VI E 10 Alcatel Lucent...
Страница 873: ...9500 MXC User Manual 3DB 23063 ADAA Rev 004 July 2007 Vol VI F 17...
Страница 874: ......