21
If you press on “Measured” you will see the current value:
You can click on RAW and see the current value or you can write the theoretical value of the
sensor output corresponding to the measurement.
The “Calibrated” button is used to test if your calibration table is correct. Note that you must
click on “Save” before making the test.
Example:
You have saved the following calibration table:
MEASURED
(Ohms)
VALUE
(Tª) (ºC)
10
15
100
50
180
95
We assume that the sensor manufacturer indicates these values. In this way to 70 ºC we must
have a measure of 140 Ohms. You switch on the engine that you have 140 Ohms (you are
pressing on Measured until that value), then press “Calibrated” and see the value, if it is about
70ºC, the calibration table is correct.
Note that X-axis values (MEASURE) must increase, from smallest to largest value