5.2 Visual Indicators
The PD8(F) has one LED to indicate status of the input voltage selected for the outputs.
The LED lights when there is voltage available to the outputs.
JP1
D2
B2
B1
+OUT3-
+OUT4-
+OUT3-
+OUT4-
+OUT5-
+OUT5-
+OUT6-
+OUT6-
DC
Figure 5.2.1
5.3 Troubleshooting
Verify jumper JP1 is present and
set properly
Jumper missing
Verify proper setting of jumper
JP1
Jumper set improperly
Check the selected power
supply and ABC cable
No voltage on the voltage buss
selected
LED not lit
Check power supply
Power supply outputting
incorrect voltage
Verify proper jumper setting
Incorrect voltage buss selected
Incorrect voltage on output
Check output wiring and
remove load for 30 seconds to
reset
Tripped output PTC (PD8)
Check output wiring and
replace fuse
Blown output fuse (PD8F)
Verify the power supply
No voltage supply
Verify jumper present
Missing jumper
Verify proper jumper setting
Jumper setting incorrect
No voltage on output
Solution
Possible Cause
Condition
PD8(F) Installation Instructions
10/27/2006, 1:58:40 PM
52-326 Rev B.01